Hoshizaki “A Superior Degr ee of Reliability” www .hoshizaki.com Models KM-1301SAH/3, SWH/3, SRH/3 KM-1400SWH-M, SWH3-M KM-1601SAH/3, SWH/3, SRH/3 KM-1900SAH/3, SWH/3, SRH/3 KM-2100SWH3, SRH3 KM-2500SWH3, SRH3 KMH-2000SWH/3, SRH/3 Stackable Crescent Cuber Hoshizaki America, Inc.
2 W ARNING Only quali ed ser vice technicians should inst all and ser vice the appliance . T o obtain the name and phone number of y our local Hoshizaki Cer ti ed Ser vice Repr esentativ e, visit www .hoshizaki.com. No ser vice should be under tak en until the technician has thor oughly r ead this Ser vice Manual.
3 CONTENTS Impor tant Saf et y Inf or mation ................................................................................................. 6 I. Construction and W ater/R efrigeration Cir cuit Diagr am ..............................................
4 C . Set tings and A djustments ............................................................................................ 45 1 . Def ault Dip Switch Set tings .................................................................................... 45 a) "E" and "G" Contr ol Board without Har v est P ump Timer Oper ation .
5 23. KM-1 900SRH with URC-21F ............................................................................... 82 24. KM-1 900SRH with URC-22F ............................................................................... 83 25. KM-1 900SRH3 with URC-21F .
6 Impor tant Safety Inf ormation Throughout this man ual, notices appear t o bring your at tention t o situations which could result in death, serious injur y , damage t o the appliance, or damage t o proper t y . W ARNING Indicates a hazar dous situation which could r esult in death or serious injury .
7 W ARNING, continued • The appliance is not intended f or use by per sons (including children) with r educed ph y sical, sensor y , or mental capabilities, or lac k of e xper ience and knowledge , unless they ha ve been giv en super vision or instr uction concerning use of the appliance by a per son responsib le f or their safety .
8 I. Construction and W ater/R efrigeration Cir cuit Diagram A. KM Construction 1 . Air-Cooled Models (SAH/3) Ev aporat or Assembl y Spra y T ubes Inlet W ater V alv e W ater Supply Inlet Hot Gas V al.
9 Ev aporat or Assembl y Spra y T ubes Inlet W ater V alv e W ater Supply Inlet Hot Gas V alv e Junction Bo x W ater Regulating Va l v e Check V alv es (refrigeration) Contr ol Bo x Liquid Line V alv .
10 Evapor at or Assembl y Spra y T ubes Inlet W ater V alv e W ater Supply Inlet Hot Gas V alv e Junction Bo xes Receiv er Check V alv es (refrigeration) Contr ol Bo x Liquid Line V alv e Drier T rans.
11 B. KMH Construction 1 . W ater -Cooled Models (SWH/3) Ev aporat or Assembl y Spra y T ubes Inlet W ater V alv e Float S witch W ater P ump W ater Supply Inlet Junction Bo x W ater Regulating V alv .
12 2. Remot e Models (SRH/3) Ev aporat or Assembl y Spra y T ubes Inlet W ater V alv e Float S witch W ater P ump W ater Supply Inlet Junction Bo x Check V alv es (refrigeration) Contr ol Bo x Liquid .
13 C. W at er/R efr igeration Cir cuit Diagr am 1 . Air-Cooled Models (SAH/3) W at er Supply Cleaning V alv e Float Switch Drain Check V alv e Thermostatic Expansion V alves Compr essor Hot Gas Va l v.
14 2. W at er -Cooled Models (SWH/3/-M) W at er Supply Cleaning V alv e Float Switch Drain Check V alv e Thermostatic Expansion V alves Compr essor Hot Gas Va l v e Check V alv es High-P ressure Switc.
15 3a. Remot e Models (SRH/3) Ex cept KM-250 0SRH3 Condenser Unit with Headmast er (CPR) W at er Supply Cleaning V alv e Float Switch Drain Check V alv e Expansion V alv es Compr essor Hot Gas Va l v .
16 3b. Remot e Models (SRH3) KM-250 0SRH3 Condenser Unit without Headmast er (CPR) W at er Supply Cleaning V alv e Float Switch Drain Check V alv e Expansion V alv es Compr essor Hot Gas Va l v e Chec.
17 II. Sequence of Operation and Service Diagnosis A. Sequence of Operation Flo w Char t 1 . "E" and "G" Control Boar d without Harvest P ump Timer Operation Components Energized w.
18 • WV time: 6 min. or the length of har vest min us 50 sec. (S4 dip switch 7), whiche ver is shor t er . Do not adjust S4 dip s witch 7 out of the f actory position.
19 B. Service Diagnosis W ARNING • The appliance should be diagnosed and repair ed only b y quali ed ser vice personnel t o reduce the risk of death, electr ic shoc k, serious injur y , or re .
20 1 . "E" and "G" Control Boar d without Harvest P ump Timer Diagnosis 3) P ow er On : T ur n on the power suppl y , then mov e the control s witch to the "ICE" position. A 5-sec. delay occur s. • "E" Contr ol Board: CB red "PO WER OK" LED tur ns on.
21 5) Initial Harvest Cy c le – LEDs 1, 4, and 2 are on. WV continues. Comp , FMR, and HGV energiz e. CB monitor s the warming of the ev aporat or via the ther mist or locat ed on the suction line. When the thermistor r eaches 48°F (9°C), CB reads 3.
22 b) Comp and FMR Diagnosis : If Comp and FMR de-energiz e once freeze begins , check that appliance has not shut of f on HPS ("POWER OK" LED of f). If so , chec k "3)b) HPS Diagnosis" abov e. If "POWER OK" LED is on, chec k for 1 1 5V AC at CB K1#1 (V) or #9 (V) to neutr al (W).
23 h) F r eeze T ermination Diagnosis: Af ter 5 min. in freeze , disconnect CB K5 FS connector . 1 5 sec. later appliance should s witch out of the freez e cy cle (1 5 second dela y af ter FS opens bef ore t er minating the freez e cy cle). If appliance remains in freez e longer than 1 5 sec.
24 8) Normal Harv est Cy c le – Same as the initial harvest c y cle. Return to st ep 5 abov e. Note: Appliance continues t o cy cle until BC is satis ed or power is turned of f .
25 2. "G" Control Boar d with Harvest P ump Timer Diagnosis 3) P ow er On : T ur n on the power suppl y , then mov e the control s witch to the "ICE" position. A 5-sec. delay occur s. CB red "PO WER OK" LED and gr een "BC CLOSED" LED turn on.
26 5a) Initial Harvest Cy c le – LEDs 1, 4, and 2 are on. WV and X1 1 r ela y continue . Comp , FMR, HGV , and X1 0 rela y energiz e . CBmonitor s the warming of the e v aporat or via the ther mist or locat ed on the suction line. When the thermistor r eaches 48°F (9°C), CB reads 3.
27 If 1 1 5V A C is present on t er minal #3(P) and not on t erminal #5 (Y), replace X1 0 rela y . If 1 1 5V A C is present on X1 0 rela y ter minal #7 (Y) and PM is not ener giz ed, check f or 1 1 5V A C at X1 0 rela y terminal #4 (R) to neutral (W) and t erminal #6 (DBU) to neutr al (W).
28 c) WV and HGV Diagnosis : If WV is ener gized, chec k for 1 15V A C at CB K1 #6 (O) t o neutral (W). If 1 1 5V A C is pr esent af ter PM ener giz es in har v est cy cle, r eplace CB. If 1 1 5V A C is not present, r eplace WV (bypassing). If HGV did not de-energiz e at the end of har v est, chec k f or 1 1 5V AC at CB K1 #2 (P) t o neutral (W).
29 7) Pump-Out Cy cle – LEDs 1, 3, and 2 are on (1 0/20 second pump-out). Timing of the rst pump-out is det er mined by S4 dip s witch 5& 6. See the tab le belo w . "G" Control Boar d Settings S4 Dip S witch Set ting Pump-Out F requency 1st Pump-Out "G" Control Boar d No.
30 8) Normal Harv est Cy c le – Same as the initial harvest c y cle. Return to st ep 5a) abov e. Note: Appliance continues t o cy cle until MBC is satis ed or power is s witched of f . The appliance alw ay s restar ts at the 1 -min. ll cy cle.
31 C. Control Boar d Check Bef or e r eplacing CB that does not sho w a visib le def ect and that y ou suspect is bad, alw ay s conduct the follo wing chec k pr ocedur e. This procedur e will help you v erify your diagnosis. Alar m R eset: If CB is in alar m (beeping), press the "ALARM RESET" b ut ton on CB while CB is beeping.
32 D . Bin Contr ol Check BC shuts down the icemak er within 1 0 sec. when ice contacts the ther mostatic b ulb , reg ardless of the cy cle at activation. NO TICE When the ambient t emperature is belo w 45°F (7°C), BC opens and shuts down the appliance e v en if the ice storage bin is empty .
33 E. Float S witch Chec k and Cleaning FS is used to det er mine that there is suf ficient w ater in the wat er tank af ter the 1 -min. ll c y cle and af ter each harvest cy cle. FS is also used to det er mine that the appr opriate v olume of wat er has been conv er ted int o ice befor e switching out of the fr eez e cy cle.
34 2. Float Switc h Cleaning Depending on local wat er conditions, scale ma y b uild up on FS . Scale on the switch can cause the oat t o stic k. In this case, FS should be cleaned. 1) T ur n of f the power suppl y . 2) Remo ve the fr ont panel, then mo v e the contr ol s witch to the "OFF" position.
35 F . Thermist or Check T o check thermistor r esistance , f ollow the steps belo w . 1) T ur n of f the power suppl y . 2) Remo ve the fr ont panel. Mov e the contr ol s witch to the "OFF" position. 3) Remo ve the contr ol bo x cov er . 4) Remo ve the thermistor fr om the r efrigerant tubing.
36 G. Diagnostic T ables 1 . No Ice Pr oduction No Ice Pr oduction - Possib le Cause 1. P ower Suppl y a) Of f, b lown fuse , or tripped break er . b) Not within specications. 2. Main T ransf ormer (3 phase model) a) V oltage tap s witch not set t o pr oper v oltage .
37 No Ice Pr oduction - Possib le Cause 15 . P ump Motor a) Motor winding open. b) Bearing wor n out or loc ked r otor . c) Def ectiv e capacitor . d) Mechanical seal worn out. 16 . Ther mostatic Expansion V alv e a) Bulb loose. b) Operating erraticall y .
38 F reeze-Up - P ossible Cause 12 . Hot Gas V alv e a) Closed or restricted. 13 . Liquid Line V alv e a) Open. F reeze Cyc le 1. Evapor at or a) Scaled up . b) D amaged. 2. Spra y T ubes and/or Spray Guides a) Dir ty . b) Out of position. 3. Refrigerant Charge a) L o w.
39 Low Ice P r oduction - P ossible Cause Long F reeze Cyc le 1. Evapor at or a) Scaled up , dir ty . 2. Float Switch See "II.E. Float Switch Chec k and Cleaning" a) Scaled up , dir ty . b) Float sticking . c) Def ectiv e s witch. 3. Inlet W ater V alv e a) Leaking by .
40 III. Controls and A djustments • A Hoshizaki e x clusive contr ol board is emplo yed in KM and KMH series appliances. • All models are pr etest ed and f actor y adjust ed. • F or a contr ol boar d chec k pr ocedur e, see "II.C . Control Boar d Check.
41 A. Control Boar d L a y out 1 . "E" Control Boar d "E" Control Boar d P ar t Number 2A1 41 0-02 "E" Contr ol Boar d Micropr ocessor (control boar d r e vision le vel i.
42 2. "G" Control Boar d "G" Control Boar d P ar t Number 2A3792-0 1 "G" Contr ol Boar d • K4 (red) Connect or Mechanical Bin Contr ol or K4 Jumper (thermostatic bin co.
43 B. LED Lights and A udible Alarm Saf eties 1 . "E" Control Boar d At star tup , a 5-second delay occur s while the control boar d conducts an int er nal timer check.
44 2. "G" Control Boar d At star tup , a 5-second delay occur s while the control boar d conducts an int er nal timer check. A beep occur s when the control s witch is mov ed to the "ICE" position. The red "PO WER OK" LED indicat es pr oper contr ol v oltage and r emains on unless a control v oltage pr oblem occur s.
45 C. Set tings and Adjustments NO TICE Dip s witches ar e f actor y set. F ailure t o maintain f actory set tings ma y adver sel y af fect perf or mance and warr anty cov erage .
46 F reeze Timer (9 & 1 0) P ump-Out Fr equency Control (5 & 6) P ump-Out Timer (3 & 4) Har v est Timer (1 & 2) F actory Use (8) Bin Contr ol Select or (7) "E" Contr ol Board.
47 3. Pump-Out Timer (S4 dip switc h 3 & 4) NO TICE On models with har v est pump timer , do not adjust 3 off and 4 on. P ump does not run in pump-out rotation in this set ting .
48 4. Pump-Out F requency Contr ol (S4 dip switch 5 & 6) The pump-out frequenc y contr ol is f actor y set. Generall y no adjustment is requir ed. How e ver , where wat er qualit y is bad and the icemaker needs a pump-out mor e of t en, the pump-out frequenc y can be adjust ed.
49 b) Harvest P ump Timer: "G" Contr ol Boar d NO TICE F actory set for pr oper operation. Do not adjust. Adjustment outside of the f actor y def ault set ting ma y r esult in damage t o the appliance. Depending on the har v est pump timer set ting, the pump mot or either sta ys of f or is energiz ed the last 50 seconds of har vest.
50 8. Float Switc h Select or (S5 dip switc h 1): "G" Control Boar d NO TICE Do not adjust. This must be lef t in the f actor y def ault position or the icemaker will not operat e corr ectl y . 9. Re ll Counter (S5 dip switch 2 thr ough 5): "G" Contr ol Boar d NO TICE Do not adjust.
51 IV . Refr igeration Cir cuit and Component Ser vice Inf or mation W ARNING • This appliance should be diagnosed and repair ed only b y quali ed ser vice personnel t o reduce the risk of death, electr ic shoc k, serious injur y , or re . • Mov e the control s witch to the "OFF" position and turn off the po wer supply .
52 2. Brazing W ARNING • R-404A itself is not ammab le at atmospheric pressur e and temperatur es up t o 1 7 6°F (80°C). • R-404A itself is not e xplosiv e or poisonous.
53 4) Close the low -side val v e and high-side val v e on the g auge manif old. 5) Disconnect the gauge manif old hose from the v acuum pump and at tach it t o a refrigerant service cylinder . Remember t o loosen the connection and purge the air fr om the hose.
54 B. Component Service Infor mation NO TICE When r eplacing a component listed belo w , see the notes t o help ensur e pr oper operation. Component Notes Compr essor 1 phase: Install a new st ar t capacitor , r un capacitor , and star t rela y . 3 phase: Install a new magnetic cont actor .
55 C. W at er R egulating V alve Adjustment (w ater -cooled models) The wat er regulating v al v e is f actor y set, and generall y no adjustment is requir ed. Howe ver , when necessar y , adjust the wat er regulator using the f ollowing pr ocedure. 1) P r epar e a ther momet er t o chec k the condenser drain t emperature .
56 V . Maintenance The maintenance schedule belo w is a guideline. More fr equent maintenance ma y be requir ed depending on wat er quality , the appliance's en vir onment, and local sanitation regulations W ARNING • Only quali ed ser vice technicians should service the appliance.
57 VI. Pr eparing the Icemak er f or Per iods of Non-Use NO TICE • When st oring the appliance f or an e xt ended time or in sub-fr eezing t emperatur es, f ollo w the instructions below t o pr e v ent damage.
58 3. On wat er -cooled model, remo v e the w ater fr om the wat er -cooled condenser: 1) Make sur e the power suppl y is off , then remo ve the fr ont, t op , and r ight side panels. 2) Close the condenser wat er supply line shut-of f val ve . If connected t o a closed loop sy stem, also close the condenser r eturn line shut-of f v al v e .
59 VII. Disposal The appliance contains r efrigerant and must be disposed of in accor dance with applicable national, st at e , and local codes and r egulations.
60 VIII. T echnical Infor mation W e r eser v e the r ight to mak e changes in specications and design without pr ior notice. A. Specication and P erf ormance Data P r essur e data is r ecor ded at 5 min. into fr eezing cycle . The data not in bold should be used f or r ef erence onl y .
61 2. KM-1 30 1SAH3 SPECIFICAT ION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 9.5 A ( 5 Min. Fr eeze AT 104°F / W T 80°F) MINIMUM CIRCUI T AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTR IC & W ATER C ONSUMPT ION 90/70°F 70/50°F ELECTR IC W (kW H /100 lbs.
62 3. KM-1 30 1SWH SPECIFICAT ION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wi re with neutral f or 115V) AMPERAGE 8.2 A ( 5 Min. Fr eeze AT 104°F / W T 80°F) MINIMUM CIRCUIT AMP ACITY 20 A MAXIMUM FUSE SIZE 20 A 90/70°F 70/50°F ELECTR IC W (kW H/100 lbs.
63 4. KM-1 30 1SWH3 SPECIFICATION SHEET 208-230/60/3 6.1 A ( 5 Min. Freeze AT 104°F / WT 80°F) 20 A 20 A 90/70°F 70/50°F 1840(3.4) 1770(3.2) 248(19.
64 5. KM-1 30 1SRH with URC-14F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115V) AMPERAGE 13.5A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.
65 6. KM-1 30 1SRH3 with URC-14F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 10.7A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2140(4.3) 2090(3.
66 7 . KM-1 40 0SWH-M SPECIFICAT ION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (2 W ire) AMPERAGE 9.7 A ( 5 Min. Freeze AT 104°F / W T 80°F) MINIMUM CIRCUIT AMPACITY 15 A MAXIMUM FUSE SIZE 15 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
67 8. KM-1 40 0SWH3-M SPECIFICAT ION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 7.1 A ( 5 Min. Freeze AT 104°F / W T 80°F) MINIMUM CIRCUIT AMPACIT Y 15 A MAXIMUM FUSE SIZE 15 A ELECTRIC & W AT ER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
68 9. KM-1 60 1SAH SPECIFICATION SHEE T AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115V) AMPERAGE 15.0 A (5 Min. Freeze AT 104°F/WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.
69 1 0. KM-1 60 1SAH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 12.0 A (5 Min. Freeze AT 104°F/ W T 80°F) MINIMUM CIRCUIT AMPACIT Y 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
70 1 1 . KM-1 60 1SWH SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral for 115V) AMPERAGE 13.4 A (5 Min. Freeze AT 104°F/ W T 80°F ) MINIMUM CIRCUIT AMPACIT Y 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & W AT ER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
71 1 2. KM-1 60 1SWH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 9.0 A (5 Min. Freeze AT 104°F/ W T 80°F) MINIMUM CIRCUIT AMPACIT Y 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
72 1 3. KM-1 60 1SRH with URC-21F Auxiliary Codes: R-0, R-1, and some S-1 This data applies t o units with an 8 l/min w at er v al v e . The 8 l/min water v alv e is par t number 3U0 1 1 1 -02 and has J248-032 stamped on the side of the val ve f acing the rear of the unit.
73 1 4. KM-1 60 1SRH with URC-21F Auxiliary Codes: some S-1 and S-2 and L ater This data applies t o units with a 1 5 l/min or 1 1 l/min water v alv e. The 1 5 l/min wat er v al v e is par t number 3U0 1 1 1 -0 1 and has J248-030 stamped on the side of the val ve f acing the r ear of the unit.
74 1 5. KM-1 60 1SRH with URC-22F Auxiliary Codes: S-2 and L ater This data applies t o units with an 1 1 l/min wat er v alv e. The 1 1 l/min water v alv e is either par t number 4A1 1 7 6-04 or 4A5251 -04 and has the par t number stamped on the side of the v al v e f acing the front of the unit.
75 1 6. KM-1 60 1SRH3 with URC-21F Auxiliary Codes: R-0, R-1, and some S-1 This data applies t o units with an 8 l/min w at er v al v e . The 8 l/min water v alv e is par t number 3U0 1 1 1 -02 and has J248-032 stamped on the side of the val ve f acing the rear of the unit.
76 1 7 . KM-1 60 1SRH3 with URC-21F Auxiliary Codes: some S-1 and S-2 and L ater This data applies t o units with a 1 5 l/min or 1 1 l/min water v alv e. The 1 5 l/min wat er v al v e is par t number 3U0 1 1 1 -0 1 and has J248-030 stamped on the side of the val ve f acing the r ear of the unit.
77 1 8. KM-1 60 1SRH3 with URC-22F Auxiliary Codes: S-2 and L ater This data applies t o units with an 1 1 l/min wat er v alv e. The 1 1 l/min water v alv e is either par t number 4A1 1 7 6-04 or 4A5251 -04 and has the par t number stamped on the side of the v al v e f acing the front of the unit.
78 1 9. KM-1 90 0SAH SPECIFICATION SHEET AC SUPPLY VOLTAGE 208- 230/60/1 (3 wire with neutral 115V) AMPERAGE 14.4 A (5 Min. Freeze AT 104°F / W T 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
79 20. KM-1 90 0SAH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208- 230/60/3 AMPERAGE 8.59 A (5 Min. Freeze AT 104°F/W T 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & W AT ER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
80 21 . KM-190 0SWH SPECIFICATION SHEET AC SUPPLY VOLTAGE 208- 230/60/1 (3 wire wi th neutral 115V) AMPERAGE 12.5 A (5 Min. Freeze AT 104°F/W T 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & W AT ER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
81 22. KM-1 90 0SWH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208- 230/60/3 AMPERAGE 8.4 A (5 Min. Freeze AT 104°F/ W T 80°F) MINIMUM CIRCUIT AMPACIT Y 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
82 23. KM-1 90 0SRH with URC-21F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208- 230/60/1 (3 wire with neutral 115V) AMPERAGE 14.9 A (5 Min. Freeze AT 104°F/ W T 80°F) MINIMUM CIRCUIT AMPACIT Y 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
83 24. KM-1 90 0SRH with URC-22F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208- 230/60/1 (3 wire with neutral 115V) AMPERAGE 14.9 A (5 Min. Freeze AT 104°F/ W T 80°F) MINIMUM CIRCUIT AMPACIT Y 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
84 25. KM-1 90 0SRH3 with URC-21F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 11.0 A ( 5 Min. Freeze AT 104°F / W T 80°F) MINIMUM CIRCUIT AMPACIT Y 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
85 26. KM-1 90 0SRH3 with URC-22F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 11.0 A (5 Min. Freeze AT 104°F/W T 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
86 27 . KM-21 0 0SWH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208- 230/60/3 AMPERAGE 10.5 A (5 Min. Freeze AT 104°F/W T 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & W AT ER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
87 28. KM-21 0 0SRH3 with URC-22F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208- 230/60/3 AMPERAGE 12.5 A (5 Min. Freeze AT 104°F/W T 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
88 29. KM-250 0SWH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208- 230/60/3 AMPERAGE 14.2 A ( 5 Min. Freeze AT 104°F/W T 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
89 30. KM-250 0SRH3 with URC-23F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208- 230/60/3 AMPERAGE 17.7 A ( 5 Min. Freeze AT 104°F/W T 80°F) MINIMUM CIRCUIT AMPACITY 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
90 31 . KMH-20 0 0SWH SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral 115V) AMPERAGE 12.1 A (5 Min. F reeze AT 104°F/W T 80°F) MINIMUM CIRCUIT AMPACIT Y 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
91 32. KMH-20 0 0SWH3 SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/3 AMPERAGE 7.7 A (5 Min. F reeze AT 104°F/W T 80°F) MINIMUM CIRCUIT AMPACIT Y 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & W AT ER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
92 33. KMH-20 0 0SRH with URC-22F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with neutral 115V) AMPERAGE 14.9 A (5 Min. Freeze AT 104°F/ W T 80°F) MINIMUM CIRCUIT AMPACIT Y 30 A MAXIMUM FUSE SIZE 30 A ELECTRIC & W ATER CO NSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
93 34. KMH-20 0 0SRH3 with URC-22F SPECIFICATION SHEET AC SUPPLY VOLTAGE 208- 230/60/3 AMPERAGE 9.9 A (5 Min. Freeze AT 104°F/W T 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & W AT ER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (k W H/100 lbs.
94 B. W iring Diagrams 1 . Diagrams without Harv est P ump Timer Rela ys ("E" and "G" Contr ol Boar ds) a) KM-1 60 1SWH, KM-1 60 1SRH, KM-1 90 0S_H, KMH-20 0 0S_H * Contr ol T ransf or mer Output 1 0.
95 b) KM-1 60 1SWH3, KM-1 60 1SRH3, KM-1 90 0S_H3, KM-21 0 0S_H3, KM-250 0S_H3, KMH-20 0 0S_H3 * Contr ol T ransf or mer Output 1 0.5V at 1 15V * High-P ressur e S witch W ater -Cooled Model Remote Mo.
96 A uxiliar y C ode T -0, U-0 * 2. Diagrams with Harv est P ump Timer Rela ys ("G" Contr ol Boar d) a) KM-1 30 1S_H A uxiliary Code T -0, U-0 * High-P ressur e S witch W ater -Cooled Model Air and Remote Models Cut-out 384± 22 PSIG 41 2± 22 PSIG Cut-in 284±22 PSIG 327±22 PSIG 0 0 Contr ol T ransf or mer Output 1 0.
97 b) KM-1 30 1S_H3 A uxiliary Code T -0, U-0 * * High-P ressur e S witch W ater -Cooled Model Air and Remote Models Cut-out 384± 22 PSIG 41 2± 22 PSIG Cut-in 284±22 PSIG 327±22 PSIG 0 0 Contr ol T ransf or mer Output 1 0.
98 c) KM-1 30 1S_H A uxiliary Code U-1 and Later and KM-1 60 1SAH * * High-P ressur e S witch W ater -Cooled Model Air and Remote Models Cut-out 384± 22 PSIG 41 2± 22 PSIG Cut-in 284±22 PSIG 327±22 PSIG 0 0 Contr ol T ransf or mer Output 1 0.
99 d) KM-1 30 1S_H3 A uxiliary Code U-1 and Later and KM-1 60 1SAH3 * * High-P ressur e S witch W ater -Cooled Model Air and Remote Models Cut-out 384± 22 PSIG 41 2± 22 PSIG Cut-in 284±22 PSIG 327±22 PSIG 0 0 Contr ol T ransf or mer Output 1 0.
10 0 e) KM-1 40 0SWH-M * * High-P ressur e S witch W ater -Cooled Model Cut-out 384± 22 PSIG Cut-in 284±22 PSIG 0 Contr ol T ransf or mer Output 1 0.
101 f) KM-1 40 0SWH3-M * * High-P ressur e S witch W ater -Cooled Model Cut-out 384± 22 PSIG Cut-in 284±22 PSIG 0 Contr ol T ransf or mer Output 1 0.
Ein wichtiger Punkt beim Kauf des Geräts Hoshizaki SRH/3 KM-2100SWH3 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Hoshizaki SRH/3 KM-2100SWH3 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Hoshizaki SRH/3 KM-2100SWH3 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Hoshizaki SRH/3 KM-2100SWH3 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Hoshizaki SRH/3 KM-2100SWH3 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Hoshizaki SRH/3 KM-2100SWH3 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Hoshizaki SRH/3 KM-2100SWH3 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Hoshizaki SRH/3 KM-2100SWH3. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Hoshizaki SRH/3 KM-2100SWH3 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.