Benutzeranleitung / Produktwartung SUA500PDR des Produzenten APC
Zur Seite of 14
Mou nt the UPS on D IN R ail This unit is designed to m ount on a heavy duty DI N rail or o n the back p anel of an e nclosure. Fo r details on DIN rail installatio n refe r to the DIN rail installation guide included in the DIN rail package. The DIN rail kit is not included .
2 Battery Ins tallation The UPS batt ery is shipp ed in a sep arate carton. Refer to the installation guide includ ed with the r eplacemen t battery for installation instructions . Front Pane l Conne ct Po wer and Equi pme nt to the U PS Hardwiring should be performed by a qualifi ed electric ian.
3 Connec tors Communic ation Port Contact Closure Port Output Con tact Ratings: Emerg enc y Pow er O ff The emergency power off (EPO) feature is user config urable. EPO provides im mediate de- energizing of connected eq uipment fro m a remote lo cation, wi thout switchin g to batter y operation .
4 Operation Oper ation UPS Displa y Panel Displ ay Pa nel I ndic ators and Func tion B utto ns Indicator LED Indicator Title Description On-Line The UPS is supplying utility power to the connected equipment (see T r oubleshooting ). A VR T rim The UPS is compensating for a high utility voltage (see T r oubleshooting ).
5 Operation Diagnostic Utility V oltage The UPS has a diagnostic feature that indicates the utili ty voltage. The UPS starts a self-test as part of this procedure. The self-test does not affect the voltage display . Press and hold the T est button to view the utility voltage bar graph indicator .
6 User Configurable Items User C onf igurab le It ems UPS se ttin gs Settings are adjusted thr ough Power Chute software or optiona l Network Ma nagement Card.
7 User Configurable Items Low Battery W arning 2 minutes 2, 5, 8, 1 1, 14, 17, 20, 23 minutes PowerChute software interface provides automatic, unattended shutdown when approximately two minutes of battery operated run time remains. The low-battery warning beeps are continuous when two minutes of run time remain.
8 Storage, Maintenance, Transport S tora ge, Ma int enanc e, T r ansp ort Storage Store the UPS covered in a cool, d ry locatio n with the batt eries fully charged. At 5° to 86 ° F (–15° to 3 0° C), charge the U PS battery ev ery six mo nths. At 86° to 113° F (30° to 45° C ), charge the UPS battery every three month s.
9 Troubleshooting T roub lesho oting Use this char t to solve m inor installati on and oper ation proble ms. Problem and/or Possible Cause Solution UPS will not turn on The battery is not connected properly . Check that the battery connector is fully engaged.
10 Troubleshooting All LEDs are off and the UPS is wir ed to input utility power The UPS is shut down or the battery is discharged from an extended outage. None: The UPS will restart automatically when utility power is restored and the battery has a sufficient char ge.
11 Troubleshooting There is no utility power There is n o utility power and the UPS i s off Use the cold start feature to supply power to the connected equipment from the UPS battery(s). Press and hold the T est button. The unit will emit two beeps, one short beep and one long beep.
12 Service Servic e If the unit re quires service , do not re turn it to the d ealer . Follow thes e steps: 1. Review the T roubleshooting section of the manual to eliminate common prob lems. 2. If the problem persists, contact APC Customer Support throu gh the APC W eb site , www .
13 Two-Year Factory Warranty T wo-Y e ar Factory W ar ranty This warranty applies only to the products you purchase for your use in accordance with this manual. T erms of warranty APC warrants its products to be free from defects in materials and workmanship for a period of two years from t he date of purchase.
© 201 1 APC by Schneider Electric. APC, the APC logo, Smart-UPS and Pow erChute are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners.
Ein wichtiger Punkt beim Kauf des Geräts APC SUA500PDR (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie APC SUA500PDR noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für APC SUA500PDR - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von APC SUA500PDR reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über APC SUA500PDR erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon APC SUA500PDR besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von APC SUA500PDR verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit APC SUA500PDR. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei APC SUA500PDR gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.