FieldPoint ™ is a trademark of National Instruments Corporation. Product a nd company names mentioned herein are trad emarks or trade na mes of their resp ective companies. 321904B-01 © Copyright 1998, 1999 National Instruments Corp. All rights reserved.
FP-RLY-420 2 www.natinst.com module. The maximum number of terminal bases per bank multiplied by 1 watt is the total po wer the network module can supply . For e xample, an FP-1000 or FP-1001 can support nine terminal bases (9*1 W = 9 W). Next, refer to the specif ications section in the operating instructions for the I/O modules.
© National Instruments Corp. 3 FP-RLY-420 Field Wiring The terminal base has connections for each of th e eight relay channels and an extern al supply to po wer f ield de vices. Each relay channel of the FP-RL Y -420 has two terminals: N.O. (Normally Open) and I.
FP-RLY-420 4 www.natinst.com Figures 2a and 2b sho w examples of basic wiring connections. Figure 2. Basic Field Connection (T wo Channels Shown) Relay Output Circuit The outputs of the FP-RL Y -420 consist of Form A electromechanical relays. The po wer -up state is off (open) to ensure safe installation.
© National Instruments Corp. 5 FP-RLY-420 Figure 3 shows the diagram of one channel’ s relay output circuit. Figure 3. Relay Output Circuit The maximum switching capacity of each relay is 3 A up to 250 V A C or 35 VDC. T o switch greater DC v oltages, refer to Figure 4.
FP-RLY-420 6 www.natinst.com In addition, the FP-RL Y -420 contains its ow n internal protection MO V to preve nt e xcessi vely high voltage from being applied across the contacts.
© National Instruments Corp. 7 FP-RLY-420 Diode Circuit CR Circuits Varistor Circuit Diagram Notes Use in DC applications only . Compared to RC type, circuit delays release time (2 to 5 times v alues stated in catalog). For larger v oltages, use diode with rev erse breakdown 10 times circuit voltage and forward load ci rcuit.
FP-RLY-420 8 www.natinst.com In-Rush Current The type of load and its in -rush current characteristics, together with switching frequency , can cause contact welding. F or loads with in-rush current, measure the steady state current and in-rush current to determine the proper relay .
© National Instruments Corp. 9 FP-RLY-420 After the module has been inserted into a terminal base ( and po wer is applied), the green POWER indicator lights and the FP-RL Y -420 informs the network mod ule of its presence.
FP-RLY-420 10 www.natinst.com •D o not share the external supply voltages (V and C on the terminal base) with other de vices (including other FieldPoint de vices) unless those devices are also isolated from human contact.
© National Instruments Corp. 11 FP-RLY-420 Maximum switching frequenc y Mechanical ................... ............. . 20 operations per second Electrical..................................... 1 operation per second at maximum load Relays operate time.
Mechanical Dimensions Figure 6 sho ws the mechanical dimensions of the FP-RL Y -420 installed onto a terminal base. Dimensions are gi ven in inches [millimeters].
Ein wichtiger Punkt beim Kauf des Geräts National Instruments FP-RLY-420 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie National Instruments FP-RLY-420 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für National Instruments FP-RLY-420 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von National Instruments FP-RLY-420 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über National Instruments FP-RLY-420 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon National Instruments FP-RLY-420 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von National Instruments FP-RLY-420 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit National Instruments FP-RLY-420. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei National Instruments FP-RLY-420 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.