Benutzeranleitung / Produktwartung FP-CTR-502 des Produzenten National Instruments
Zur Seite of 22
323324B-01 June 2003 © 2002–2003 Nationa l Instruments Corp. A ll rights res erved. FieldPoint™, Nati onal Instruments™, NI™, and ni.com™ are trademarks of N ational Instruments Corpo ration. Product and company names ment ioned herein are trademark s or trade names of their respecti ve companies.
FP-CTR-502 and cFP-CTR-502 2 ni.com Installing the FP-CTR-502 The FP-CTR-502 mounts on a FieldPoint terminal base (FP-TB- x ), which provides operating po wer to the module. Instal ling the FP-CTR-502 onto a po wered termin al base does not disrupt the operation of the FieldPoint bank.
© National Instruments Corp. 3 FP-CTR-502 and cFP-CTR-502 2. Press firmly to seat the cFP-CTR-502 on the backplane. 3. Using a number 2 Phillips scre wdri ver with a shank of at least 64 mm (2.5 in.) length, tighten the capti v e scre ws to 1.1 N ⋅ m (10 lb ⋅ in.
FP-CTR-502 and cFP-CTR-502 4 ni.com Use a 5–30 VDC external po wer s upply for the input channels. The power supply must provid e e nough current to po wer all of the input channels and all of the f i eld de vices on the output channels.
© National Instruments Corp. 5 FP-CTR-502 and cFP-CTR-502 Inputs Each input channel has one input terminal, V IN . Each channel also has V SUP and COM terminals that can supply power to f ield de vices or provide additional conne ctions to the external po wer supply .
FP-CTR-502 and cFP-CTR-502 6 ni.com V IN is 21 V or lower , a nd an OF F state when V IN is 22 V or higher . The channel state is indeterminate when V IN is between 21 V a n d2 2V . Ensure that the sinking-output de vices ha v e OFF state leak age currents of less than 0.
© National Instruments Corp. 7 FP-CTR-502 and cFP-CTR-502 Figure 4. Wiring an O utput Channel to a Sourcing-Input Device If you connect a [c]FP-CTR-502 output to an e xternally po wered sourcing-inpu.
FP-CTR-502 and cFP-CTR-502 8 ni.com Configuring Count-Input Channels Channels 0 –7 are count-input channels. In FieldPoint software, you can conf igure each count-i nput channel to operate with attributes and comman ds.
© National Instruments Corp. 9 FP-CTR-502 and cFP-CTR-502 to Channel 0, Channel 0 to Chan nel 7, Channel 7 to Channel 6, and so on. If you select this op ti on for all of the channels, no counting occurs. Gate Source Select Gate Input 0 –3 from the V alue menu to associate a gate-input channel with a count-i nput channel.
FP-CTR-502 and cFP-CTR-502 10 ni.com Noise Rejection Each count-input channel has a so ftware-enabled lo wpass f ilter that you can set to reject freque ncies abov e 200 Hz or 50 kHz. Select 200 Hz or 50 kHz from the V alue menu to configure noise rejection.
© National Instruments Corp. 1 1 FP-CTR-502 and cFP-CTR-502 Output Mode For each output channe l select one of the follo wing output modes from the V alue menu : Toggle, Reset Off ; Toggle, Reset On ; On Pulse ; or Off Pulse . The output modes work only if you select Counter Channel 0 –7 for the Output Source .
FP-CTR-502 and cFP-CTR-502 12 ni.com On Pulse In On Pulse mode, the output ch annel starts low and goes high when the terminal count is e xce eded. The output channel returns to low after one count.
© National Instruments Corp. 1 3 FP-CTR-502 and cFP-CTR-502 Application Note: Generating a Contin uous Pulse T rain Y ou can use two [c]FP-CTR-502 count-input cha nnels and one output channel to generate a co ntinuous pulse train with a controllable duty cycle and period .
FP-CTR-502 and cFP-CTR-502 14 ni.com 4. Set the Count Source of the pr escaler cou nter to the clock on which you want to base your pul se train. This can be the external counter input or one of the [c]FP-CTR-502 internal references.
© National Instruments Corp. 1 5 FP-CTR-502 and cFP-CTR-502 T o determine the frequenc y of the output from the pulse counter , use the follo wing formula: where f pulse is the pulse counter output frequency f pre is the prescaler c ounter output frequency term pulse is the terminal count value for the pulse counter Step 3.
FP-CTR-502 and cFP-CTR-502 16 ni.com Status Indicators Figure 12 shows the status indica tor LEDs on the [c]FP-CTR-502 . Figure 12. Status Indicators The [c]FP-CTR-502 has two green status LEDs, POWER and READY .
© National Instruments Corp. 1 7 FP-CTR-502 and cFP-CTR-502 Follo w these guideli nes to ensure a safe total system. • The [c]FP-CTR -50 2 has a safety isolation barrier between the I/O channels and the inter-modu le commu nication b us. Th ere is no isolation between channe ls unless otherwise noted.
FP-CTR-502 and cFP-CTR-502 18 ni.com Specifications The follo wing specif ications are typical for a range of – 40 to 70 °C unless otherwise noted. 1 Input Characteristic s Number of channels ... ........... ............ 12 (8 count, 4 gate) Input type .
© National Instruments Corp. 1 9 FP-CTR-502 and cFP-CTR-502 Maximum output current Per channel .......... ........... ........... . 1 A Across all channe ls .................. ... 4 A Output impedance ... .............. ........... . 0.12 Ω Output bandwidth .
FP-CTR-502 and cFP-CTR-502 20 ni.com Shock and Vibration These specifications apply only to the cFP-CTR-502. NI recommends Compact FieldPoi nt if your application is subject to shock and vibration. Operating vibration, random (IEC 60068-2-64)....... .
© National Instruments Corp. 2 1 FP-CTR-502 and cFP-CTR-502 CE Compliance This product meets the essentia l requirements of applicable European Directi v es, as amended for CE Marking, as follo ws: Lo w-V oltage Directi v e (s afety). ..... ... 73/23/EEC Electromagnet ic Compatibility Directiv e (EMC) .
FP-CTR-502 and cFP-CTR-502 22 ni.com Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating instructions Go to ni.
Ein wichtiger Punkt beim Kauf des Geräts National Instruments FP-CTR-502 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie National Instruments FP-CTR-502 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für National Instruments FP-CTR-502 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von National Instruments FP-CTR-502 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über National Instruments FP-CTR-502 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon National Instruments FP-CTR-502 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von National Instruments FP-CTR-502 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit National Instruments FP-CTR-502. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei National Instruments FP-CTR-502 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.