PRODUCT DATA 63-2489—2 T775A,B,C,D Remote T emperature Controller APPLICATION The T775 family of Electr onic Remo te T emperatur e Controllers provide on-off temperat ure control for ducts, t anks, chillers, heating and refri geratio n units, and other application s where electronic accuracy in addition to re mote sensing is desired.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 2 ORDERING INFORMATION When purchasing replacement and modernizat io n products from your TRADELINE® whol esaler or distributor , refer to the TRADELINE® Catalog or price sheets for complete ordering number .
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 3 63-2489—2 Contact Ratings: 1/2 hp; 9.8 FLA, 58.8 LRA at 120 V ac. 1/2 hp; 4.9 FLA, 29.4 LRA at 240 V ac. 125 V A pilot du ty at 120/240 V a c. 10A at 24 V ac (resistive). Approvals: Underwriters Laboratories Inc.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 4 Fig. 3. Feature locations for T775 A,B. Fig. 4. Feature locations for T775 C,D. SELECT SET ENTER 12 3 4 1 2 3 4 SA SB C F SENSOR A SENSOR B TOD 24V 5 6 120V COM 240V OUTPUT 2 OUTPUT 1 OUTPUT 3 OUTPUT 4 NO COM NC NO COM NC NC COM NO M7423 F/C SELECTION DIP SWITCHES FOR SENSOR SELECTION.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 5 63-2489—2 INSTALLATION When Installing this Product... 1. Read these instructions carefully . Failure to follow them could damage the product o r cause a hazardo us condition. 2. Check ratings given in instructions and on the produ ct to ensure the product is sui table for your application.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 6 Fig. 7. Senso r mounted on w all. Fig. 8. Parallel-series wiring of sensors. WIR ING CAUTION Electrical Shock or Equipment Damage Hazard. Can shock individuals or sh ort equipment circuitry . Disconnect power supply before installation.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 7 63-2489—2 OPERATION Control Algorithm On/Off Control The T775AC operate with one temperature input supplied by the remote sensor while T775B,D have two temperatu re inputs. The T775A,B,C,D are all capable of providi ng up to four stages of on/off control relay ou tputs.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 8 2. For two sensor models (T775B), determine which loads will be controlled fro m sensor A or sensor B and enter on the worksheet. 3. Determine setpoint (Setpt) and switching differential (Diff) for each load and enter on the worksheet.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 9 63-2489—2 This selection is accomplished in the Select screen scrolling loop: 1. T o lock on to either sensor , use the Select key to scroll through the loop to the temperature prompt of interest. 2. S top at Sensor A or Sensor B sensed temperature point.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 10 CHECKOUT Error Messages There are seven error messages that can display in response to T775 software or hardware problems. The error Codes that can flash on the display are: • SF: Sensor Failure — A flashing SF indicates an o ut-of-range or defective sensor .
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 11 63-2489—2 Fig. 10. Checkout T able and checkout example with Sensor A = 6 8°F and Sensor B = 73°F . SELECT ENTER SET M7426A HEA T OR COOL MODE DIFFERE.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 12 Fig. 1 1. T wo-st age control, 24 V ac input, 24 V ac load. COOL MODE HEA T MODE RELA Y 1 AND 2 ENERGIZED RELA Y 1 AND 2 ENERGIZED NULL NULL R.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 13 63-2489—2 Fig. 12. T w o-stage control, 120 or 240 V ac input; 120 or 240 V ac load. BLK WHT 120 V AC LOAD 1 LOAD 2 M7422A DIFFERENTIAL 2 DIFFERENTIAL 1.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 63-2489—2 14 Fig. 13. Four stage control, 120 or 240 V ac input, 120 or 240 V ac load. HEA T MODE M7424A NULL DIFFERENTIAL 3 TEMPERA TURE RISE RELA Y 1 ,2,.
T775A,B,C,D REMOTE T EMPERATURE CONTROLLER 15 63-2489—2 Fig. 14. Four-st age control, 24 V ac input; 24 V ac load. HEA T MODE NULL DIFFERENTIAL 3 TEMPERA TURE RISE SETPOINT 3 RELA Y 1,2 AND 3 ENERGI.
Automation and Co ntrol Solutions Honeywell Internation al Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Dri ve North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered T rademark © 2005 Honeywell International I nc.
Ein wichtiger Punkt beim Kauf des Geräts Honeywell T775A (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Honeywell T775A noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Honeywell T775A - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Honeywell T775A reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Honeywell T775A erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Honeywell T775A besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Honeywell T775A verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Honeywell T775A. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Honeywell T775A gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.