Only qualified personnel should install this unit. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Impr oper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards.
2 Model LFC Low-Profile Fan Coil ® The unit should be stored at least 3½ in. (89 mm) of f the floor on wooden blocks covered with moistur e proof paper or polyethylene sheathing. Aisles between parts and along all walls should be provided to permit air circulation and space for inspection.
3 Model LFC Low-Profile Fan Coil ® T able of Contents Installation U n i t L a y o u t .............................. . 3 Lifting / Hanging Instructions ................ 3 Dimensions / Weights ...................... 4 Filter Sizes / Quantity . . . . .
4 Model LFC Low-Profile Fan Coil ® Unit Dimensions Unit Size I J K Width Inlet Outlet w/o Filter w/ 2 in. Filter w/ 4 in. Filter Height Width Height Width 15 40 42 44 8.0 11.0 38 9.0 36 4.0 6.75 20 40 42 44 11.0 14.0 38 12.0 36 6.5 6.75 25 40 42 44 13.
5 Model LFC Low-Profile Fan Coil ® Coil Dimensions NOTE Fluid enters the coil from the bottom connection (Inlet) and exits from the top (Outlet). Hot W ater • 1 and 2 Row Unit Size A B 15 7.63 0.75 20 10.13 0.75 25 12.63 0.875 30 15.13 0.875 45 15.
6 Model LFC Low-Profile Fan Coil ® Unit Size A B 4 row 6 row 8 row CDCDCD 30 12.00 7.00 0.625 0.625 0.625 0.875 0.625 0.875 45 12.00 7.00 0.625 0.625 0.625 0.875 0.625 0.875 50 13.50 7.75 0.625 0.625 0.625 0.875 0.625 1.125 65 17.00 9.50 0.875 0.875 0.
7 Model LFC Low-Profile Fan Coil ® System Start-Up For proper unit function and safety , follow everything in this start-up procedur e in the order pr esented. This is to be done after the electrical connections are complete. PRE-ST ART CHECK LIST 1.
8 Model LFC Low-Profile Fan Coil ® Symptom Possible Cause Corrective Action Blower fails to operate Blown fuse or open circuit br eaker Replace fuse or reset cir cuit breaker and check amps Broken fa.
9 Model LFC Low-Profile Fan Coil ® Hot W ater , Chilled W ater Coils 1. Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. Water pipes are copper with sweat connections. USE WET TOWEL TO AVOID BURNING COIL CONNECTION GROMMETS.
10 Model LFC Low-Profile Fan Coil ® Steam Coils, General - continued 3. Standard steam coils are pitched in the casings when installed for horizontal airflow. The casing must be level after the unit is installed for proper condensate drainage. If condensate is not removed, the coil will suffer from water hammering and will have a shortened life.
11 Model LFC Low-Profile Fan Coil ® Y early Bearings — Most bearings are permanently lubricated and requir e no further lubrication under normal use. Normal use being considered -20ºF to 120ºF and in a relatively clean envir onment. Some bearings are r elubricatable and will need to be regr eased depending on fan use.
12 Model LFC Low-Profile Fan Coil ® Coil Maintenance Start-Up Documentation CAUTION Fin edges are sharp. Coils must be clean to obtain maximum performance.
13 Model LFC Low-Profile Fan Coil ® Maintenance Log Date __________________ Time _____________ AM/PM Notes:___________________________________________ ________________________________________________.
14 Model LFC Low-Profile Fan Coil ® Maintenance Log Date __________________ Time _____________ AM/PM Notes:___________________________________________ ________________________________________________.
15 Model LFC Low-Profile Fan Coil ® Maintenance Log Date __________________ Time _____________ AM/PM Notes:___________________________________________ ________________________________________________.
16 464496 • LFC, Rev . 1, August 2004 Copyright 2004 © Greenheck Fan Corporation Greenheck warrants this equipment to be fr ee from defects in material and workmanship for a period of one year fr om the shipment date.
Ein wichtiger Punkt beim Kauf des Geräts Greenheck Fan LFC (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Greenheck Fan LFC noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Greenheck Fan LFC - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Greenheck Fan LFC reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Greenheck Fan LFC erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Greenheck Fan LFC besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Greenheck Fan LFC verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Greenheck Fan LFC. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Greenheck Fan LFC gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.