Benutzeranleitung / Produktwartung 110 Vac des Produzenten American Power Conversion
Zur Seite of 14
990 - 1853 C, 10 /2005 User Manual English APC Smart - UPS ® SC 420/620 VA 110/120/230 Vac Tower Uninterruptible Power Supply.
.
1 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brow n outs, sags, and surges from reaching your eq uipment. The uninterruptible power supply (UPS) filters small uti l- ity line fluctuations and isolates your equipment from large disturbances by internally disconnecting from the utility line.
2 2: S TART UP Connect the Battery Œ • Connect black wire to battery. (Red wire is already connected.) Note: Small sparks at the poin t of battery conne c tion are normal. Ž • Connect Equipment to the UPS Rear Panels 110/120 V: 230 V: § 230 V models: The top off - white outlet pr o- vides surge protection only.
3 Connect the UPS to the Network (if Applicable) Network Connectors Serial Port Telephone/Network Surge Suppression Ports Use only interface kits a p proved by APC. Use only the supplied cable to connect to the Serial Port. A standard ser ial interface cable is inco m- patible with the UPS.
4 3: O PERATION Front Display Panel 110/120 V 230 V I NDICATOR D ESCRIPTION On L ine The UPS is supplying utility power to the connected equipment. On Ba t tery Th e UPS is supplying battery power to the connected equipment. Ove r load The connected loads are drawing more than the UPS power rating.
5 4: U SER C ONFIGURABLE I TEMS N OTE : S ETTINGS ARE ADJUSTED THROUGH P OWER C HUTE B USINESS E DITION SOFTWARE F UNCTION F ACTORY D E FAULT U SER S E LECTABLE C HOICES D ESCRIPTION Automatic Self - .
6 N OTE : S ETTINGS ARE ADJUSTED THROUGH P OWER C HUTE B USINESS E DITION SOFTWARE F UNCTION F ACTORY D E FAULT U SER S E LECTABLE C HOICES D ESCRIPTION Low Battery War n ing 2 minutes PowerChute Business Edition sof t ware provides automatic, una t- tended shutdown when approx i- mately 2 mi n utes of battery ope r- ated runtime r e- mains.
7 5: S TORAGE AND M AINTENANCE Sto rage Store the UPS covered in a cool, dry location, with the ba t tery fully charged. At - 15 to +30 ° C (+5 to +86 ° F), charge the UPS ba t tery every six months. At +30 to +45 ° C (+86 to +113 ° F), charge the UPS ba t tery every three months.
8 6: T ROUBLESHOOTING , S HIPPING , AND S ERVICE Use the chart below to solve minor UPS installation and operation problems. Refer to www.apc.com with co m plex UPS problems, and f or battery runtime charts. P ROBLEM AND / OR P OSSIBLE C AUSE S OLUTION UPS WILL NOT TURN ON UPS not connected to utility power supply.
9 P ROBLEM AND / OR P OSSIBLE C AUSE S OLUTION THE OVERLOAD LED IS ILLUMINATED AND THE UPS EMITS A SU S TAINED ALARM TONE The UPS is overloaded. The connected equipment is dra w- ing more VA than the UPS can sustain. The connected eq uipment exceeds the specified “maximum load.
10 Shipping and Service Prepare the UPS for shipping: Shutdown and disconnect any equipment attach ed to the UPS. Shut down the UPS, and di s connect the UPS from the utility power outlet. Disconnect the battery. If the UPS requires service do not return it to the dealer.
11 7: R EGULATORY AND W ARRANTY I NFORMATION 110/120 V models This equipment has been tested and found to comply with the limits for a Class A digital device, pu r- suant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial enviro n ment.
12 Limited Warranty American Power Conversio n (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole o p tion, any such defective prod ucts.
Ein wichtiger Punkt beim Kauf des Geräts American Power Conversion 110 Vac (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie American Power Conversion 110 Vac noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für American Power Conversion 110 Vac - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von American Power Conversion 110 Vac reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über American Power Conversion 110 Vac erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon American Power Conversion 110 Vac besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von American Power Conversion 110 Vac verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit American Power Conversion 110 Vac. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei American Power Conversion 110 Vac gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.