Installation Instructions MODEL 8870 These instructions are for connecting the Thermostat to the HV AC equipment. T o connect communication features, please reference the Communicating Thermostat System Installation Manual.
INST ALLA TION INSTRUCTIONS MANUAL T ABLE OF CONTENTS W arning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Model 8870 Thermostat Specifications . . . .
1 READ COMPLETE SAFETY & INST ALLA TION INSTRUCTIONS BEFORE ST ARTING W ARNING 1. 120-volts may cause serious injury from electrical shock. Disconnect electrical power to the furnace and air conditioner before starting installation. This thermostat is not a 120-volt (line voltage) device.
MODEL 8870 THERMOST A T SPECIFICA TIONS: Control V oltage 24V AC ± 20% Switched V oltage 18 – 30V AC Maximum Operating Current 2.0A total at rated voltage, through all outputs. 1.0A through any one output. Maximum Surge Current 2.0A Control Accuracy ± 1.
2. WHA T’S IN THE BOX • Thermostat ( Figure 1 ): front panel, cover , and base • Installation Manual • Owners Manual • Hardware bag: screws and wall anchors FIGURE 1 3. SELECT THE THERMOST A T LOCA TION Determine if the thermostat will be operating alone, or with remote temperature sensors.
DO NOT locate the thermostat: • Behind doors, in corners or other dead air spaces. • In direct sunlight or near lamps, appliances or other sources of radiant heat. • On an outside wall or wall exposed to an unconditioned space (i.e. garage, etc.
FIGURE 3 5. MOUNT BASE TO WALL There are four screw holes located on the base of the thermostat; two are for a junction box mounting, along with two for alternate mounting spacing.
6 6. SETTING THE DIP SWITCHES Set the dip switches located on the thermostat circuit board ( Figure 4 ) according to the application needs ( T able 2 ).
T ABLE 2 APPLICA TION SWITCH #1 SWITCH # 2 SWITCH # 3 SWITCH # 4 Single Stage Furnace & AC Servant Fossil Single H / C T wo Stage Furnace & T wo Stage AC Servant Fossil Multi H / C Roof T op U.
8 FIGURE 5.
9 7. WIRING THE THERMOST A T (Cont.) c) Check each wire to ensure it is securely fastened, not broken, and exposed wires are not touching. 8. REASSEMBLE THE THERMOST A T No tools required – line up pins on circuit board with the corresponding terminal blocks.
10 Mode Fan Enter SCROLL / SET-UP BUTTONS ADJUST BUTTONS MESSAGE DISPLAY MAIN DISPLAY REMOTE NETWORK OVERRIDE COOL HEAT EM. -AUX DEHUM HUMIDIFY BIAS DIF1 DIF2 C FAN RH ON ROOM F C F R O FIGURE 6 Use the Check Out Procedure ( Figure 7 , on the next page) to determine if the thermostat is controlling the HV AC equipment.
11 CHECK-OUT PROCEDURE CAUTION: The following check-out procedure will turn the heating and cooling equipment on and off. Do not operate in cooling at low outdoor temperatures. Do not operate in heating at high outdoor temperatures. Refer to equipment manufacturer specifications for safe operating temperatures.
10. OPTIONAL HV AC SET -UP FEA TURES There are a number of HV AC features that can be configured for the particular application. These include temperature control options, display options and high / low balance points (heat pumps only). A) TEMPERA TURE CONTROL OPTIONS 1.
B) BALANCE POINTS (Cont.) 1. LOW BALANCE POINT – the outdoor temperature below which compressor terminals will not be energized. 2. HIGH BALANCE POINT – the outdoor temperature above which the auxiliary heat terminal will not be energized in the HEA T mode (does not ef fect Emergency Heat operation).
14 FIGURE 8 11. TO ACCESS THESE HV AC SET -UP FEA TURES (Cont.) Set-Up is menu driven but only one menu item is visible at a time. Figure 8 shows the entire Main Menu. Selecting any one of the Main Menu items (by pressing the Enter button) will enter a corresponding Sub-Menu.
15 FIGURE 8 (Cont.).
IMPORTANT! The B terminal is for reversing valve-heat. DO NOT connect the B terminal to common side of transformer. NOTE: HVAC installer may need to connect 24V AC to th e R and C terminals to check the HVAC operation.
FAN RELAY 2ND STAGE HEAT 1ST STAGE HEAT R TWO-STAGE FURNACE C G W1 Y1 W2 Y2 1ST STAGE COOL 2ND STAGE COOL L1 L2 120 VAC 24 VAC 1ST STG COOL 2ND STG COOL TWO-STAGE AIR CONDITIONER Y1 C Y2 IMPORTANT! The B terminal is for reversing valve-heat. DO NOT connect the B terminal to common side of transformer.
18 FAN RELAY 2ND STAGE HEAT 1ST STAGE HEAT R ROOF TOP UNIT C G W1 W2 Y2 Y1 L1 L2 120 VAC 24 VAC IMPORTANT! The B terminal is for reversing valve-heat. DO NOT connect the B terminal to common side of transformer.
FAN RELAY R AIR HANDLER C G Y1 1ST STAGE COOL L1 L2 120 VAC 24 VAC IMPORTANT! The thermostat B terminal is for reversing valve-heat. DO NOT connect the B terminal to common side of transformer.
FAN RELAY AUX HEAT R INDOOR HEAT PUMP UNIT C G W1 Y1 COMPRESSOR L1 L2 120 VAC 24 VAC IMPORTANT! The thermostat B terminal is for reversing valve-heat. DO NOT connect the B terminal to common side of transformer.
FAN RELAY 2ND STAGE HEAT 1ST STAGE HEAT R INDOOR HEAT PUMP UNIT C G W1 Y1 W2 Y2 1ST STAGE COMPRESSOR 2ND STAGE COMPRESSOR L1 L2 120 VAC 24 VAC G Y1 W1 Y2 W2 RH RC O APRILAIRE MODEL 8870 THERMOSTAT COMMUNICATION TERMINALS B C RSB RSR RSC R RSA B+ A- A+ B- REF REMOTE SENSOR(S) Y1 O B W1 C 1ST STG COMP.
G Y1 W1 Y2 W2 RH RC O APRILAIRE MODEL 8870 THERMOSTAT COMMUNICATION TERMINALS B C RSB RSR RSC R RSA B+ A- A+ B- REF REMOTE SENSOR(S) FAN RELAY 1ST STAGE HEAT R ONE STAGE FURNACE C G W1 Y1 1ST STAGE CO.
23 NOTES:.
24 NOTES:.
25 NOTES:.
B2202660 REV . 011/01 P .O . BO X 1467 • MADISON, WI 53701-1467 THE BE ST IN IN DOOR AIR CO M FORT ® The Aprilaire ® Indoor Air Comfort System is an integr ated group of air quality enhancement products designed to work with heating and cooling systems to make homes more comfortable.
Ein wichtiger Punkt beim Kauf des Geräts Aprilaire 8870 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Aprilaire 8870 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Aprilaire 8870 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Aprilaire 8870 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Aprilaire 8870 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Aprilaire 8870 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Aprilaire 8870 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Aprilaire 8870. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Aprilaire 8870 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.