PRODUCT D A T A Copyright © 1996 Honeywell Inc. • All Rights Reserved X-XX UL 60-2337-3 R4140G Flame Safeguard Programming Controls APPLICA TION The R4140G Flame Safeguard Programmers provide flame.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 2 ORDERING INFORMA TION When purchasing replacement and modernization products from your TRADELINE ® wholesaler or distributor , refer to the TRADELINE ® Catalog or price sheets for complete ordering number or specify order number .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 3 NOTE: Allowable inrush can be up to ten times the pilot duty rating. EXAMPLE: Pilot duty rating = 50 V A. At 120V , running current is: 50 120 = 0.42A . Maximum allowable inrush is ten times 0.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 4 Fig. 1. Mounting dimensions of the Q520A wiring subbase in in. (mm). 13/64 (5) DIAMETER (4) (FOR MOUNTING ON 4 X 4 [102 X 102] JUNCTION BOX.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 5 Accessories: W136A T est Meter (includes 1 17053 Meter Connector Plug); has SPL position with damping for testing self- checking flame detection systems. 1 17053 Meter Connector Plug (for older W136A models).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 6 OPERA TION Models with Preignition Interlocks Fig. 3 shows all contacts in the standby position (zero seconds). The opening and closing times are shown adjacent Fig. 3. Simplified schematic dia gram of R4140G1015 Programmer .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 7 Fig. 4. Timer sequence for R4140G1015 Programmer . Step-By-Step Operation (R4140G1015) Start And Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 8 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 9 Fig. 5. Simplified schematic dia gram of R4140G1106 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 10 Fig. 6. Timer sequence for R4140G1106 Programmer . Step-By-Step Operation (R4140G1106) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 11 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 If using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 12 Fig. 7. Simplified schematic dia gram of R4140G1049 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 13 Fig. 8. Timer sequence for R4140G1049 Programmer . M10055 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTERRUPTED PILOT/IGN.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 14 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 15 Fig. 9. Simplified schematic dia gram of the R4140G1056 and R4140G1064 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 16 Fig. 10. Timer sequence for R4140G1056 and R4140G1064 Programmer s. M10056 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTE.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 17 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or first stage fuel valve when using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 18 Fig. 11. Simplified schematic dia gram of R4140G1171, R4140G122 and R4140G1114 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 19 Fig. 12. Timer sequence for R4140G1171, R4140G1122 and R4140G1114 Programmer s. M10057 1 2 3 4 5 6 TERMINAL NUMBERS (CIRCLED). SLOPE DEPENDS ON MOTOR TIMING. TIMER STOPS AT 60 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 20 Ignition T rials 70 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (and terminal 7, main oil valve solenoid, if using direct spark ignition of oil).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 21 Fig. 13. Simplified schematic dia gram of R4140G1148 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 22 Fig. 14. Timer sequence for R4140G1148 Programmer . Step-By-Step Operation (R4140G1148) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 23 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 24 Fig. 15. Sample bloc k diagram of field wiring f or R4140G1007, R4140G1015 and R4140G1106 Programmer s.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 25 Fig. 16. Sample bloc k diagram of field wiring f or R4140G1049, R4140G1056, R4140G1064, R4140G1114, R4140G1122, R4140G1148 and R4140G1171 Programmer s.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 26 Optional Hookups f or T wo-Sta ge Switching or Intermittent Pilot/Ignition (Nonmodulating Oil Burners) If modulation of the firing rate is.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 27 M10061 TIMER SECONDS INTERRUPTED PILOT/IGNITION OR 1ST STAGE OIL VALVE 20 SECOND INTERRUPTED PILOT/IGNITION MAIN FUEL VALVE OR 2ND STAGE OIL VALVE 0 10 20 30 40 50 60 70 80 90 100 110 120 3 1 1 2 3 2 12 5 6 TERMINAL NUMBERS (CIRCLED).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 28 Honeywell Europe S.A. 3 Avenue du Bourget B-1140 Brussels Belgium Honeywell Asia Pacific Inc.
Ein wichtiger Punkt beim Kauf des Geräts Honeywell R4140G (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Honeywell R4140G noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Honeywell R4140G - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Honeywell R4140G reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Honeywell R4140G erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Honeywell R4140G besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Honeywell R4140G verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Honeywell R4140G. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Honeywell R4140G gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.