Benutzeranleitung / Produktwartung H-IM-80C des Produzenten Heatcraft Refrigeration Products
Zur Seite of 24
Beacon II Smart Controller Installation & Operation Manual H-IM-80C ( 12/03) December , 2003 Part No. 25000601 Replaces H-IM-80B (12/02) Features ................................................................ 2-3 Installation ...................
2 The Beacon II Smart Controller performs all the standard Beacon functions with the additional benefit of: a) Remote mounting for easy access b) Remote monitoring and programming c) Controlling four .
3 Features of the Beacon II Smart Controller • Monitoring of the complete refrigeration system. • Programming of a variety of parameters for the optimum control of the refrigeration system.
4 INST ALLA TION The Beacon II Smart Controller should be installed in a location where the large Liquid Crystal Display (LCD) can be viewed easily , yet is secure and vibration free. Because of the LCD screen, the Beacon II Smart Controller should not be mounted where it will experience temperatures below 40 ° F or above 100 ° F.
5 WIRING All 24 volt wiring must be run separate from the line voltage wiring . All Low voltage wiring must be 18 gauge minimum and must be run separate from high voltage wiring. The maximum distance from the Beacon II Smart Controller t o the Master Evaporator is 1000 ft.
6 For the second system, connect MUL TI OUT 2 from the Beacon II Smart Controller t o the MUL TI IN on the Beacon II board on the Evaporator in this second system. Then connect MUL TI IN 2 from the Beacon II Smart Controller t o t h e MUL TI OUT on the Beacon II board on the Evaporator on this second system.
7 will continue to operate and maintain the box temperature. This occurs only if an external power supply is used on the Beacon II Smart Controller . If the Beacon II Smart Controller LCD displays all 88888 this indicates that the power supply is below 18 V AC.
8 • COOLING: Depressing this button will start the system in the cooling cycle immediately (The 4 minutes “Hold Off” is bypassed). This button will illuminate to indicate that the Cooling function is “ON”. System operation will be as described under REFRIGERA TION MODE in the Beacon II installation manual.
9 • SUPRHT – Superheat: 4 to 20 ° F . Use “SETPOINT” slide-bar to select desired superheat temp., then press “ENTER.” If multiple evaporators are connected, use the “+” button to set other evaporators on this system. • SMT DFT : Smart Defrost: On/Of f.
10 • EXVSET - Expansion valve step setting (Stepper Motor setting 0 to 255 steps: use + button to check other evaporators if Master/slave) • SUCTMP – Evaporator Suction temperature (Measured by .
11 • *SPSEN - Suction pressure transducer shorted, open or not installed • *ODSEN - Outdoor temperature sensor shorted • *SUPLO - Superheat too low • *SHTDN - Compressor shutdown (High or low refrigerant pressure or low oil pressure) The error code will flash alternately with the normal display information.
12 The system will pumpdown, cycle off and try to restart for three consecutive times. Each try will be after the 4 minutes “Hold Off” period, for the following fault conditions.
13 Real-time data can also be recorded and stored on a Desktop PC while the PC is connected to the Beacon II Smart Controller . The PC will continuously request information from the Beacon II Smart Controller regarding system operation and setup and record this data every minute, in an Excel spreadsheet.
14 PC & MODEM ACCESS For access to the system from a PC directly or via a modem, the SMART II Software must be purchased and installed on your PC. With PC access, ALL system settings can be monitored, changed or logged from a remote location. The stored data can be viewed in an Excel spreadsheet.
15 SYSTEM DEF AUL TS Following are factory defaults for the parameters which can be programmed in the Beacon II Smart Controller . If the user does not select a setting for any of the following parameters, the default will be used. It is important the user set ALL parameters based of their needs.
16 Parts Parts List HRP P ART P ART DESCRIPTION NUMBER Beacon II Control Board 28910101 T emperature Sensor kit – White Leads* 89904902 T ransformer 120/24 volt – 40 V A 22529601 T ransformer 240/.
17 Beacon II T roubleshooting Guide PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check Primary Power Supply Disconnect 1. Check fuses and circuit breakers 2. Check V oltage to Evaporator Transformer Go to 2. Check field wiring for breaks LED is not lit.
18 PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check wiring connection to the board • Correct field wiring to the board 2. Low Pressure Safety (LPS) T ripped: • Check for correct refrigerant type .
19 Beacon II T roubleshooting Guide (continued) PROBLEM Step ACTION ITEM IF OK IF NOT OK E9 Multi-out to Multi-in 1. Check for 24 volts power to the board 1. If no voltage, see “LED is not lit” above Communication Wiring for low voltage, see “88888 LED display” (only shows after initial 2.
20 PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check system operation: Is it running? 1. Check power to condensing unit Check position of Service Mode switches Check compressor overloads and contactor 2. Check system charge 2. Add or remove refrigerant to proper charge 3.
21 Wiring Diagrams.
22 Wiring Diagrams.
23 Wiring Diagrams.
Heatcraft Refrigeration Products LLC 2175 West Park Place Blvd • Stone Mountain, GA 30087 (770) 465-5600 • Fax (770)465-5990 www .heatcraftrpd.com Since product improvement is a continuing effort, we reserve the right to make changes in specifications without notice.
Ein wichtiger Punkt beim Kauf des Geräts Heatcraft Refrigeration Products H-IM-80C (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Heatcraft Refrigeration Products H-IM-80C noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Heatcraft Refrigeration Products H-IM-80C - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Heatcraft Refrigeration Products H-IM-80C reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Heatcraft Refrigeration Products H-IM-80C erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Heatcraft Refrigeration Products H-IM-80C besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Heatcraft Refrigeration Products H-IM-80C verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Heatcraft Refrigeration Products H-IM-80C. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Heatcraft Refrigeration Products H-IM-80C gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.