Benutzeranleitung / Produktwartung WEB-700 des Produzenten Honeywell
Zur Seite of 28
INSTALLATION INSTRUCTIONS Put Bar Code Here 95-7776-03 CE AND OTHER LOGOS WEB-700 WEB-700-O CP-700 APPLICATION The WEB-700 and CP-700 are compact, em bedded controller/ser ver platf or ms that allow integrated control and management of external devices ov er the Inter net.
WEB-700 WEB-700-O CP-700 95-7776—0 3 2 ABOUT THIS GUIDE This document covers the mounting and wirin g of the T r idium® WEB/CP-700 (T -700) controller . It assumes that you are an engineer , technician, or service person who is perf or ming control system installation.
WEB-700 WEB-700-O CP-700 3 95-7776—03 PR ODUCT DESCRIPTION The WEB/CP-700 controll er is a compac t embedded processor pl atform using on-board Flash memor y f or backup , in an ex pandable DIN-modular package.
WEB-700 WEB-700-O CP-700 95-7776—0 3 4 . Fig. 2. WEB/CP-700 main controller boar d and 2 option cards uninstalled. As a 7 ser ies controller , the WEB/CP-700 uses a Po werPC 440EPx processor , 1G B Flash storage, and 1 GB DDR-2 RAM. TCP/ IP access is via two standard Gigabit Ether net por ts.
WEB-700 WEB-700-O CP-700 5 95-7776—03 T echnical Specifications WEB/CP-700 PLATFORM • P o werPC 440Epx @ 667MHz processor (speed approximate due to spread spectrum clock). • 1GB on-board NAND Flash storage. • 1 GB DDR-2 333Mhz RAM (maximum Ja va Heap size 384MB).
WEB-700 WEB-700-O CP-700 95-7776—0 3 6 PREPARATION Unpack the WEB/CP-700 and inspect the package contents f or damaged or miss ing components. If damaged, notify the appropriate carrier at once and retur n any damaged components for immediate repair or replacement.
WEB-700 WEB-700-O CP-700 7 95-7776—03 WARNING A 120V a c or 240V ac cir cuit power s the NPB-PWR-UN-H power supply f or the controller . 15 Vdc input (DC only) to controller . Disconnect power bef ore in stallation or ser vicing to prevent electr ical shock or equipment damage.
WEB-700 WEB-700-O CP-700 95-7776—0 3 8 Ph ysical Mounting The follo wing information app lies about physically mounting the unit. • Y ou can mount the WEB/CP-700 in any orientation. It it not necessar y to remov e the cov er bef ore mounting. • Mounting on a 35mm wide DIN rail is recommended.
WEB-700 WEB-700-O CP-700 9 95-7776—03 T o mount on DIN rail 1. Securely install the DIN rail with at least two screws, near the tw o rail ends. 2. P osition the NPB-PWR- UN-H power supply module on the rail, t ilting to hook DIN rail tabs over one edge of the DIN rail (Fig.
WEB-700 WEB-700-O CP-700 95-7776—0 3 10 Boar d Lay o ut Fig. 5 shows the location of conn ectors, optio n slots, and other f eatures of th e main board in the WEB/CP-700 . F or side views o f communications por ts and other features, see Fig. 6, page 13.
WEB-700 WEB-700-O CP-700 11 95-7776—03 ABOUT EXPANSION OPTIONS The WEB/CP-700 provides for field-installab le expansion using these types of options: • Option card — Install on connectors inside the WEB/C P-700 base u nit. See About Option Ca rds, page 11.
WEB-700 WEB-700-O CP-700 95-7776—0 3 12 OPTION CARD COM PORT ASSIGNMENTS COM por t assignments for option cards installed in a WEB/CP-700 st ar t at COM5, with Slot 1 e valuated f irst, then Slot 2. (COM1 and COM2 are alwa ys assigned to the onboard RS-232 and RS-485 por ts, while COM3 and COM4 are reserved f or slots.
WEB-700 WEB-700-O CP-700 13 95-7776—03 WIRING DETAILS See Fig. 5, page 10 to locate connectors and ot h er components on the WEB/CP-700 controlle r . Make connections to the WEB/CP-700 in the follo wing order . 1. Install any option board (LON, RS-485, RS-232, etc.
WEB-700 WEB-700-O CP-700 95-7776—0 3 14 SERIAL There are two “RS” serial por ts on the W EB/CP-700 base board. Each has a UAR T capable of operation up to 115,200 b aud. At the bottom of the board (see Fig. 6, page 13) is an RS-232 por t using an DB-9 plug (male) connector .
WEB-700 WEB-700-O CP-700 15 95-7776—03 Fig. 7. Gr ounding and po wer wiring con nections to NPB-PWR-UN-H module. Po w e r W i r i n g There are two power options f or the WEB/ CP-700 controlle r : the NPB-PWR- UN-H power supply module (typical), or a NPB- WPM-US (W all Mount AC Adapter).
WEB-700 WEB-700-O CP-700 95-7776—0 3 16 Wiring NPB-PW R-UN-H input power and ear th ground. 1. Remove power from the A C circuit being wired to the NPB-PWR-UN-H—see pre vious . 2. Remov e the NPB-PWR-UN-H cov er . T o do this, press in the f our tabs on both ends of the unit, and lift the cov er off.
WEB-700 WEB-700-O CP-700 17 95-7776—03 Contact Inputs Three contact inputs (CIs) are availab le on a 6-position conn ector ne xt to the 2-posi tion external batter y conn ector . CIs are typically used to monitor nor mally-closed (N.C .) alar m contacts , if a vailab le on a UPS and/or the “door tamper” switch of an enclosure.
WEB-700 WEB-700-O CP-700 95-7776—0 3 18 EXTERNAL 12V BAC KUP BATTERY A 2-position connector provides suppor t for an e xternal 12V sealed lead -acid (SLA) type rechargable batter y . For more details, see About the Backup Batteries, page 20. Fig. 10.
WEB-700 WEB-700-O CP-700 19 95-7776—03 Wiring to Remote I/O Modules Wiring to remote I/O modules typically provides both 15Vdc power and 12V batter y backup , along with RS-485 communications to the module s.
WEB-700 WEB-700-O CP-700 95-7776—0 3 20 If after applying power , the ST A TUS LED goes out, or if t he BEA T LED comes on (steady) and sta ys lit longer than 2 minutes, contact your local distributor for technical a ssistance. See also “About LEDs” on page 21.
WEB-700 WEB-700-O CP-700 21 95-7776—03 ABOUT LEDS The WEB/CP-700 provides a number of LEDs on its main board. On ly the Status and Hear tbeat LEDs are visible on the cov er .
WEB-700 WEB-700-O CP-700 95-7776—0 3 22 Required NiMH Battery Maintenance Batter y life e xpectancy is a function of its discharge cycles (the number of discharges and their depth) and the ambient temperature of the batter y dur ing nor mal o peration.
WEB-700 WEB-700-O CP-700 23 95-7776—03 NO TE: Dispose of the use d NiMH batter y properly . 4. Unplug the NiMH batter y from the main board connector (see Fig. 12). 5. Using a 1/4" (6mm) nutdriver , unfasten and re tain the two k ep nuts that secure the m etal batter y brack et to the shield, and remov e the shield and batter y pack.
WEB-700 WEB-700-O CP-700 95-7776—0 3 24 Replacing the WEB/CP-700 NO TE: Before handling circuit boar ds, discharge an y accumulated static b y touching a nearby ear th ground.
WEB-700 WEB-700-O CP-700 25 95-7776—03 Returning a Defective Unit F or proper credit on an in-warranty unit, ship the def ective unit to T r idium within 30 days . NO TE: If the defective unit is under warranty , please fo llow return instructions pr ovided in this section.
WEB-700 WEB-700-O CP-700 95-7776—0 3 26 CER TIFICATIONS Federal Comm unications Commission (FCC) This equipment generates, uses, and can radiate radio frequency energy , and if not instal led and used in accordance with the instruction ma nual, ma y cause interference with radio communicati ons.
WEB-700 WEB-700-O CP-700 27 95-7776—03 T AB MOUNTING DIMENSIONS Measurements are in inches and (mm). DIN mounting is recommended ov er tab mounting. See Fig . 3, page 8. NO TE: Electronic and pr inted versions of this guide may not show the dimensio ns to scal e.
WEB-700 WEB-700-O CP-700 Automation and Control Solu tions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U .S. Registe red T rademark © 2012 Hone ywell International I nc. 95-7776—03 M.S. Re v .
Ein wichtiger Punkt beim Kauf des Geräts Honeywell WEB-700 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Honeywell WEB-700 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Honeywell WEB-700 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Honeywell WEB-700 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Honeywell WEB-700 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Honeywell WEB-700 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Honeywell WEB-700 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Honeywell WEB-700. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Honeywell WEB-700 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.