Benutzeranleitung / Produktwartung VB/VW-500 des Produzenten A.O. Smith
Zur Seite of 24
1 W ARNING: If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life. — Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
2 SAFE INST ALLA TION, USE AND SERVICE Y our safety and the safety of others is extremely important in the inst allation, use, and servicing of this boiler . Many safety-related messages and instructions have been provided in this manual and on your own boiler to warn you and others of a potential injury hazard.
3 GENERAL SAFETY.
4 SAFE INST ALLA TION, USE, AND SERVICE ....................................................................................................................................... 2 GENERAL SAFETY ..........................................................
5 For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed in every dwelling, building or structure used in whole or in p art.
6 CONNECTION DIAGRAM.
7.
8 SCHEMA TIC DIAGRAM VB/VW-500, 750 & 1000 SCHEMA TIC DIAGRAM.
9 LIGHTING & OPERA TION INSTRUCTIONS FOR MODELS VB/VW 500, 750 AND 1000:.
10 children to use a hot water t ap, or to draw their own bath water . Never leave a child or disabled person unattended in a bathtub or shower . The boiler should be located in an area that is inaccessible to the general public. T ABLE 1. Risk of Scalds.
11 sequences and safety features associated with a gas ignition control system. The system continuously performs various diagnostic test s to verify proper appliance and control operation.
12 the temperature is less than the operating setpoint minus the differential temperature and the thermostat input is closed then a call for heat is established and the system shift s to the run mode (green "Running" LED turns on). 5. The heating sequence begins by applying power to the pump.
13 waits for a heat request (determined by the Thermost at or controlling probe input s). All outputs are o f f i n this st ate except that if the Post-Circulate time i s set to continuous, th e pump will be on. When the heat request i s received, the system moves to the Pre-Circulate state.
14 if the blower prover does not activate after 15 seconds. This time allows the blower relay to activate, the blower to come up to speed, and the response from the blower prover to be filtered. • User Settings Screen: Each setpoint or user setting has either a limited selection of values, or a limited range of values.
15 kBtu rating of the boiler (0 to 5750kBtu in 10kBtu increments) The sof tware revision level of the MCB. • Current Error Screen: Displays the last error that the system has detected plus a time stamp of when the error occurred. (The time st amp is based on the elapsed hours value at the time the error occurred.
16 TROUBLESHOOTING IGNITION SYSTEM Fault Messages and Lockout S tatus (* = stage number: 1, 2, 3, or 4) FAUL T DISPLA YED DESCRIPTION RED LED LOCKOUT “Display Fail” Communications with UIM interrupted Continuous Auto Reset Check communication cable to UIM.
17 This is a pre-mix burner system. The flame is not supposed to be directly on the burner . The flame should be just above the burner deck approximately 1/8” and blue in color , see illustration. BURNER FLAMES Visually check flame characteristics through the view port located on the top head of the boiler .
18 Any safety devices including low water cutoffs used in conjunction with this boiler should receive periodic (every six months) inspection to assure proper operation. A low water cutoff device of the float type should be flushed every six months. Periodic checks, at least twice a year , should be made for water leaks.
19 lines with air or water and clear or replace the blocked portions of the line as necessary . Note that areas of the drain line which include a sag or low spot in the line will also form a condensate trap which can be removed by levelling the tube and does not indicate a blocked system.
20 NOTES.
.
22 NOTES.
23 LIMITED W ARRANTY A. O. Smith Corporation, the warrantor , extends the following LIMITED WARRANTY to the owner of this boiler: 1. If within TEN years after initial inst allation of the boiler, a he.
24 500 T ennessee W altz Parkway , Ashland City , TN 37015 Phone: 800-433-2545 w w w .hotwater .com E-Mail: p art s@hotwater .com.
Ein wichtiger Punkt beim Kauf des Geräts A.O. Smith VB/VW-500 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie A.O. Smith VB/VW-500 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für A.O. Smith VB/VW-500 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von A.O. Smith VB/VW-500 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über A.O. Smith VB/VW-500 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon A.O. Smith VB/VW-500 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von A.O. Smith VB/VW-500 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit A.O. Smith VB/VW-500. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei A.O. Smith VB/VW-500 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.