Benutzeranleitung / Produktwartung Smart-UPS RC 2000VA des Produzenten APC
Zur Seite of 21
990-3485B 01/2009 Smart-UPS ® RC Uninterruptible Power Supply T ower/Rack-Mount 4U XLI/XLICH/XLI-CC SRC1000/2000/3000 V A 220/230/240 V ac English.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/ 2000/3000 VA 220/230/240 Vac Tower/Ra ck-Mount 4U 3 Introduction Overview The American Power Conversion (APC ® ) Smart-UPS ® RC is a high performance uninterruptible power supply (UPS) that provides protection fo r electronic equipment from utility power blackou ts, brownouts, sags and surges.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/20 00/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 4 Specifications Environment al Specifications Physical Specifications T emperature Operating 0° to 40° C (32° to 104° F) This unit is intended for indoor use only .
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/ 2000/3000 VA 220/230/240 Vac Tower/Ra ck-Mount 4U 5 Front and rear p anels Rear panel Features The input circuit breaker protects th e UPS from extreme overload cond itions. Serial port for: • Power management software • Interface kits Use only interface kits supplied or appr oved by APC.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/20 00/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 6 Inst allation Units may vary in appear ance fro m those depicted in this manual. Always place UPS above XLBPs in rack-mount configuration. Connect all battery string s.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/ 2000/3000 VA 220/230/240 Vac Tower/Ra ck-Mount 4U 7 Output hardwire instructions Adher e to all nation al an d local electrical codes. Wiring must be performed by a qualified electrician. • Use 1.3 mm 2 (#16 A WG) wire (not suppl ied) • Maximum o utput rating: 220-240 V , 50 -60 Hz, 10 A 1.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/20 00/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 8 Inst all and conne ct batterie s This unit is equipped with battery modules. Each module must be connected to battery connectors on the chassis. 1. Install batt eries.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/ 2000/3000 VA 220/230/240 Vac Tower/Ra ck-Mount 4U 9 2-post rack-mount configuration This UPS is intended for installation in a 19”, two-post or fou r-post rack. For details on 4-post rail and rack in stallation refer to instructio ns in rail kit.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/20 00/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 10 Secure 2-post rack t o floor Inst all UPS in rack The UPS and XLBPs should be installed at or near bottom of rack. Always place UPS above XLBPs. Batteries must be r emoved from units p rior to installation in a rack .
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/ 2000/3000 VA 220/230/240 Vac Tower/Ra ck-Mount 4U 11 Connect internal batte ries This unit is equipped with internal battery modules. Each modul e must be connected t o battery connectors on chassis. 1. Install batteries.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/20 00/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 12 Start - u p Connect equipment and extern al battery p acks to UPS Prior to connecting the grounding cable, ensure that the UPS is NOT connect ed to utility or bat tery power .
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/ 2000/3000 VA 220/230/240 Vac Tower/Ra ck-Mount 4U 13 Operation Front p anel display Display p anel function buttons and indicators UPS function butt ons Button Function This button has three functions. • Press this button to turn on the UPS.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/20 00/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 14 UPS indicators Indicator Description The On Line LED illuminates when UPS is draw ing utility power and performing double conversio n to supply power to connected equipment.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/ 2000/3000 VA 220/230/240 Vac Tower/Ra ck-Mount 4U 15 Configuration UPS Settings Settings are adjusted t hrough PowerChute sof tware or optional SmartSlot ac cessory cards.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/20 00/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 16 Output voltage Allows user to select out put voltage while on-line.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/ 2000/3000 VA 220/230/240 Vac Tower/Ra ck-Mount 4U 17 Emergency Power Off (EPO) The Emergency Power Off (EPO) option is a safety f eature that will immediately remove power to all connected equipment.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/20 00/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 18 T roubleshooting Use the table below to solve minor installation and operatio n problems. Refer to the APC W eb site, www .apc.com for assistance with complex UPS probl ems.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/ 2000/3000 VA 220/230/240 Vac Tower/Ra ck-Mount 4U 19 Bypass and Fault LEDs are illuminated The UPS has automatically swit ched to Bypass mode. Bypass mode operation is the result of an internal UPS fault or an overload condition while operating on utility power .
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/20 00/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 20 Maintenance and transport Battery replacement This UPS has a replacable, hot-swappable battery module . Replacement is a safe pr ocedure, isolated from electrical hazards.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/ 2000/3000 VA 220/230/240 Vac Tower/Ra ck-Mount 4U 21 Service If the UPS requires service do not retu rn it to the dealer . Follow these steps: 1. Review the problem s discussed in T roubleshooting in this manual to eliminate com mon problems.
User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/20 00/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 22 T wo-Y ear W arranty The limited warranty pr ovided by American Power Conversion (APC®) in th is st.
Ein wichtiger Punkt beim Kauf des Geräts APC Smart-UPS RC 2000VA (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie APC Smart-UPS RC 2000VA noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für APC Smart-UPS RC 2000VA - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von APC Smart-UPS RC 2000VA reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über APC Smart-UPS RC 2000VA erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon APC Smart-UPS RC 2000VA besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von APC Smart-UPS RC 2000VA verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit APC Smart-UPS RC 2000VA. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei APC Smart-UPS RC 2000VA gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.