990-7031C, Rev ision 4 12/99 APC Smart-UPS Uninterruptible Pow er Supply Models 1400XLT, 2200XLT, 3000T, 5000T User’s Manual.
Entire con tents copy rig ht ©1999 by Am erican Pow er Con version . All rig hts res erved. Reprodu ction in wh ole or in part w ith out permis sion is prohibited. Sm art-UPS is a reg istered tradem ark of APC. A ll other tradem arks are the property of th eir respectiv e ow ners.
990-7031C, Rev ision 4 12/99 Smart UPS Safety Guide English This Sa fety Guide contains im portant instr uctions that should be follow ed during insta llation and m aintenanc e of the APC equipm ent and batte ries. It is intended f or APC customers w ho setup, install, reloc ate, or m aintain APC equipm ent.
.
990-7031C, Rev ision 4 12/99 Table of Contents Introduction........................................................................................................................................................................... 1 Unpackin g .......
.
990-7031C, Rev ision 4 12/99 1 Introduction This Uninterru ptible Power Supply (UPS) is design ed to prevent black outs, brow nouts, s ags and su rges from reaching your com puter and other valuable electronic equipm ent.
990-7031C, Rev ision 4 12/99 2 Inst allation Install ing your UP S req uires five steps: 1. Position the UPS in the desired locatio n. For rack m ount units this m ay in clude installing the rails in to the rack. 2. Conn ect the batteries . All UPSs ship w ith th e batteries dis connected.
990-7031C, Rev ision 4 12/99 3 Determine the Loca tion of the UPS in the Rack UPSs a re hea vy. Select a rack l ocat ion stur dy enough to handle the weight. Mo unt the UP S at o r near the b otto m of the rack. Select a rack location w ith adequate air f low that is free f rom exces sive dust .
990-7031C, Rev ision 4 12/99 4 3 Expand the rails so that it spans from the front rack post to the back rack post. Replace the tw o screw s (rem oved in step 1) that hold the rail sections together. 4 Bac k Attach th e rail to the back rack post using th e same hardw are (10-32 f lat head screw s and con ical w ashers) u sed in step 2.
990-7031C, Rev ision 4 12/99 5 2. Connect the B atteries Note: All UPSs ship with the b atteries discon nected. In add ition, 5000 VA uni ts have the batteries s hipped outside the UPS case so you m ust install the batteries before connecting them .
990-7031C, Rev ision 4 12/99 6 3U Rack Mount Units 1. Reach in to the fing er pull and open th e front cover. Sw ing the cover open as show n. 2. Unhook the si de of the cov er from the chass is and lif t it aw ay to expose th e battery door.
990-7031C, Rev ision 4 12/99 7 3. Connect Powe r and Equipment to the UPS • Connect th e UPS line cord (L6-30 plug ) into the electrical outlet. • Use y our equipm ent’s pow er cords to con nect to the UPS. Caution: DO NOT use a standard serial interface cable to connect to the Com puter In terface Port on the UPS.
990-7031C, Rev ision 4 12/99 8 Charge the ba ttery The UPS charges its battery w henever it is conn ected to utility pow er. The battery will ch arge fully during the f irst four hours of norm al operation. Do not expect full runtim e during this in itial charge period.
990-7031C, Rev ision 4 12/99 9 Operating Instructions Switch On — Switch Of f With the UPS p lugged in, press a nd re lease the large up per on/test button t o supp ly power to the load s. T he loa ds are imm ediately powered w hile th e UPS beeps and perform s a self- test.
990-7031C, Rev ision 4 12/99 10 Load Bar Gra ph 85% 67% 50% 33% 17% The 5-LED display on the lef t of the f ront panel represents the pow er drawn from th e UPS as a percentage of total capacity. For exam ple, if three L EDs are lit, the load is drawing betw een 50% and 67% of the UPS’s capacity.
990-7031C, Rev ision 4 12/99 11 Sto r a g e Storage Conditions Store the UPS covered and upright in a cool, dry location, w ith its battery f ully ch arged.
990-7031C, Rev ision 4 12/99 12 Battery Replacement Proced ure - To wer Unit s 5000 VA 1. Grasp th e top edge of t he bottom front cover and tilt it out. For the 5000 VA u nit: Rem ove the fron t bezel by gras ping the f inger clips on the side of th e bezel and carefu lly loosen ing the f our (4) snaps.
990-7031C, Rev ision 4 12/99 13 Battery Replacement Procedure - 3U Rack Mount Units 1. Reach in to the fing er pull and open th e front cover. Sw ing the cover open as show n. 2. Unhook the si de of the cov er from the chass is and lif t it aw ay to expose th e battery door.
990-7031C, Rev ision 4 12/99 14 Battery Replacement Procedure - 5U Rack Mount Units 5000 VA 1. Reach in to the fing er pull and open th e front cover. Sw ing the cover open as show n. For 5000 VA un its: Rem ove the fron t bezel by gras ping the f inger clips on the side of th e bezel and carefu lly loosen ing the f our (4) snaps.
990-7031C, Rev ision 4 12/99 15 User Configur ation Items Note: Settin g th ese items req uires o ptio nal so ftware o r ha rdware. Fun ction Factory Defau lt User Selectabl e Choi ces Descriptio n Au.
990-7031C, Rev ision 4 12/99 16 Tow er and 5U Rack M ount Models - 3000 & 5000 VA Models Typical On-B attery Run Time Versus Load, in Hours Load 3000 VA Internal Battery 3000 VA w/ 1 Battery Pack 5000 VA Intern al Battery 100 VA 3.80 8.18 7.17 150 VA 3.
990-7031C, Rev ision 4 12/99 17 Sp ecifications 1400 VA 2200 VA 3000 VA 5000 VA Acceptable input v oltag e 0 - 325 VAC Inpu t vo ltage (o n-line operation )* 160 - 253 VAC 208 vo lt outpu t range * 17.
990-7031C, Rev ision 4 12/99 18 T roubleshooti ng Use the chart below to solve m inor UPS installa tion problem s. Contact A PC Tec hnical Support Staf f f or assis tance w ith comple x UPS problem s. See APC Contact Inform atio n , page 19 , for a location near you.
990-7031C, Rev ision 4 12/99 19 Service If the UPS requires service do not return it to the dealer! Follow these steps: 1. Revi ew t he problem s discu ssed in Troublesh ooting , page 18, to eli min ate comm on problem s. 2. Verify that no circuit break ers are tripped.
990-7031C, Rev ision 4 12/99 20 A pp endix A : XL Informatio n When used w ith external battery pack s, the extended ru n (XL) UPS offers longer run tim es than a standard UPS and extra load protection during battery replacem ent.
990-7031C, Rev ision 4 12/99 21 Smart-UPS Battery Protocol Smart- UPS XL models are not designed to k now h ow m any external battery packs are conn ected to them . You mu st program the Sm art-UPS XL w ith the appropriate num ber of external batteries in one of four w ay s.
990-7031C, Rev ision 4 12/99 22 Use the HyperTerminal Pro gram to Chang e the Number of External Battery Packs Hy perTermina l is us ed for Window s 95, Window s 98, and Win dow s NT 4.0 1. EXIT out of t he Pow erChu te plus Serv er. In the case of Window s NT, the UPS s ervice m ust be s topped.
990-7031C, Rev ision 4 12/99 23 A ppendix B: T y pes of Racks and Mounting Har dw are This appendix describes th e hardw are required f or the diff erent ty pes of rack s and desc ribes the ty pe of rack s that m ay be used in y our indu stry . All APC rack moun t units are s hipped ready f or 19-inch w ide EIA /IEC rack cabinets .
990-7031C, Rev ision 4 12/99 24 A ppendix C: T ransporti ng Y our Smart-UPS Follow these g uidelines if y ou need to ship the UPS to another location. T hese guidelines apply w heth er you are transporting the UPS alone, rack m ounted in an equipmen t cabinet, or installed in a sys tem.
Ein wichtiger Punkt beim Kauf des Geräts American Power Conversion 1400XLT (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie American Power Conversion 1400XLT noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für American Power Conversion 1400XLT - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von American Power Conversion 1400XLT reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über American Power Conversion 1400XLT erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon American Power Conversion 1400XLT besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von American Power Conversion 1400XLT verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit American Power Conversion 1400XLT. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei American Power Conversion 1400XLT gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.