Benutzeranleitung / Produktwartung 5000 RT des Produzenten MGE UPS Systems
Zur Seite of 44
Pulsar MX 5000 R T — UPS EXB R T — Extended Battery T ransformer 5000 Installation and User Manual www .mgeups.com.
.
Installation and User Manual 86-87050-00 A01 Pulsar MX Installation and User Manual Revision History Pulsar MX Installation and User Manual, 86-87050-00 Revision: A00 ECN#: 004747 04/2006 Revision: A01 ECN#: 004773 05/2006 Copyright © 2006 MGE UPS SYSTEMS, INC.
Pulsar MX 86-87050-00 A01.
Contents Contents c i 86-87050-00 A01 Introduction ..........................................................................................................................1 Important Safety Instructions ..............................................
Pulsar MX Contents c ii 86-87050-00 A01 Life Cycle Monitoring (LCM) 6.1 Description ................................................................................................................ ..6 — 1 Maintenance 7.1 Hot Swapping the Power Sub-Module .
Introduction Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment. The Pulsar MX range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS (Uninterruptible Power System).
Pulsar MX 2 86-87050-00 A01 IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS. This manual contains important instructions that should be followed during installa- tion and maintenance of the UPS and batteries.
Symbol Usage Important instructions that must always be followed. Information, advice, help. Visual indication. Action. Audible signal. LED off LED on Installation and User Manual 3 86-87050-00 A01 In.
(This page left blank intentionally) Pulsar MX 4 86-87050-00 A01.
Presentation 1.1 Standard Positions T ower Position Rack Position 1 — 1 86-87050-00 A01 Presentation Dimensions (H x W x D) in inches/mm Pulsar MX 5000 RT 17.5 x 5.16 x 29.2/ 444.5 x 131 x 741.4 Pulsar MX EXB RT 17.5 x 5.16 x 25.6/ 444.5 x 131 x 650 T ransformer 5000 17.
1.2 Rear Panels Pulsar MX 5000 RT Pulsar MX EXB RT T ransformer 5000 (1) One group of 4 L6-30R outlets for connection of equipment (2) Output terminal block (3) Normal AC source input cable with L6-30.
1.3 Display and Control Panel 1.4 Accessories for Rack Mount Rack Mounting Kit T elescopic rails for Pulsar MX RT mounting in 19’’ enclosure with mounting hardware (35) Front mounting bracket (36) Rear support bracket (37) T elescopic rails, 639 mm to 1005 mm length (27.
1.5 Extended Battery (EXB) Pulsar MX RT offers a standard backup time of 5 minutes at full load. T o increase backup time, it is possible to connect Pulsar MX EXB RT modules to the UPSs for backup times up to 62 minutes (at full load).
2 — 1 86-87050-00 A01 Installation 2.1 Unpacking and Contents Check UPS Module Contents (87050) Optional T ransformer Module Contents (87102) Step down transformer is designed to provide isolated 120 volts AC outlets.
2.2 Internal Battery Connection (Battery Start-up) 2.3 Installation in T ower Position Follow steps 1 to 3 in the illustration below to adjust the tower stands for the upright position. Always keep 6 inches free space behind the UPS rear panel. The distance between the tower stands should be 17.
2.4 Installation in Rack Position Adjustment of the orientation of the logo and control panel UPS module rack mounting Pulsar MX RT is very heavy . T o ease its rack integration, we strongly recommend to remove the battery tray as shown below .
Do not install the UPS or battery module in hermetic closed environments without any exchange of air . Follow steps 1 to 4 for rack mounting the UPS onto the rails. The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS. Note for step 1: It is possible to adjust the position of both front mounting brackets.
2.5 Communication Ports Pulsar MX RT provides 4 communication methods. 1. The RS232 port provides communications using MGE UPS SYSTEMS Serial HID UPS transfer (SHUT) protocol. The SHUT protocol is compatible with the power management applications available on the enclosed Solution-Pac 2 CD-Rom.
Remote Power Off communication port (9) Installation of a Remote Power Off function must be carried out in compliance with applicable regulations. In order to fully de-energize Pulsar MX RT with the RPO port, it is necessary to use a two-position switch (Normally Open or Closed contact).
2.7 Hardwire Connection of Output Power Cable to UPS ◗ This type of connection must be carried out by qualified electrical personnel. ◗ Before carrying out any connection, check that the battery circuit breaker and the upstream protection device (Normal AC source) is open "0" (off).
2.8 Connection to Output Receptacles 2.9 Connection of Extended Battery Module, UPS, and T ransformer 1. Check that the battery circuit breaker(s) (13) is OFF ("0" position). 2. Connect the battery power cable (52) to the connector (4) of the power module and to the connector (12) of the battery module.
Operation 3.1 Initial Start-Up T o ensure that your system is configured in complete accordance with safety regulations and to benefit from the manufacturer ’s warranty , please contact T echnical Support. UPS Set-Up If UPS personalization is desired, it is advised to enter the personalization mode at this time (see the 4.
Pulsar MX 3 — 2 86-87050-00 A01 3.3 Operating Modes Normal mode ECO mode AC out of tolerance If normal AC source is out of tolerance: LEDs (20) , (21) are ON. LEDs (30) , (32) , (34) are green. The equipment is protected by the UPS. The main advantage of the Eco mode (see glossary) is that it reduces the consumption of electrical power .
3.4 Operation on Battery Power When the Normal AC source is not available, the load continues to be protected by the UPS. Power is supplied by the battery . T ransfer to battery power Low battery warning End of backup time LED (22) is ON. LED (34) is red.
3.5 Return to Normal AC Source After an outage, the UPS restarts automatically when Normal AC source is restored (unless this function has been disabled via UPS personalization) and the load is supplied again. 3.6 UPS Shutdown When AC Present Before shutdown, please read ALL instructions below: 3.
Access to Maintenance and Personalization Data 4.1 Display Organization 4.2 Access to Measurements Press the scroll button (25) to access measurements for voltage, current, frequency , power output and battery capacity .
4.4 UPS Set-Up Local Settings Output Settings ON/OFF Settings Function Factory Setting Options Comments Cold Start Disabled Enabled Start on battery Forced Reboot Enabled Enabled Enables automatic res.
Battery Settings 4.5 Maintenance 4.6 UPS Set-Up Using External Software ◗ Insert the Solution-Pac CD-ROM in the drive. ◗ On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal Solution-Pac software.
(This page left blank intentionally) Pulsar MX 4 — 4 86-87050-00 A01.
5 — 1 86-87050-00 A01 T roubleshooting 5.1 T roubleshooting LEDS (21) and (22) 5.2 T roubleshooting Not Requiring MGE UPS SYSTEMS After-Sales Support Press the "Enter" button (27) to displ.
5.3 T roubleshooting Requiring MGE UPS SYSTEMS After-Sales Support Note: In case of multiple fault, press the "Enter" button (27) and the scroll button (25) to get access to further details. Display Signification Correction POWER MODULE F AUL T The battery is incorrectly connected.
Life Cycle Monitoring (LCM) 6.1 Description This function, embedded in the UPS, displays messages on screen, and communication channels, at every important stage of the UPS’ s life, allowing you to: Get free offers LCM warning details Signification 3 MONTHS FREE W ARRANTY EXTENSION FOR PRODUCT REGISTRA TION CONT ACT MGE A T www .
Secure your installation power continuity Anticipate needed maintenance actions thanks to automatically displayed warnings: Reset or disable LCM In case of any LCM messages displayed: ◗ For temporary reset: Press ESC for more than 3 seconds in the Status and Alarm screen, to temporarily cancel the alarm status.
Maintenance 7.1 Hot Swapping the Power Sub-Module This operation must be carried out by qualified electrical personnel only . This operation can be performed without interrupting the equipment. Disconnecting the power sub-module (87100): Reconnecting the power sub-module: ◗ Carry out the above instructions in reverse order .
Pulsar MX 86-87050-00 A01.
Appendix 8.1 T echnical specifications (1) If the output voltage is 200V — 250V , the output power is 5000V A / 4500W . (2) With one EXB module or more, the standard output power is 5000V A / 4000W . (3) V alues for 70% / 100% of UPS output. (4) Programmable: 200V / 208V / 220V / 230V / 240V / 250V using the Personal Solution-Pac software.
Pulsar MX 86-87050-00 A01 MGE W arranty & Proprietary Rights for Single Phase Products Standard W arranty Form (Applicable within the United States, Canada and Mexico) MGE Standard Single Phrase W arranty MGE UPS SYSTEMS, INC.
MGE Customer Care Center - Single Phase Products T echnical Support and Product Services T echnical questions? If you encounter a problem while following the instructions in this manual, or have questions about the operation, repair , or servicing of your equipment, please direct calls to MGE UPS SYSTEMS, INC.
Pulsar MX 86-87050-00 A01.
Glossary Backup time T ime that the connected equipment can operate on battery power . Bypass AC source Source supplying the bypass line. The equipment can be transferred to the bypass line if an overload occurs on the UPS output, for maintenance or in the event of a malfunction.
Notes: Pulsar MX 86-87050-00 A01.
.
1660 Scenic A venue, Costa Mesa, California 92626 • (714) 557-1636 www .mgeups.com Contact MGE United States MGE UPS SYSTEMS 1660 Scenic Ave. Costa Mesa, CA 92626 T el: (714) 557-1636 (800) 523-0142 Fax: (714) 557-9788 email: info@mgeups.com www: mgeups.
Ein wichtiger Punkt beim Kauf des Geräts MGE UPS Systems 5000 RT (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie MGE UPS Systems 5000 RT noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für MGE UPS Systems 5000 RT - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von MGE UPS Systems 5000 RT reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über MGE UPS Systems 5000 RT erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon MGE UPS Systems 5000 RT besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von MGE UPS Systems 5000 RT verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit MGE UPS Systems 5000 RT. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei MGE UPS Systems 5000 RT gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.