GREENHECK P .O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410 PH. 715-359-6171 ® Installation, Operation and Maintenance Instructions for Neutralizer 100% Outdoor Air V entilators W ARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death.
2 T ABLE OF CONTENTS W arrant y ............................................................................................................ Pg. 2 Installation Instructions: N V -45 • Horizontal Discharg e ...........................................
INT AKE DISCHARGE DISCHARGE INT AKE C L C L Equipment Support Footprint C L A A ( fig. 4) Roof mounted arrangement HZ with weatherhood, mounted on three equipment supports.
4 B C L C* Rectangular Curb Footprint C L C L A A/2 A Roof Opening A/2 C* C* *C- Determine equal dimension for these 3 locations Sealant Ductwork Duct Adaptor Supply Ductwork by Others Step 1 Roof Opening Determine the center of the supply duct roof opening.
5 Model TSU Supply Unit Lifting Lugs (4 places) Step 5 Install Supply Unit Use a crane and a spreader bar hooked to the factory lifting lugs (as shown in the diagram) to lift and center the NV unit on the curb and equipment support. Use self-tapping sheet metal screws to fasten unit to the curb and equipment support through holes provided.
6 GREENHECK ® Before beginning this installation: Make sure that there is room to access the unit from all sides. Make sure inlet of unit is located well away from any exhaust fans. Installation Instructions for: SLAB, RAIL, AND CURB MOUNTING NV -90 and NV -120 w/Horizontal Dischar ge Lifting Lugs (4) Spreader Bar NV Unit Intake 1a.
7 Rails located 6-12" in from sides of unit. Rails extend 6" from end of filter section Rails extends 6" from discharge end of unit Lifting Lugs (4) Spreader Bar 2.
8 Straight A B C D Duct Length NV-90 16 1 / 4 24 34 1/ 2 22 3 / 8 81 NV-120 16 1 / 4 25 1 / 2 34 23 1 / 4 96 5. Attach Ductwork to Unit Discha r ge Chart and drawing below show opening size (ID) and location for discharge collar. Also included is the recommended straight duct lengths for optimal performance.
9 Installation Instructions for: CURB MOUNTING* NV -90 and NV -120 *For installations using Greenheck's optional roof curb. 1. Assemble Roof Curb Curbs are shipped knockdown and require assembly by others. Assembly instructions are also included with curb.
10 5. Install Unit. Use a crane and spreader bar to prevent damage to unit. Lifting lugs are provided as shown in illustration. It is highly recommended that all accessory items be lifted separately and attached after the unit is in place. Electrical and pipe connections can be made at this time.
11 Weatherhood fastener locations typical for entire section. T op fasteners are accessed fr om outside, side and bottom fasteners are accessed from inside.
12 Sequence for wiring NV unit: For units without contr ol centers: The motor nameplate is to be used for determining the voltage and amperage required by the unit. For units with control centers: 1. The unit’s nameplate states the voltage and total amperage required.
SYSTEM ST AR TUP For proper unit function and safety, follow everything in this startup procedure in the order presented. This is to be done after the electrical connections are complete. • Voltage meter • Incline manometer or equivalent Special T ools Requir ed • Tachometer • Thermometer • Amperage meter 1.
14 Steam Coils Application Recommendations: Satisfactory operation and service life are best ensured when coils are installed with proper piping, trap, and support arrangement. The following notes and figure 1 ( page 15 ) are recommended for the coil unit installation and operation.
15 Steam Main Return Main Gate V alve Control V alve, Modulating T wo-Position Check V alve-V acuum Breaker Float and Thermostat T rap Strainer Dir ect Expansion Coils Application Recommendations: 1. Piping should be in accordance with accepted industry standards.
16 Coil Maintenance Filters: Filters upstream of the coil should be checked regularly for dirtiness and clogging. If the filters are dirty, they should be cleaned or replaced. It is important that the coils stay clean to maintain maximum heat transfer capability.
17 TROUBLE SHOOTING Blower Unit Symptom Possible Cause Corrective Action Blower fails Blown fuse or open circuit breaker Replace fuse or reset circuit breaker and to operate check amps Broken fan belt.
18 General Dimensions and W eights PLAN VIEW Motor Control Center Optional Filter/Heating Section Optional Heating Coil Cooling Coil 110 1 / 2 ELEV A TION VIEW 88 Optional Curb or Support Blower/Motor.
19 Maintenance Greenheck recommends these procedures to insure trouble free operation of this unit. Most unit failures can be attributed to poor setup or poor maintenance. A record of maintenance performed on this unit should be kept. This information will provide essential information if problems are encountered.
20 Job Information Job Name: ________________________________________ Address: _________________________________________ City: ________________ State: ________ Zip: __________ Phone: _________________.
Ein wichtiger Punkt beim Kauf des Geräts Greenheck Outdoor Air Ventilator (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Greenheck Outdoor Air Ventilator noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Greenheck Outdoor Air Ventilator - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Greenheck Outdoor Air Ventilator reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Greenheck Outdoor Air Ventilator erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Greenheck Outdoor Air Ventilator besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Greenheck Outdoor Air Ventilator verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Greenheck Outdoor Air Ventilator. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Greenheck Outdoor Air Ventilator gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.