Benutzeranleitung / Produktwartung E1000RM1U des Produzenten Minuteman UPS
Zur Seite of 28
User's Manual Enterprise 1U Rackmount Series.
1 © Copyright Para Systems, Inc., 2005 Enterprise 1U Rackmount Series User's Manual 1 . Introduction 2 2 . Controls and Indicators 6 3. Installation 8 4. Operation 12 5 . T roubleshooting 15 6 . Replacing the Battery 16 7 . Obtaining Service 19 8 .
2 IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS ! English Thank you for purchasing a MINUTEMAN power protection product. It has been designed and manufactured to provide many years of trouble free service.
3 W ARNING: Risk of Electrical Shock. Hazardous live parts inside these power supplies are energized from the battery even when the AC input is disconnected. CAUTION! T o de-energize the outputs of the UPS: 1. If the UPS is on press and release the On/Off/T est button.
4 English After removing your MINUTEMAN UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored.
5 English Para Systems Life Support Policy As a general policy , Para Systems Inc. (Para Systems) does not recommend the use of any of its products in life support applications where failure or mal- f.
6 English The AC normal (green) LED illuminates in a steady state when the UPS is on and operating in the AC normal mode. The AC normal LED will extinguish when operating in the Battery mode. The On-Battery (green) LED illuminates in a steady state when the UPS is operating in the Battery mode.
7 English The Load Level Bar Graph operates as follows: LED #10: >10% load (green/red/yellow) LED will be green and illu- minated when there is at least 10% of the rated capacity . LED #30: >30% load (green/yellow) LED will be green and illumi- nated when there is at least 30% of the rated capacity .
8 English INST ALLA TION PLACEMENT The Enterprise 1U Rackmount Series is intended to be install in a temperature controlled environment that is free of conductive contaminants. Select a loca- tion which will provide good air circulation for the UPS at all times.
9 English INST ALLA TION Be sure to read the installation placement and all the cautions before installing the UPS. Place the UPS in the final desired location and complete the rest of the installation procedure. These UPSs are shipped with the internal batteries disconnected.
10 English Installing the UPS in a 4-post rack USE CAUTION: The UPS is heavy . Use the appropriate number of personnel when installing the UPS. 1. Install the rails in the 4-post rack. (FIG . 1) 2. Install the rack ears on the UPS. (FIG . 2) 3. Align the cleats with the rails and slide the UPS into the rails.
11 English CHARGING THE BA TTER Y The Enterprise 1U Rackmount Series UPS will charge the internal batteries whenever the UPS is connected to an AC source.
12 English SYSTEM OVERVIEW This Line-Interactive 1U Rackmount model UPS protects internetworking and telecommunications equipment from blackouts, brownouts, overvoltages, and surges. The A VR function continuously corrects the volt ages, in-between the brownout and overvoltage transfer points (85 - 150V AC), to a safe usable level.
13 English ALARMS ON BA TTER Y When the UPS is operating on the batteries, the On-Battery LED will illuminate and the audible alarm will sound once every ten-seconds. The alarm will stop once the UPS returns to the AC normal mode. LOW BA TTER Y W ARNING The UPS will sound two beeps every five-seconds when the battery reserve runs low .
14 English COMMUNICA TIONS PORTS (RS232 and USB) The RS232 communication port is a standard DB9 female with both RS232 and simulated contact closure cap ability . The Enterprise 1U Rackmount Series UPS will poll the port and activate the port for RS232 or contact closure in accordance with the type of cable it finds connected to the port.
15 English Possible Cause Symptom What T o Do Press and release the On/Off/ T est button to start UPS On/Off/T est button not pushed UPS will not turn on Reset circuit breaker by pressing the plunger back in.
16 English REPLACING THE BA TTER Y W ARNING! This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONL Y .
17 English BA TTER Y REPLACEMENT PROCEDURE PLEASE READ THE CAUTIONS AND W ARNINGS BEFORE A TTEMPTING TO REPLACE THE BA TTERIES Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system.
18 English 8. Remove the four retaining screws for the battery ret aining bracket. (FIG . 3) 9. Remove the battery retaining bracket. (FIG . 3) 10. Grasp the battery tray and gently pull the battery tray out far enough to get to the battery connectors (red and black).
19 English IF THE UPS REQUIRES SERVICE 1.Use the TROUBLESHOOTING section to eliminate obvious causes. 2.V erify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem.
20 English Default 120V AC User selectable 120/127V AC 700V A 490W 1500V A 900W 1000V A 700W Protection W aveform T ype Over-Current, Short-Circuit Protected and Latching Shutdown Sine Wave Frequency 50/60Hz, +/-0.
21 English BA TTER Y SYSTEM T ypical Recharge T ime T ypical Battery Life Battery Quantity/Rating 3-5 years, depending on discharge cycles and ambient temp 4-6V9Ah 4-6V9Ah 8 hours from total discharge.
22 English (These items may require optional software or hardware) Function Factory Default Description User Choices Set inverter output voltage Shut- down T ype Set audible alarm state Enable/ Disabl.
23 English Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase.
24 English EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL P ARA SYSTEMS BE LIABLE FOR DIRECT , INDIRECT , SPECIAL, INCIDENT AL, OR CONSEQUEN- TIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT , EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
25 English DECLARA TION OF CONFORMITY Application of Council Directive(s): 89/336/EEC, 73/23/EEC S tandard(s) to which Conformity is declared: Manufacturer’s Name: Para Systems, Inc.
26 English Notes:.
Para Systems, Inc. 1455 Lemay Dr . Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-901 1 Internet: minutemanups.com UPS Sizing: sizemyups.com PN - 34000256 Rev .
Ein wichtiger Punkt beim Kauf des Geräts Minuteman UPS E1000RM1U (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Minuteman UPS E1000RM1U noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Minuteman UPS E1000RM1U - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Minuteman UPS E1000RM1U reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Minuteman UPS E1000RM1U erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Minuteman UPS E1000RM1U besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Minuteman UPS E1000RM1U verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Minuteman UPS E1000RM1U. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Minuteman UPS E1000RM1U gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.