Comet 40-150kV A Uninterruptible Power Supply Installation and User Manual fa ult E ME RG E NCY P O W E R O F F ı Í ⁄ UPS SY S T E M S M G E CO M ET Load Prot ec ted % KV A Load 0% Setup A la rm s Inpu ts Lo a d B a t tery Mai n U P S I n p u t KA2 KA1 K3N Q F1 lo a d www .
.
Installation and User Manual i 86-160310-00 E00 Comet 40 - 150kV A Installation and User Manual Revision History Comet 40-150kV A UPS Installation and User Manual 86-160310-00 Revision: A00 Initial Re.
Comet 40-150kV A Important Safety Instructions ii 86-160310-00 E00 IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS – This manual contains important instructions for the Comet 40-150kV A that must be followed during operation and maintenance of the equipment.
Installation and User Manual iii 86-160310-00 E00 Certification Standards and Safety of Persons W ARNING HIGH LEAKAGE CURRENT . Earth connection essential before connecting supply . A TTENTION COURANT DE FUITE ELEVE. Raccordement a la terre indispensable avant le raccordement au reseau.
(This page left blank intentionally) Comet 40-150kV A iv 86-160310-00 E00.
Contents Contents c i 86-160310-00 E00 section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comet 40-150kV A Contents c ii 86-160310-00 E00 section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page Section 2 Installation (continued) 2.6 Connections . . . . . . . . . . . . . . . . . . . . . .
Installation and User Manual Figures figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-1: Comet 40-80kV A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comet 40-150kV A c iv 86-160310-00 E00 CAUTION: Record All Serial Numbers! CAUTION: Record All Serial Numbers! RECORD ALL SERIAL NUMBERS FOR THE COMET UPS AND ACCESSORIES.
(This page left blank intentionally) c v 86-160310-00 E00 Installation and User Manual.
Comet 40-150kV A c vi 86-160310-00 E00 Symbol Usage This manual uses five icon symbols with text to convey important information and tips. W ARNING Information provided to protect the user and service personnel against safety hazards and/or possible equipment damage.
System Description and Specifications 1.0 Scope Provides a general description of the Comet 40-150kV A Uninterruptible Power Systems major components, available options, and system specifications.
Figure 1-3, and 1-4 show single-line diagrams of a typical UPS system installation. During normal operation, utility power (Main Input) is supplied to the UPS Rectifier where it is converted to DC voltage. The Inverter converts the DC voltage from the Rectifier to three-phase regulated AC voltage, which supplies the critical load.
Installation and User Manual 1.2 Major Components The following is a description of the cabinets and major components. Refer to Figures 1-5 to 1-8. UPS Cabinet Converts the input AC power to direct current and charges the battery . DC power is converted back to clean AC power by the inverter for the critical load.
Figure 1-5: Front View of the Comet 40-80kV A. Comet 40-150kV A System Description and Specifications 1 — 4 86-160310-00 E00 A 05 01 02 04 DET AIL BEHIND ITEM 25 (KA1) Input Contactor (K3N) Output C.
Installation and User Manual Figure 1-6: Rear View of the Comet 40-80kV A. System Description and Specifications 1 — 5 86-160310-00 E00 T1 INPUT TRANSFORMER (OPTIONAL) T2 OUTPUT TRANSFORMER (OPTIONA.
Figure 1-7: Front View of the Comet 100-150kV A. Comet 40-150kV A System Description and Specifications 1 — 6 86-160310-00 E00 (KA1) Input Contactor (K3N) Output Contactor (KA2) Bypass Input (F1, F2.
Installation and User Manual Figure 1-8: Front View of Communications Components for the Comet 100-150kV A. System Description and Specifications 1 — 7 86-160310-00 E00 COMMUNICA TION PCAs T OP COND.
1.3 Specifications The Comet 40-150kV A UPS systems are rated for various input and output voltages (see T able 1-1). When different input and/or output voltages are specified, optional transformers provide step up/down functions as required. T able 1-1: Comet 40-150kV A Specifications.
Installation and User Manual NOTES: 1. T otal width, weight, and heat loss are for system line-up excluding battery cabinets. 2. Data does not include battery data; refer to the installation drawings supplied with your equipment. Consult the installation drawings provided with your equipment.
1.3.4 Mechanical Specifications (UPS Cabinet Only) Height 66.70 in/1694 mm Width 32.75 in/832 mm Depth 33.42 in/823 mm W eight at 480 V AC in and 480 V AC out 40/50kV A 65/80kV A 100-150kV A 880 lbs/400 kg 970 lbs/440 kg 1460 lbs/662 kg 1.
Installation and User Manual 1.4 Options and Accessories Options are available for the Comet 40-150kV A UPS’s. Most options must be specified at the time of the original order for factory installation. Some options can be field installed; contact your MGE Sales Representative for further information.
COMET 40-150kV A Chaptername 1 — 12 86-160310-00 E00.
(This page left blank intentionally) Comet 40-150kV A 1 — 13 86-160310-00 E00.
Installation 2.0 Scope Installation of the Comet 40-150kV A UPS, which include receiving, handling, and storage procedures; prerequisites to installation; installation procedures; and startup procedures. CAUTION Scheduling of the MGE Field Service Engineers typically should be done 7 to 10 days before they are required on-site.
If the equipment is to be stored for more than three months before installation, it should be unpacked and connected to an AC input source to allow the batteries to be recharged. Refer to the installation instructions that follow , and the installation drawings.
Installation and User Manual 2.4.2 Mechanical The Comet UPS can be mounted on a raised computer room floor , or flush-mounted on a concrete floor . All floors must be level. On a raised floor , conduits can be run below the floor , with cut-outs made in the floor tiles as shown on the installation drawings.
2.5 Installation Procedures The steps to be followed are: ◗ Placement of the UPS and associated equipment. ◗ Connection of input power , output power , and control cables. Installation of UPS equipment must be handled by skilled technicians and electrician's familiar with the special requirements of high-energy electrical equipment.
Installation and User Manual 2.6.4 AC Output The connections to be made are the three phases, and ground cables from the load source to the UPS. The output cables are terminated at the Output T erminal Block (TB2) for 40-80kV A, and the output busbars for 100- 150kV A.
COMET 40-150kV A Chaptername 2 — 6 86-160310-00 E00.
(This page left blank intentionally) Comet 40-150kV A 2 — 7 86-160310-00 E00.
Operation 3.0 Scope Important information on the Comet 40-150kV A systems’ operation procedure sequences; for normal, on battery , and bypass operation, with descriptions of the control and display indicators.
3.1.3 Power Flow , For Bypass Operation Should there be an internal fault in the UPS, the load will automatically be transferred to the "Static Switch". (If bypass AC input is within tolerance). The load is supplied without interruption while the UPS is bypassed (see Figure 3-3).
Installation and User Manual Figure 3-4: Comet Front Panel GUI, Controls and Indicators. NOTE For details on the Graphical User Interface (GUI) display , please refer to manual 86-160316-00.
Graphical User This display provides specific information concerning normal UPS operation as Interface Display well as faults. Emergency Power Off This red Emergency Power Off (EPO) pushbutton is used to stop the unit during an emergency situation only .
Installation and User Manual 3.3 Startup Procedures 3.3.1 Preliminary Checks ◗ Check the settings of the protection devices. ◗ V erify that the battery circuit breaker(s) are in the "OFF" position. ◗ V erify that the Manual Bypass Switch SR1 is set to the “NORMAL” position.
3.5 Operating Procedures 3.5.1 Normal Operation ◗ The AC input power is present. ◗ The green "Load Protected" LED is on. The GUI display indicates the operating status of the UPS. ◗ The power drawn by the load is supplied by AC input power via the Rectifier and Inverter modules.
Installation and User Manual 3.5.4 Overload When an Inverter temporary overload occurs, the load is transferred to the "Static Switch". Return to normal mode of operation is automatic, following elimination of the overload.
3.6 Emergency Shutdown Using EPO/REPO CAUTION Pressing the “Emergency Power Off” (EPO) or “Remote Emergency Power Off” (REPO) pushbutton disconnects the attached load. The EPO is to be used during emergency situations only , where a hazard to personnel or equipment exists, such as during a fire.
Installation and User Manual NOTE The cooling fans will remain operational when the UPS is placed on Maintenance Bypass mode to prevent the optional input/output transformers inside the UPS from overheating. If it is necessary to de-energize the fans, move the fan control switch (SR2) to the “OFF” position.
3.9 Shutdown Procedures 3.9.1 Inverter Shutdown ◗ Press and hold the gray "Inverter OFF" pushbutton for 3 seconds. ◗ The green “Load Protected” LED goes off. ◗ The red “Load Not Protected” LED goes on. ◗ The buzzer sounds. ◗ The Inverter stops if the transfer conditions are correct.
Maintenance 4.0 Scope Preventive maintenance and battery safety instructions for Comet 40-150kV A UPS, and information about replacement parts, and customer service.
4.3 Replacement Parts There are no user serviceable parts inside the Comet UPS. Three levels of replacement parts are available for the Comet. The three levels are designated A, B, and C.
MGE W arranty & Proprietary Rights Statement for Three Phase Products (Applicable within the United States, Canada and Mexico) MGE Standard Three Phase W arranty MGE UPS SYSTEMS, INC.
W arranty and Product Registration Thank you for choosing MGE UPS SYSTEMS, INC. for your power protection, distribution, and quality requirements. We are pleased to have you join our increasing family of users.
MGE Customer Care Center - Three Phase Products T echnical Support and Product Services T echnical questions? If you encounter a problem while following the instructions in this manual, or have questions about the operation, repair , or servicing of your equipment, please direct calls to MGE UPS SYSTEMS, INC.
(This page left blank intentionally) Comet 40-150kV A W—4 86-160310-00 E00.
Glossary T erm used Definition / Meaning @ At. / And/or . +/- Plus or Minus. ≤ Equal to or less than. # Number . °C Degree Celsius. °F Degree Fahrenheit. Ø Phase angle. Ω Ohm; unit of resistance. ® T rade Mark. 2nd Second. AC or ac Alternating current, also implies root-mean-square (rms).
C.S.S. Customer Support Service. Current rating The maximum current that a conductor or equipment can carry reliably without damage. dBA Decibel Adjusted. dBrnC Decibel above reference noise. DC or dc Direct current, or voltage. Digital Meter The LCD display on the front panel of inverter system.
Glossary G — 3 86-160310-00 E00 Module Refers to individual power inverter module. N Neutral. NC Normally closed. NO Normally open. NEC National Electrical Code. NEMA National Electrical Manufacturers Association. NFP A National Fire Protection Association.
Comet 40-150kV A G — 4 86-160310-00 E00 (This page left blank intentionally).
Reorder Form 1660 Scenic A venue Costa Mesa, CA 92626 Use this form to report any errors, omissions, or other problems you have experienced, or to order additional hardcopies of this document. A free copy of this document may be downloaded from the proprietary MGE Rep Web site.
.
.
1660 Scenic Avenue, Costa Mesa, California 92626 • (714) 557-1636 www .mgeups.com Contact MGE United States MGE UPS SYSTEMS 1660 Scenic Ave. Costa Mesa, CA 92626 T el: (714) 557-1636 CCC: (800) 438-7373 Fax: (714) 557-9788 email: info@mgeups.com www: mgeups.
Ein wichtiger Punkt beim Kauf des Geräts MGE UPS Systems 40-150kVA (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie MGE UPS Systems 40-150kVA noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für MGE UPS Systems 40-150kVA - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von MGE UPS Systems 40-150kVA reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über MGE UPS Systems 40-150kVA erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon MGE UPS Systems 40-150kVA besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von MGE UPS Systems 40-150kVA verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit MGE UPS Systems 40-150kVA. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei MGE UPS Systems 40-150kVA gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.