SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ····································2 2. P ART NAMES AND FUNCTIONS ······················3 3. SPECIFICA TION·················································3 4.
2 1 TECHNICAL CHANGES MUZ-GA50V A - ➔ MUZ- GB50V A - E1 E1 1. Refrigerant filling capacity has been changed. 2. Outdoor electronic control P .C. board has been changed. Revision A: • Compressor has been changed. Previous New Model SNB130FLDH SNB130FLDH1 RoHS P AR TS LIST number E12 851 900 E12 939 900 OB455A--1qxq 06.
3 P ART NAMES AND FUNCTIONS 2 3 SPECIFICA TION Air inlet Piping Air outlet (back and side) Drain hose Drain outlet MUZ-GB50V A Outdoor model Function Power supply Capacity Rated frequency(Min.
4 Specifications and rating conditions of main electric parts Model Item Current transformer Current transformer Smoothing capacitor Fuse Fuse Fuse Expansion valve coil Intelligent power module Intelligent power module Reactor Power factor controller Resistor Resistor Resistor Solenoid coil relay T erminal block T erminal block Relay R.
5 4 NOISE CRITERIA CUR VES OUTDOOR UNIT MICROPHONE 1m COOLING FUNCTION SPL(dB(A)) LINE High F AN SPEED HEA TING 52 55 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC-60 NC-50 NC-40 NC.
6 OUTLINES AND DIMENSIONS 5 Unit: mm OUTDOOR UNIT MUZ-GB50V A 30 - 35 - 155 90 198 40 515 299 66 34 51 330 360 850 430 500 80 121 840 Open as a rule 500mm or more if the front and both sides are open .
7 WIRING DIAGRAM 6 MUZ-GB50V A R64B YLW 230V~ 12-24V CN912 CN663 WHT BLU NOISE FILTER P.C.BOARD BRN TO INDOOR UNIT CONNECTING RED S3 RT65 2 1 CN61 1 3 GRN/YLW 5 PFC GRN LD9 POWER BOARD RT64 2 1 CN3 RED WHT RS2 RS1 R64A RS3 RS4 F801 CN901 NR64 ELECTRONIC CONTROL P.
8 7 REFRIGERANT SYSTEM DIAGRAM MUZ-GB50V A OUTDOOR UNIT Unit:mm Outdoor heat exchanger Flared connection Defrost thermistor RT61 Discharge temperature thermistor RT62 Flared connection Stop valve Stop valve (with service port) Capillary tube [ 3.6 ✕ [ 2.
9 PERFORMANCE CUR VES 8 The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
10 Indoor air Dry-bulb temperature difference ( : ) In d o o r in ta k e a ir D r y -b u lb te m p e r a tu r e ( : ) Outdoor intake air Wet-bulb temperature ( : ) Outdoor intake air Wet-bulb temperature ( : ) In d o o r in ta k e a ir D r y -b u lb te m p e ra tu r e ( : ) 24.
11 COOL operation 1 Both indoor and outdoor unit are under the same temperature/humidity condition. 2 Operation : TEST RUN OPERA TION (refer to 8-3.) Dry-bulb temperature( : ) Relative humidity(%) 20 50 25 60 30 70 8-4.
12 MSZ-GB50V A : MUZ-GB50V A 21 18 5.88 3.00 0.51 1320 5.63 2.87 0.51 1386 5.40 2.75 0.51 1452 5.20 2.65 0.51 1518 21 20 6.13 2.39 0.39 1386 5.88 2.29 0.39 1469 5.70 2.22 0.39 1502 5.50 2.15 0.39 1568 22 18 5.88 3.23 0.55 1320 5.63 3.09 0.55 1386 5.40 2.
13 21 18 4.90 2.50 0.51 1617 4.50 2.30 0.51 1716 4.30 2.19 0.51 1749 21 20 5.15 2.01 0.39 1683 4.80 1.87 0.39 1766 4.60 1.79 0.39 1815 22 18 4.90 2.70 0.55 1617 4.50 2.48 0.55 1716 4.30 2.37 0.55 1749 22 20 5.15 2.21 0.43 1683 4.80 2.06 0.43 1766 4.60 1.
14 PERFORMANCE DA T A HEA T operation CAPACITY:5.8(kW) INPUT:1700(W) OUTDOOR WB( : ) INDOOR -10 -5 0 5 10 15 20 DB( : ) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 21 26 3.65 1105 4.41 1326 5.16 1496 5.92 1615 6.67 1717 7.37 1768 8.12 1802 3.
15 10 TROUBLESHOOTING 3. T roubleshooting procedure 1) First, check if the OPERA TION INDICA TOR lamp on the indoor unit is flashing on and off to indicate an abnormality . T o make sure, check how many times the abnormality indication is flashing on and off before starting service work.
16 Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-4.
17 2. Flow chart of the detailed outdoor unit failure mode recall function Operational procedure Note1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
18 OFF None (Normal) 2-time flash 3-time flash 4-time flash 5-time flash 6-time flash 7-time flash 8-time flash Lighting Lighting Lighting Once Lighting Once Lighting Twice Lighting 3 times Lighting 4.
19 11-time flash • Check the connecting wire between outdoor electronic control P.C. board and power board. • Replace the power board. • Check the connecting wire among electronic control P.C. board, noise filter P.C. board and power board. • Replace the power board.
20 Start Indoor unit operates. Outdoor unit doesn't operate. Indoor unit doesn't receive the signal from remote controller . OPERA TION INDICA T OR lamp on the indoor unit is flashing on and off. Outdoor unit operates only in T est Run operation.
21 LED1(Red) LED2(Yellow) Lightning Twice Outdoor power system • Check the connection of the compressor connecting wire. • Refer to 10-6. A "How to check inverter/compressor". • Check the stop valve. Lightning 3 times Discharge temperature thermistor • Refer to 10-6.
22 Primary current protection Secondary current protection High-pressure protection Defrosting in cooling 3 times Lighting Discharge temperature protection • Check refrigerant circuit and refrigerant amount. • Refer to 10-6. G "Check of LEV".
23 Part name Figure Check method and criterion Defrost thermistor (RT61) Ambient temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68) Normal 2.
24 10-6. T roubleshooting flow MUZ-GB50V A A A How to check inverter/ compressor No No Ye s Ye s Ye s No Ye s No Disconnect the terminal of the compressor . 3 minutes after turning on the power supply , start EMERGENCY OPERA TION. Is output balanced? Clarify the causes by counting time until the inverter stops.
25 B B Check of outdoor thermistors • When OPERA TION INDICA TOR lamp flashes 6-time. • When thermistor is abnormal. Ye s Ye s No No Reconnect the connector CN661, CN663 and CN3. 3 minutes after turning on the power supply , start EMERGENCY OPERA TION.
26 C C Check of R.V . coil No Ye s No Ye s No Ye s No Ye s No Ye s 1. Disconnect the lead wire leading to the compressor . 2. 3 minutes after turning on the power supply , start EMERGENCY OPERA TION in HEA T mode. Is there voltage of 230V AC between pin1 and pin 2 at connector CN912? W T urn off power supply of indoor and outdoor unit.
27 D D Check of outdoor fan motor • Fan motor does not operate or stops operating shortly after starting the operation. Ye s No No Ye s Ye s No (Fixed to either 5V or 0V DC) Check the connection between the connector CN931 and CN932. Disconnect CN932 from outdoor electronic control P .
28 Outdoor unit does not operate at all, or stops immediately due to overcurrent. F F Check of current-limiting resistor ● Check other electric parts in the main circuit together in the case that the current-limiting resistor is defective. Turn ON the power supply and press EMERGENCY OPERATION switch.
29 H H How to check mis-wiring and serial signal error (when outdoor unit does not work) • When unit cannot operate neither by the remote controller nor by EMERGENCY OPERA TION switch. Indoor unit does not operate. • When OPERA TION INDICA TOR lamp flashes ON and OFF in every 0.
30 I I Electromagnetic noise enters into TV sets or radios Replace or repair the antenna. Replace or repair the coaxial cable. No No No Yes Yes No No Yes Yes Yes Is the distance between the antennas a.
31 1. Outdoor electronic control P .C. board MUZ-GB50V A LED 1 LED 2 CN801 325V DC ~ 370V DC Input ( ( CN932 20-90V AC GND 5V 5V DC pulse wave ( To f a n motor Defrost thermistor (RT61) Discharge temperature thermistor (RT62) Outdoor heat exchanger temperature thermistor (RT68) ( ( (+) (–) (+) Rush current relay (–) R.
32 { CN912 R.V . coil 230V AC 230V AC Input 230V AC Output { { CN901 T o electronic control P .C. board MUZ-GB50V A F64 FUSE 2A/250V F91 1 FUSE 1A/250V 2. Noise filter P .C. board CN902 T o power board CN903 T o power board { 230V AC Output NR64 V ARISTOR OB455 A--2qxp 06.
33 MUZ-GB50V A 3. Outdoor power board 325-370V DC Output (Red) (White) Connect to the compressor V oltage among phases: 5V to 180V Connect to the earth CN5 Primary current detection (Connect to the noise filter) CN2 Connect to the controller board (+)1-5(–): Signal transmission (T o electronic control P .
34 DISASSEMBL Y INSTRUCTIONS 11 (1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism. 1 Slide the sleeve. 2 Pull the terminal while pushing the locking lever . 1 Hold the sleeve, and pull out the terminal slowly .
35 OPERA TING PROCEDURE PHOTOS 2. Removing the inverter assembly , inverter P .C. board and power board (1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel.(Refer to 1.) (3) Disconnect the following connectors; <Electronic control P .
36 5. Removing outdoor fan motor (1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly . (Refer to 2.) (4) Remove the propeller . (5) Remove the screws fixing the fan motor .
37 OPERA TING PROCEDURE PHOTOS Photo 8 6. Removing the compressor and 4-way valve (1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly . (Refer to 2.) (4) Recover gas from the refrigerant circuit.
38 12 RoHS P ARTS LIST (RoHS compliant) 4 17 1 12 9 11 2 5 6 7 8 15 13 18 20 21 22 23 27 28 29 3 10 14 16 19 26 25 24 MUZ-GB50V A 12-1. OUTDOOR UNIT STRUCTURAL P ARTS, ELECTRICAL P ARTS AND FUNCTIONAL P ARTS OB455 A--2qxp 06.
39 RoHS Symbol in Wiring Diagram Q'ty/unit Remarks Part No. No. Part Name MUZ-GB 50V A - E1 E12 819 297 E12 851 630 E12 938 301 E12 851 501 E12 851 290 E12 819 232 E12 819 009 E12 819 521 E12 065.
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN C C Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO.,L TD Distributed in Aug. 2006. No. OB455 REVISED EDITION-A 6 Distributed in Mar . 2006. No. OB455 6 Made in Japan New publication, effective Aug.
Ein wichtiger Punkt beim Kauf des Geräts Mitsubishi MUZ-GB50VA (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Mitsubishi MUZ-GB50VA noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Mitsubishi MUZ-GB50VA - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Mitsubishi MUZ-GB50VA reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Mitsubishi MUZ-GB50VA erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Mitsubishi MUZ-GB50VA besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Mitsubishi MUZ-GB50VA verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Mitsubishi MUZ-GB50VA. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Mitsubishi MUZ-GB50VA gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.