INST ALLA TION INSTRUCTIONS 69-2076-01 S9360A, S9361A, S9370A, S9371A Integrated Boiler Controllers APPLICATION These integra ted boiler cont rol modules prov ide ignition sequence , flame monitorin g and safet y shutof f for either intermittent pilo t spark ignition or direct hot surface ignition heating systems.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 2 Fig. 1. S936X In tegrated Boiler Controller , dimensions in in. (mm). Electrical Ratin gs: Line V oltag e: 120 V ac, 60 Hz (220 V ac, 50 Hz on speci fic model numb ers). T ransformer: Nominal 24 V ac (maximum 30 V ac, minimum 18 V ac).
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 3 69-2076—01 T able 1. Recom mended Igniti on Cables. T ransformer Requireme nt: Add curren t ratings of module, pil ot valve, main valve , vent da mper and any othe r compone nts o f the con trol system to deter mine transfor mer size require ment.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 4 WARNING Fire or Explosi on Hazard. Can cause seve re injury , death or property damage. 1. The modu le can malfun ction if it gets wet, leading to ac cumulation of explo sive gas.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 5 69-2076—01 Fig. 3. Align module with slo ts in control box. Wire the Syst em WARNING Electrical Shock Hazard. Can cause seve re injury , death or property damage. Disconnect the power su pply before making wir ing connections to preve nt electrical shock or equipment dama ge.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 6 NOTE: Cable length must be 36 in. (0.9 m) or less. The cable mus t not be in co ntinuous c ontact with a metal surface or spark voltage w ill be greatly reduced. Use c eramic or plastic standoff insulators as re quired.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 7 69-2076—01 Fig. 4. S park Ignition W iring (S936X). M24216 CIRCULA TOR SP ARK IGNITER FLAME SENSE INDUCER L1 L2 GND GND 24 V AC TRANSFO.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 8 Fig. 5. Hot Surf ace Ignition W iring (S937X). Common Connectors SENSOR 1 SENSOR 2 GAS CONTROL MV MV PRESSURE SWITCH LIMIT SWITCH M24218 ENVIRACOM DISPLA Y ENVIRACOM DIAGNOSTIC 24 V AC TRANSFORMER L2 L1 GND FLAME SENSE HOT SURF ACE IGNITER CIRCULA TOR INDUCER GND T able 3.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 9 69-2076—01 a Indicates optio nal connection b ased on configura tion. HSI Model Specific Co nnectors In addit ion to the com mon connectors lis ted above, T able 4 identi fies conn ectors avai lable on th e HSI model board assemblies.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 10 T able 5. Spark Model Specif ic Connec tors. a Indicates optio nal connections bas ed on configur ation. T able 6. Pin Confi guration. T emperature Control T emperatur e control s etpoint on t he module can be adjusted as de scribed in the fo llowing sections.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 1 1 69-207 6—01 “SP_” Setpoint. “Df_” Setpoint Differential (se lect models). “°F_” Degrees Fahrenheit Then press th e UP or DOW N button unt il the parameter has reached t he desired valu e.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 12 Mounting Sensor and Thermowell The remote upper temperature senso r is installed in an immersion well (Fig. 8) that extends int o the supply w ater side of the boiler. Immersion Well Fitting The immersion well must snugly f it the sensing bu lb for good thermal re sponse.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 13 69-2076 —01 Fig. 10. Operat ing Sequence. IGNITION SEQUENCE IDLE ALL OUTPUTS OFF CHECK LEAKA GE/ SET FLAME BIAS WAIT LIMIT SWITCH CLOS.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 69-2076— 01 14 T ROUBLESHOOTING IMPORT ANT 1. The following service procedures a re provided as a general g uide. Follow ap pliance manufac - turer ’s service instruction s if available.
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS 15 69-2076 —01 T able 7. Error Codes. Segment Display Definitio n Pressure Switch failed to open (contacts stuck clo sed). Flame sens ed out of nor mal sequenc e (before ope ning gas va lve or after closing gas valve).
S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS Automation and Cont rol Solution s Honeywell Internatio nal Inc. Honeywell Limited-H oneywell Limitée 1985 Douglas Dr ive North 35 Dynamic Drive Golden Valley, MN 55 422 Toronto, Ontario M1V 4Z9 customer.
Ein wichtiger Punkt beim Kauf des Geräts Honeywell S9360A (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Honeywell S9360A noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Honeywell S9360A - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Honeywell S9360A reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Honeywell S9360A erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Honeywell S9360A besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Honeywell S9360A verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Honeywell S9360A. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Honeywell S9360A gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.