Only qualified personnel should install this unit. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Impr oper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards.
2 Model VFCD/VFCB V ertical Fan Coil ® The unit should be stored at least 3½ in. (89 mm) of f the floor on wooden blocks covered with moistur e proof paper or polyethylene sheathing. Aisles between parts and along all walls should be provided to permit air circulation and space for inspection.
3 Model VFCD/VFCB V ertical Fan Coil ® T able of Contents Installation U n i t L a y o u t .............................. . 3 Mounting Instructions ...................... 3 Unit Dimensions / Weights .................. 4 Inlet and Outlet Duct Details .
4 Model VFCD/VFCB V ertical Fan Coil ® Chilled Water Coil Conditions Fin Height: 22.5 Fin Width: Width-7 Fins Per Inch: 10 Fin Surface: B Circuiting: Half Ent.
5 Model VFCD/VFCB V ertical Fan Coil ® Coil Dimensions NOTE Fluid enters the coil from the bottom connection (Inlet) and exits from the top (Outlet). Hot W ater • 1 and 2 Row Unit Size A B C D 600 20.00 22.50 22.63 0.875 800 20.00 22.50 22.63 0.875 1300 24.
6 Model VFCD/VFCB V ertical Fan Coil ® NOTE With airflow from left to right, the fluid enters the coil from the bottom connection (Inlet) and exits from the top (Outlet). The other two coil connections should be capped off (Cap). Chilled W ater • 4, 6 or 8 Row C B A E D F 1.
7 Model VFCD/VFCB V ertical Fan Coil ® Filter Sizes and Quantity Model V ertical Filter Size (inches) Quantity Face Area (ft 2 ) VFCD/VFCD-600 20 x 24 1 2.7 VFCD/VDFCB-800 20 x 24 1 2.7 VFCD-VFCB-1300 20 x 24 1 2.7 VFCD/VFCB-1600 24 x 24 1 3.6 VFCD/VFCB-2000 16 x 25 2 4.
8 Model VFCD/VFCB V ertical Fan Coil ® 4. Air Volume Check and Measurement Along with the building balance, the unit’ s air volume (cfm) should be measured and compar ed with its rated air volume. This unit is flexible for varying air volume, but the actual air volume should be known for making final adjustments.
9 Model VFCD/VFCB V ertical Fan Coil ® Speed Contr ols Speed controls may be used on Model VFCD fans for manual adjustment of the fan’ s performance (for final system balancing) or to control the fan’ s output in confined spaces, such as conference or meeting rooms.
10 Model VFCD/VFCB V ertical Fan Coil ® Symptom Possible Cause Corrective Action Blower fails to operate Blown fuse or open circuit br eaker Replace fuse or reset cir cuit breaker and check amps Brok.
11 Model VFCD/VFCB V ertical Fan Coil ® Hot W ater , Chilled W ater and DX Coils 1. Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. Water pipes are copper with sweat connections.
12 Model VFCD/VFCB V ertical Fan Coil ® 2P = minimum 2P = minimum Drain Pan / Drain T rap Drain Pan / Drain T rap Drain lines and traps should be run full size from the drain pan connection. Drain pans should have drain lines and traps to permit the condensate from the coils to drain freely .
13 Model VFCD/VFCB V ertical Fan Coil ® Y early Bearings — Most bearings are permanently lubricated and requir e no further lubrication under normal use. Normal use being considered -20ºF to 120ºF and in a relatively clean envir onment. Some bearings are r e-lubricatable and will need to be re- greased depending on fan use.
14 Model VFCD/VFCB V ertical Fan Coil ® Coil Maintenance Start-Up Documentation CAUTION Fin edges are sharp. Coils must be clean to obtain maximum performance. Check once a year under normal operating conditions and, if dirty , brush or vacuum clean.
15 Model VFCD/VFCB V ertical Fan Coil ® Maintenance Log Date __________________ Time _____________ AM/PM Notes:___________________________________________ ____________________________________________.
Greenheck warrants this equipment to be fr ee from defects in material and workmanship for a period of one year fr om the purchase date. Any units or parts which pr ove defective during the warranty period will be replaced at our option when returned to our factory , transportation pr epaid.
Ein wichtiger Punkt beim Kauf des Geräts Greenheck Fan 464696 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Greenheck Fan 464696 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Greenheck Fan 464696 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Greenheck Fan 464696 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Greenheck Fan 464696 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Greenheck Fan 464696 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Greenheck Fan 464696 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Greenheck Fan 464696. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Greenheck Fan 464696 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.