Benutzeranleitung / Produktwartung NI 9475 des Produzenten National Instruments
Zur Seite of 24
OPERATING INSTRUCTIONS AND S PECIFICATIONS NI 9475 8-Channel, 60 V, High-Speed , Sourcing Digital Output Module ni.com/manuals Deutsch Français.
NI 9475 Operating I nstruction s and Specificati ons 2 ni.com This doc u ment describes ho w to u se the National Instr u ments 9475 and incl u des specif ications and pin assignments for the NI 9475. Vi s i t ni.com/info and enter rd s oftwarever s ion to determine which software yo u need for the mod u les yo u are u sing.
© National Inst ruments Corp. 3 NI 9475 Operating Instructi ons and Specific ations Safety Guidelines Operate the NI 9475 only as described in these operating instr u ctions. Hot Surface This icon denotes that the component may be hot. T o u ching this component may res u lt in bodily inj u ry .
NI 9475 Operating I nstruction s and Specificati ons 4 ni.com Caution S u bstit u tion of components may impair s u itability for Class I, Division 2. Caution For Zone 2 applications, install the system in an enclos u re rated to at least IP 54 as defined b y IEC 60529 an d EN 60529 .
© National Inst ruments Corp. 5 NI 9475 Operating Instructi ons and Specific ations Special Conditions fo r Marine Appli cations Some mod u les are Lloyd’ s Re gister (LR) T ype Approv ed for marine applications. T o verify Llo yd’ s Register cert ification, visit ni.
NI 9475 Operating I nstruction s and Specificati ons 6 ni.com Connecting the NI 9475 The NI 9475 has a 25-pin DSUB connector that pro vides connections for eight digital o u tp u t channels.
© National Inst ruments Corp. 7 NI 9475 Operating Instructi ons and Specific ations Each channel of the NI 9475 has a DO pin to which yo u can connect a dev ice.
NI 9475 Operating I nstruction s and Specificati ons 8 ni.com Yo u can directly connect the NI 9475 to a va riety of ind u strial de vices s u ch as solenoids, motors, act u ators, relays, and lamps. Make s u re the devices yo u connect to the NI 9475 are co mpatible with the o u tp u t specif ications of t he mod u le.
© National Inst ruments Corp. 9 NI 9475 Operating Instructi ons and Specific ations Increasing Current Drive Each channel ha s a contin u o u s o u tp u t c u rrent of 1 A. If yo u want to increase the o u tp u t c u rrent to a device, yo u can connect any n u mber of channels together in parallel.
NI 9475 Operating I nstruction s and Specificati ons 10 ni.com I/O Protection The NI 9475 is short-circ u it proof in accordance with IEC 1131-2 and provides o verc u rr ent protection.
© National Inst ruments Corp. 11 NI 9475 Operating Instructi ons and Specific ations Higher inr u sh c u rrents that exist for less than the trip time do not trip the protec tion circ u itry .
NI 9475 Operating I nstruction s and Specificati ons 12 ni.com ove rc u rrent condition occ u rs. A channel LED may be on ev en if the channel is of f beca u se of an ov erc u rrent condition. T o determine if the channel is in an overc u rrent state, meas u re the voltage between DO and V s u p .
© National Inst ruments Corp. 13 NI 9475 Operating Instructi ons and Specif ications s u pport for sleep mode. Refer to the softw are help for information abo u t enabling slee p mode. V isit ni.com/info and enter c s erie s doc for information abo u t C Series doc u menta tion.
NI 9475 Operating I nstruction s and Specificati ons 14 ni.com O u tp u t impedance ( R 0 ) .................. ... 0.14 Ω max Contin u o u s o u tp u t c u rrent ( I 0 ), per channel .......... ........... ........... ........ 1 A max O u tp u t voltage .
© National Inst ruments Corp. 15 NI 9475 Operating Instructi ons and Specific ations MTBF .......... ........... .................. ........ 1,096,296 ho u rs at 25 °C; Bellcore Iss u e 6, Method 1, Case 3, Limited P art Stress Method Note Contact NI for Bellcore MTBF specifications at other temperat u res or for MIL-HDBK-21 7F specifications.
NI 9475 Operating I nstruction s and Specificati ons 16 ni.com Safety Maximum Voltage 1 Connect only v oltages that are within the follo wing lim its. V s u p -to-COM.
© National Inst ruments Corp. 17 NI 9475 Operating Instructi ons and Specific ations Isolation Voltages Channel-to-channel ...... ............. ........ No isolation betwe en channels Channel-to-earth gro u nd Contin u o u s ................... .....
NI 9475 Operating I nstruction s and Specificati ons 18 ni.com Hazardous Locations U.S. (UL) ........ ........... ........... ........... . Class I, Di vision 2, Gro u ps A, B, C, D, T4; Class I, Zone 2, AEx nA IIC T4 Canada (C-UL) .......... ........
© National Inst ruments Corp. 19 NI 9475 Operating Instructi ons and Specific ations Operating h u midity (IEC 60068-2-56)....... ........... ............ 10 to 90% RH, noncondensing Storage h u midity (IEC 60068-2-56)....... ........... ............
NI 9475 Operating I nstruction s and Specificati ons 20 ni.com Electromagnetic Compatibility This prod u ct is designed to meet the req u ire ments of the follo wing standards of EMC for electrical eq.
© National Inst ruments Corp. 21 NI 9475 Operating Instructi ons and Specific ations Note Refer to the Declaration of Co nformity (DoC) for this prod u ct for any additional reg u latory compliance information. T o obtain the DoC for this prod u ct, visit ni.
NI 9475 Operating I nstructions and Specifications 22 ni .com Waste Electrical and Electronic Equipment (WEEE) EU Customers At t he end of their life cycl e, all prod u cts must be sent to a WEEE re c ycling center . For more information abo u t WEEE recycling ce nters and National Instr u ments WEEE initiati ves, visit ni.
© National Inst ruments Corp. 23 NI 9475 Operating Instructions and Specific ations Where to Go for Support The National Instr u ments W eb site is yo u r complete reso u rce for technical s u pport.
© 2007–2008 Nati onal Instruments Corp. All rights reserved. 374711C-01 Feb08 National Instruments, NI, n i.com, and LabVIEW are trademarks of National Instruments C orporation. Refer to the Terms of Use section on ni.com/legal for more information about National Instruments trademarks.
Ein wichtiger Punkt beim Kauf des Geräts National Instruments NI 9475 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie National Instruments NI 9475 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für National Instruments NI 9475 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von National Instruments NI 9475 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über National Instruments NI 9475 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon National Instruments NI 9475 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von National Instruments NI 9475 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit National Instruments NI 9475. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei National Instruments NI 9475 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.