Benutzeranleitung / Produktwartung TR71 des Produzenten Honeywell
Zur Seite of 24
OPERATING GUIDE 63-2719-03 Zio ® /Zio Plus LCD W all Modules TR70, TR71, TR75 with Sylk ® Bus APPLICATION The Zio TR70 Series (TR70, TR70-H, TR71, TR71-H, TR75, and TR75-H OS numbers) LCD W all Modu.
ZIO ® /ZIO PLUS LCD W ALL MODULES 63-2719—0 3 2 TR70 SER IES F EATURES * A maximum of f our Zios ma y be wired on a single Sylk bus, with no more than one TR70 per bus. Compatibility The TR70 Series LCD Wall Modules operate with the Sylk Enhanced Spyder Controller or the Sylk Enhanced Comf or tP oint Controller.
ZIO ® /ZIO PLUS LCD W ALL MODULES 3 63-2719—03 SETUP AND CONF IGURATION Initial Setup and Conf iguration Once the wall module i s wired to the controller , you configure the wall module using the PC-based, Niagara W orkbench T ool. Refer to the applicable programmab le controlle r User’ s Guide.
ZIO ® /ZIO PLUS LCD W ALL MODULES 63-2719—0 3 4 SAV E BUTTON A SA VE button is av ailable on screens that allow entries or selections. It is enabled whene ver any change is made on th e screen, and allows you to sa ve y our selections/entr ies at any time.
ZIO ® /ZIO PLUS LCD W ALL MODULES 5 63-2719—03 General Settings Using Fig. 6 and T able 4 as a guide, conf igure the General Settings. An image of the selected model and its capabiliti es updates in the d isplay at the bottom of the window . Fig. 6.
ZIO ® /ZIO PLUS LCD W ALL MODULES 63-2719—0 3 6 Fig. 8. Adding a Cate gor y . ADDING A PARAMETER Fig. 9 shows the categories and parameters listed in tree f or mat in the mai n window . The parameters are listed und er each categor y . Click on the bo x ne xt to the categor y item to e xpand that item i n the tree .
ZIO ® /ZIO PLUS LCD W ALL MODULES 7 63-2719—03 P ARAMETER T YPES AND LIMITS See Fig. 12 for an illustration of the Par ameter T yp e drop down list. There is a limit to th e number of param eters that ca n be configured. In addition to the parameter limit, there is also a memor y limit (see “Memor y Usage” on page 4).
ZIO ® /ZIO PLUS LCD W ALL MODULES 63-2719—0 3 8 Fig. 14. Select from the existing library or de fine enumer ated val u e s . HIGH/LOW LIMIT P ARAMETER LINKING This option allows f or changes to a setpoint's high or low limit directly at a Zio b y linking the high and low limit to a related setpoint.
ZIO ® /ZIO PLUS LCD W ALL MODULES 9 63-2719—03 Home Scree n Options I Home Screen Options selection from Wizard Menu Fig. 15, shows the Home Screen Options window and lists the Home screens currently configured, where y ou can add, edit, or remov e them.
ZIO ® /ZIO PLUS LCD W ALL MODULES 63-2719—0 3 10 Occupancy and Ov err ide I Ocupancy and Override selection from Wizard Menu Fig. 17 shows the Occupancy and Override options in the main window f or standard and advanced settings. Clic king the Sh ow Adv anced Settings button displa ys the advanced settings.
ZIO ® /ZIO PLUS LCD W ALL MODULES 11 63-2719—03 OVERRIDE SETTINGS Clicking the Settings button displa ys the Override to Occupancy settings pop-up (see Fig. 18), where you can select Continuous (default) or Ti med (hours or days) Ov err ide settings.
ZIO ® /ZIO PLUS LCD W ALL MODULES 63-2719—0 3 12 F an Command I F an Co mmand selection from Wizard Menu Fig. 19, shows the F an Comman d options in the main window f or standard and advanced settings. Clicking the Show Advanced Settings b utton displays the adv anced settings.
ZIO ® /ZIO PLUS LCD W ALL MODULES 13 63-2719—03 System Status and Command I System Sta tus and Command selection from Wizard Menu Fig. 20 shows the System Status and Command options in the main window . Clicking the Show Advanced Settings b utton displays the advanced settings.
ZIO ® /ZIO PLUS LCD W ALL MODULES 63-2719—0 3 14 Schedule/Time I Schedule/Time Options selection from Wizard Menu Fig. 21. Schedule /Time f or TR75. Fig. 22. Schedule/Tim e for TR70/TR71 is not suppor t ed so all options are gra yed out. As shown in Fig.
ZIO ® /ZIO PLUS LCD W ALL MODULES 15 63-2719—03 Pa s s w o r d I P ass word Option selection from Wizard Menu Fig. 23. Assign P asswo rd for TR71/TR75 As shown in Fig. 23, the TR 71/TR75 can be conf igured with a pass word that limits access to contractor le vel system changes from the TR71/TR75.
ZIO ® /ZIO PLUS LCD W ALL MODULES 63-2719—0 3 16 Pre view I Pre view selection from Wizard Menu Pre view is a great wa y to verify all your configuration and setup par ameters to ensu re that they work exac tly the wa y you want them to function.
ZIO ® /ZIO PLUS LCD W ALL MODULES 17 63-2719—03 Completing the Setup and Conf iguration F or custom configurations, begin with “Custom Configurations Only”, otherwise continue with “All Configurations”. Custom Conf igurations Only If you are customizing a configur ation, use the Sa ve to Library button to sav e your conf iguration.
ZIO ® /ZIO PLUS LCD W ALL MODULES 63-2719—0 3 18 Link Slots on the Wire Sheet This section descr ibes how parameters may be linked to the wall module. Refer the user to the Sp yder User Guide, f orm 63-2662, for more specif ic information on variables and wire sheet logic.
ZIO ® /ZIO PLUS LCD W ALL MODULES 19 63-2719—03 OPERATING THE ZIO W ALL MODULE There are two modes of operation: • Contractor mode provides f eatures a contractor would use such as selecting the Home screen, selecting parameters the tenant can view , and monitoring /modifying controller parameters, which includes balancing.
ZIO ® /ZIO PLUS LCD W ALL MODULES 63-2719—0 3 20 Fig. 30. Sample Contractor display sho wing Home screen setup . SET VIEW MORE allows the contractor to provide para meter access (view only or adjustable) to the tenant’ s VIEW MORE softk ey . • Clicking the VIEW MORE softk ey displa ys the first configured parameter as sho wn Fig.
ZIO ® /ZIO PLUS LCD W ALL MODULES 21 63-2719—03 Sample Contractor LCD Displa ys The contractor mode allows advanced options using the softke ys. Contractor mode also allows f or customizing the T enant view including setting th e tenant’ s Home screen and View More access .
ZIO ® /ZIO PLUS LCD W ALL MODULES 63-2719—0 3 22 Fig. 38. Select th e da y . Fig. 39. Select the Event to edit the time and occupancy state. T enant Mode Operation The tenant, using the softke ys and ar row ke ys, ma y ch ange the setpoint, f an spee d, system mode (heat/cool), or initiate ov erride, if these features ar e conf igured.
ZIO ® /ZIO PLUS LCD W ALL MODULES 23 63-2719—03 Fig. 42. Override display f or T enant. SYSTEM & VIEW MORE Depending on the configuration, this softkey allo ws the tenant to change the system state and view/adjust configured parameters (see Fig.
ZIO ® /ZIO PLUS LCD W ALL MODULES Automation and Control Solutions Honeywell Internationa l Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U .S. Registe red T rademark © 2012 Hone ywell International I nc. 63-2719—03 S .
Ein wichtiger Punkt beim Kauf des Geräts Honeywell TR71 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Honeywell TR71 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Honeywell TR71 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Honeywell TR71 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Honeywell TR71 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Honeywell TR71 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Honeywell TR71 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Honeywell TR71. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Honeywell TR71 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.