MGE Galaxy 5000 40–130 kV A 480 V Installation.
.
T able of Contents IMPORT ANT SAFETY INSTRUCTIONS - SA VE THESE INSTRUCTIONS ............................................................................................................... 1 Symbols Used ...............................................
Install Panels and Labels on 48” Battery Cabinet (Stand Alone Only) ...........21 Install Panels and Labels on 48” Battery Cabinet ................
IMPORT ANT SAFETY INSTRUCTIONS - SA VE THESE INSTRUCTIONS Symbols Used W ARNING: Indicates an electrical hazard, which, if not avoided, could r esult in injury or death. Caution: Indicates a hazard, which, if not avoided, could result in injury or death.
Specications AC Input AC input 40 kV A 50 kV A 60 kV A 80 kV A 100 kV A 130 kV A Nominal input voltage (V) 480 480 480 480 480 480 Input frequency (Hz) 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz Nominal i.
Recommended Fuses 40 kV A 50 kV A 60 kV A 80 kV A 100 kV A 130 kV A Input and output fuse rating (A) 160 160 160 160 315 315 990–5217 MGE Galaxy 5000 40–130 kV A 480 V 3.
Connect Input and Ground Cables in Single Systems Single Utility/Mains Systems 1. Remove the protection cover in the bottom of the enclosure. 2. Connect the AC input cables to the AC input terminals and to the UPS grounding plate. 3. Connect the AC output cables to the AC output terminals and to the UPS grounding plate.
Connect AC Input and Power Cables in Parallel Systems Single Utility/Mains Note: A maximum of two UPS units can be installed for Pn. 1. Remove the protection cover in the bottom of the enclosure. 2. Connect the AC input cables to the AC input terminals and to the UPS grounding plate for both UPS units in both UPS units.
Dual Utility/Mains Systems Caution: If the two UPS units are placed side by side, connect as indicated below . In other congurations, always make sure that the cables between the UPS units and the bypass source have the same cross-section and the same length.
Connect Communication Cables Overview of Communication Cables in Single Systems Caution: T o ensure suf cient isolation of control and communication cables, they must be run separately from the power cables. Reinforce the insulation of these control and communication cables if any risk of contact with the power cables exists.
Overview of Communication Cables in Parallel Systems Caution: T o ensure suf cient isolation of control and communication cables, they must be run separately from the power cables. Reinforce the insulation of these control and communication cables if any risk of contact with the power cables exists.
Connect Relay Communication Card Caution: Isolate and lock-out all power sources for this card before making connections. Never connect SEL V (safety extra low voltage) and non-SEL V circuits to the dif ferent outputs of the same card.
4. Connect conductors to the output terminals. A. General alarm B. Battery fault C. Load on UPS D. Load on automatic bypass E. Load on battery power F . Low battery warning 5. Put the cover back in place and secure it with the screws. 6. T ighten the screws to lock the cables.
1. Remove the wire jumper from the terminal block. 2. Connect the general shutdown NC contact to terminals 1 and 2 (SEL V). 3. Secure the cable. Connect Parallel Communication Cables in Redundant Parallel Systems Note: The supplied cables (33 ft) limit the distance between two UPS units to approximately 20 ft.
Connect Parallel Communication Cables in Capacity Parallel Systems Note: The supplied cables (33 ft) limit the distance between the two UPS units to approximately 20 ft. 1. Use the XMS02 and XMS03 terminals to create a loop between all UPS units as shown on the illustration (all the XMS02 and XMS03 terminals must be used).
2. Daisy-chain the UPS units using the XMS06 and XMS07 terminals. Fit a blue connector on the rst UPS units and a red plug on the last UPS unit (all the XMS06 and XMS07 connectors must be used).
14 MGE Galaxy 5000 40–130 kV A 480 V 990–5217.
Install an External Battery Cabinet Install A TIZ PCA and GND Busbar 26” and 32” Battery Cabinet 48” Battery Cabinet 1. If the A TIZ PCA option has been purchased, install the A TIZ PCA in the rst battery cabinet. 2. Install the Ground (GND) busbar .
The Battery Circuit Breaker Note: Only one circuit breaker is necessary even if several battery cabinets are connected. 1. The battery circuit breaker is pre-installed in the battery cabinet from factory . 2. Secure the base plate to the battery cabinet to support the circuit breaker .
Connect Power and Control Cables Power and Control Cable Connections for 26” and 32” Battery Cabinets 990–5217 MGE Galaxy 5000 40–130 kV A 480 V 17.
Power and Control Cable Connections for 48” Battery Cabinets 1. Route the power and control cables as shown. For multiple adjacent cabinets, cables interconnect through the middle of cabinet.
Mount the Battery Cells Caution: The battery cabinet must only be assembled by trained personnel. Caution: A minimum clearance of 150 mm is required between the top of the battery cells and the next shelf. 1. Place the battery cells on each shelves and interconnect them.
Install Panels and Labels on 26” Battery Cabinet (Stand Alone Only) 1. V erify proper lock operation in door . 20 MGE Galaxy 5000 40–130 kV A 480 V 990–5217.
Install Panels, Labels and Pallet on 26” Battery Cabinet 1. Place kickplates on top of unit. 2. Place interconnect brackets kit on top of unit. 3. Use corner board and damage label. Install Panels and Labels on 48” Battery Cabinet (Stand Alone Only) 1.
Install Panels and Labels on 48” Battery Cabinet 1. Place kickplates on top of unit. 2. Place interconnect bracket kit on top of unit. 3. Use corner board and damage label.
990–5217 MGE Galaxy 5000 40–130 kV A 480 V 23.
Worldwide Customer Support Customer support for this or any other product is available at no char ge: • Contact the Customer Support Center by telephone or e-mail. For local, country-specic centers: go to www .apc.com/support/contact for contact information.
Ein wichtiger Punkt beim Kauf des Geräts APC MGE Galaxy 5000 40 kVA (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie APC MGE Galaxy 5000 40 kVA noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für APC MGE Galaxy 5000 40 kVA - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von APC MGE Galaxy 5000 40 kVA reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über APC MGE Galaxy 5000 40 kVA erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon APC MGE Galaxy 5000 40 kVA besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von APC MGE Galaxy 5000 40 kVA verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit APC MGE Galaxy 5000 40 kVA. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei APC MGE Galaxy 5000 40 kVA gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.