P OWER P ROTECTION UPSta tion GXT ™ 6 kV A Maintenance Bypass U SER M ANUAL Transformerless with Configurable Output Distribution.
.
i T ABLE OF CONTENT S I MPORTANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
1 IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS This manual cont ains import ant instructions tha t should be c losely follow ed during installation and maintenance of this UPS tation GXT 6kV A Maintenance Byp ass. This product is designed fo r commercial / industr ial use only .
2 GLOSSARY OF SYMBOLS Risk of electrical shock Indicates W arning or Caution foll owed by import ant instructions Request s the user to consult the manual Equipment grounding conductor On Off i.
3 GENERAL DESCRIPTION Congratulation s on you r purchase of Liebert's UPS tation GXT 6 kV A Maintenance Bypass. As with every Liebert product, we st and behind our quality .
4 Maintenance Byp ass component layout UPS input switch (SW2) Output breaker (CB1) Configurable Output Distribution Bypass availability indicator (amber) UPS input power present (amber) Bypass switch .
5 MAJOR COMPONENT S The following is a genera l description of ea ch component and it s functions. Please review this section carefully , as it will give you a better understan ding as to how the UPS tation GXT 6 kV A Maintenance Byp ass operates.
6 CABLE INST ALLATION W IRING P REP ARATION For access to terminal blocks, see diagrams on pag e 4. P OWER C ABLE I NST ALLATIO N Refer to the chart be low when selecting cable s: ! CAUTION Please read this section thoroughly before attempting to install wiring to this unit.
7 Connecting Maintenance Byp ass to UPS t ation GXT6000T - 208 12 3 4 MAINTENANCE BYP ASS GND 1 208 VA C GND 3 GND 2 Utility TB1 UPS output TB3 UPS input TB2 2 132 132 13 4 L1 L2 L1 L2 +- Input Output Ext. battery Utility input L1 L2 NOTE GMB12 models are supp lied with an attached input power cord complete with L14-30 plug.
8 Connecting Maintenance Byp ass to UPSt ation GXT6000T - 208X 12 3 4 MAINTENANCE BYP ASS GND 1 208V GND 3 GND 2 Utility TB1 UPS output TB3 UPS input TB2 2 13 2 13 2 13 4 L1 L2 N L1 +- Input Ext. battery Utility input L2 NOTE GMB12 models are supplied with an attach ed input power cord complete with L14-30 plug.
9 Connecting Maintenance Byp ass to UPSt ation GXT6000T - 240X 12 3 4 MAINTENANCE BYP ASS GND 1 240V GND 3 GND 2 Utility TB1 UPS output TB3 UPS input TB2 2 13 2 13 2 13 4 L1 L2 N L1 +- Input Ext. battery Utility input L2 NOTE GMB12 models are supplied with an attached input power cord complete with L14 -30 plug.
10 W ALL-MOUNT DIAGRAM D IAGRAM FOR A TT ACHING U NIT TO W ALL Use the following diagram, which sh ows the location and measurement s of factory-cut mounting slot s, when prepar ing to attach the GXT Maintenance Bypass to a wall. Liebert recommend s using 1/4-20 mounting scre ws.
11 HARDWIRE OUTPUT OPTION This product is intended to be inst alled by a qualified electrician only . 1. COMPLETEL Y R EMOVE ALL P OWER FROM THE FRAME. If the Ma inte nance Bypass is connected to the UPS, disconnect external battery sup ply . 2. Remove the en d cover plate to access th e terminal block (see Accessing ter minal block below).
12 OPERATING PROCEDURES S T ART-UP AND INITIALIZATION Follow these steps in or der to start up the GXT 6kV A UPS while connected to the Maintenance Byp ass. O N M AINTENANCE B YP ASS 1. Set the Maintenance Bypa ss switch (SW1) to UPS position. 2. Close (position I ) UPS Input switc h (SW2).
13 S PECIFICATIONS T ypical Tr ansfer T ime (to or from maintenance byp ass) < 6 milliseconds Input V oltage Nominal 208V AC or 240V AC T otal Current 30A max. Operating Ambient T emperature 0° to +40° C S t orage Ambie nt T em perature -20° to +60° C Dimensions, W x D x H, in (mm) 8.
.
.
The Comp any Behind the Product s With over a million installations around th e globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a c.
Ein wichtiger Punkt beim Kauf des Geräts Liebert UPStation GXT (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Liebert UPStation GXT noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Liebert UPStation GXT - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Liebert UPStation GXT reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Liebert UPStation GXT erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Liebert UPStation GXT besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Liebert UPStation GXT verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Liebert UPStation GXT. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Liebert UPStation GXT gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.