536636-UIM-D-1211 SINGLE PIECE V ARIABLE SPEED AIR HANDLERS MODELS: A V*(C) SERIES INSTALLATION MANUAL ISO 9001 Certified Quality Management System LIST OF SECTIONS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
536636-UIM-D-1211 2 Johnson Controls Unitary Products 1. Install this air handler only in a location and position as specified in SECTION III of these instructions. 2. Always install the air handler to operate within the air handler’s intended maximum outlet air t emperature.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 3 DOWNFL OW AND HORIZONT AL CONVERSION (A V ONL Y) These air handler units are supplied ready to be installed in a upflow and right hand horizontal position. If unit requires left hand positioning, the unit must have the coil assembly repositioned.
536636-UIM-D-1211 4 Johnson Controls Unitary Products CLADDING CONFIGURA TION FOR DOWNF LO W INST ALLA TION (IF USED) T o reconfigure the cladding parts, remove the grille by pulling gently at the top. Once the grille is removed, the circuit breaker cover can also be removed.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 5 DUCT CONNECTIONS Air supply and return may be handled in one of several ways best suited to the installation.
536636-UIM-D-1211 6 Johnson Controls Unitary Products TXV METERING D EVICES If the model (C) numb er is of the following format: 4F , 4G , 4H, 4J, and 4K will have the coil with R410A TXV metering device installed at the factory .
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 7 DRAIN CONNECTIONS All drain lines should be trapped a minimum of three inches, should be pitched away from unit drain pan and should be no smaller than the coil drain connection.
536636-UIM-D-1211 8 Johnson Controls Unitary Products CONVENTIONAL L OW V OL T AGE CONTROL WIRING (24 V AC) The 24 volt power supply is provi ded by an int ernally wired low voltage transformer which .
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 9 . * Optional dehumidificat ion hu midistat switch cont acts open on humidit y rise. NOTES : 1. “Y/Y2” T erminal on air handler control board must be con nected for full CFM and appli cations requiring 60 second blower of f delay for SEER enhancement.
536636-UIM-D-1211 10 Johnson Controls Unitary Products The low voltage connections may be connected to the screw terminals or the quick connect terminals. T he screw terminals and t he quick con- nect terminals are phy sically connected o n the control board.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 11 The control energizes the fir st stage of electric heat immediately , the second stage 10 seconds after the call for second st age heat, and the third stage 20 seconds after the call for third stage heat.
536636-UIM-D-1211 12 Johnson Controls Unitary Products SECTION VIII: AIRFLO W AND COMFORT SETTING SELECTION AIRFLOW SELECTION The airflow and comfort setting se lection jumpers must be set properly at the time of installation for proper system operation.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 13 * May be 0 (no breaker) or 1 (with breaker). TA B L E 8 : Elect rical Data - Cool ing Only (60 Hz) Models T otal Motor Amp s Minimum Circuit Ampacity Max. O.C.P . Amps/T ype 1 Minimum Wire Size A.
536636-UIM-D-1211 14 Johnson Controls Unitary Products * May be 0 (no breaker) or 1 (with breaker). TA B L E 11 : Electrical Data - (For Single Source Power Supply) - Copper W ire - 208/23 0-1-60 Models Heater Models* Heater Amps 240V Field Wiring Min.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 15 T ABLE 13: Electrical Data - 208/230-3 -60 Models Heat Kit - Three Phase Max. Stat ic Min. Spe ed Ta p To t a l H e a t 1 kW S taging kW MBH W1 Only W2 Only W1 + W2 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V 24B 4HK06501025 0.
536636-UIM-D-1211 16 Johnson Controls Unitary Products T ABLE 16: Air Handler Air Flow Data HIGH/LOW SPEED COOLING AND HEA T PUMP AIRFLOW CFM m 3 /min JUMPER SETTINGS 24B 36C 24B 36C High Low High Low High Low High Low COOL T ap ADJ T ap 1088 707 1387 905 30.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 17 SECTION X: MAINTENANCE Filters must be cleaned or replaced when they become dirty . Inspect at least once per month. Th e frequency of cleaning depends upon the hours of operation and the local atmospheric conditions.
Subject to change without not ice. Published in U.S.A. 536636-UIM-D-1211 Copyright © 201 1 by Johnson Controls, In c. All ri ghts reserved. Supersedes: 536636-UIM-C-1010 Johnson Contro ls Unit a r y .
Ein wichtiger Punkt beim Kauf des Geräts Johnson Controls AV*(C) Series (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Johnson Controls AV*(C) Series noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Johnson Controls AV*(C) Series - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Johnson Controls AV*(C) Series reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Johnson Controls AV*(C) Series erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Johnson Controls AV*(C) Series besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Johnson Controls AV*(C) Series verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Johnson Controls AV*(C) Series. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Johnson Controls AV*(C) Series gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.