Benutzeranleitung / Produktwartung GSX130361E des Produzenten Goodman Mfg
Zur Seite of 44
SS-GSX13 www .goodmanmfg.com 2/14 Supersedes 11/13 GSX1 3 S plit S yStem A ir C onditioner 13 Seer / 1½ t o 5 t onS C oolinG C Ap ACity : 1 8,000 - 60,000 BtU/ h Standard Featur es • R-410Ach.
P roduct S Pecifica tionS 2 www .goodmanmfg.com SS-GSX13 n omenClA tUre Brand Engineering * G Goodman ® Brand or Minor Revision Amana ® Distinctions ® Brand Engineering * Major Revision Product Cat.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 3 S peCifiCA tionS GSX13 0181E* GSX13 0241D* GSX13 0301B* GSX13 0361C* GSX13 0361E* GSX13 0421B* GSX13 0481B* GSX13 0601B* GSX13 0611A* Cap aciti.
P roduct S Pecifica tionS 4 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 301 81e* / CApf1 824B6dB Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 525 MBh 15.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 5 e Xp Anded C oolinG d A tA — GSX1 301 81e* / CApf1 824B6dB ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 525 MBh 16.
P roduct S Pecifica tionS 6 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 302 4 1d* / CA*f1 82 4*6d* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 700 MBh 20.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 7 e Xp Anded C oolinG d A tA — GSX1 302 4 1d* / CA*f1 82 4*6d* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 700 MBh 20.
P roduct S Pecifica tionS 8 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30 301B* / CA *f30 30*6d* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 945 MBh 26.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 9 e Xp Anded C oolinG d A tA — GSX1 30 301B* / CA *f30 30*6d* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 945 MBh 27.
P roduct S Pecifica tionS 10 www .goodmanmfg.com SS-GSX13 Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1350 MBh 32.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 11 Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1350 MBh 33.
P roduct S Pecifica tionS 12 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30 36 1e* / CA *f3 6 3 6*6d* Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1350 MBh 32.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 13 e Xp Anded C oolinG d A tA — GSX1 30 36 1e* / CA *f3 6 3 6*6d* ( Cont .) .
P roduct S Pecifica tionS 14 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30421B* / CA *f3 642*6B* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1225 MBh 36.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 15 e Xp Anded C oolinG d A tA — GSX1 30421B* / CA *f3 642*6B* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1225 MBh 37.
P roduct S Pecifica tionS 16 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30481B* / CA *f4860*6B* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1400 MBh 40.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 17 e Xp Anded C oolinG d A tA — GSX1 30481B* / CA *f4860*6B* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1400 MBh 41.
P roduct S Pecifica tionS 18 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30601B* / CA *f496 1*6A * Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1500 MBh 50.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 19 e Xp Anded C oolinG d A tA — GSX1 30601B* / CA *f496 1*6A* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1500 MBh 51.
P roduct S Pecifica tionS 20 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 306 1 1*/CA *f496 1*6d*+eep Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1500 MBh 53.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 21 e Xp Anded C oolinG d A tA — GSX1 306 1 1*/CA *f496 1*6d*+eep ( Cont .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1500 MBh 55.
P roduct S Pecifica tionS 22 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0181E* ACNF18XX16D* 16,800 12,800 13.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 23 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0181E* CAPT3131*4A* A*EH800603B*A* 18,000 13,700 14.
P roduct S Pecifica tionS 24 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0241D* CA*F1824*6D* A*VC950453BXB* 23,000 16,900 14.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 25 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0301B* ACNF30XX16D* 27,600 20,800 13.
P roduct S Pecifica tionS 26 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0301B* CA*F3131*6D*+MBVC1200**-1A* 28,400 21,400 14.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 27 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0301B* CAPT3743*4A*+MBVC1600**-1A* 28,200 21,200 14.
P roduct S Pecifica tionS 28 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0361E* CA*F3642*6D* G*VC950905CXB* 34,000 26,400 14.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 29 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0361E* CAPT3743*4A* A*VM961005DXB* 34,000 26,400 13.
P roduct S Pecifica tionS 30 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0421B* CA*F3642*6D*+EEP 40,000 30,600 13.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 31 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0421B* CHPF3642D6C* G*VC950905CXB* 40,000 30,600 13.
P roduct S Pecifica tionS 32 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0481B* CA*F4860*6D*+TXV A*VM960604CXB* 46,000 35,200 14.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 33 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0481B* CHPF4860D6D*+TXV A*EH801005C*A* 46,000 35,200 13.
P roduct S Pecifica tionS 34 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0601B* CAPT4961*4A* A*VC950915D XB* 55,000 39,000 13.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 35 Ahri r A tinGS ( Cont .) Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* ARPT48D14A* 54,500 37,400 13.00 11.00 1,500 5586528 ARPT60D14A* 55,000 37,600 13.
P roduct S Pecifica tionS 36 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* CA*F4961*6D*+TXV G*VC80805C*B* 56,500 38,500 14.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 37 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* CAPT4961*4A* G*VC950905CXB* 56,500 38,500 13.
P roduct S Pecifica tionS 38 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* CSCF4860N6D*+TXV GME951005DXA* 55,000 37,600 13.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 39 d imenSionS H W D Model Dimensions W” D” H” GSX130181E* 23 23 25¾ GSX130241D* 23 23 25¾ GSX130301B* 26 26 27½ GSX130361C* 29 29 28¾ .
P roduct S Pecifica tionS 40 www .goodmanmfg.com SS-GSX13 W irinG d iAGrAm — GSX1 3 01 81e USE N.E.C. CLASS 2 WIRE COMP ALTERNA TE DOUBLE POLE CONTACTO R ONL Y IO T1 M A I N R A U X 5 S SR SA 2 1 RC.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 41 W irinG d iAGrAm — GSX1 3 0(3 0-60)1B/C/e* ref er to the wiring diagram or the unit for the most up-t o-date wiring.
P roduct S Pecifica tionS 42 www .goodmanmfg.com SS-GSX13 ref er to the wiring diagram or the unit for the most up-t o-date wiring.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 43 W irinG d iAGrAm — GSX1 3 06 1 1* ref er to the wiring diagram or the unit for the most up-t o-date wiring.
P roduct S Pecifica tionS 44 www .goodmanmfg.com SS-GSX13 Goodman Manufacturing Company , L.P ., reserves the right to discontinue, or change at any time, specica tions or designs without notice or without incurring obligations. © 2014 • Goodman Manufacturing Company , L.
Ein wichtiger Punkt beim Kauf des Geräts Goodman Mfg GSX130361E (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Goodman Mfg GSX130361E noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Goodman Mfg GSX130361E - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Goodman Mfg GSX130361E reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Goodman Mfg GSX130361E erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Goodman Mfg GSX130361E besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Goodman Mfg GSX130361E verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Goodman Mfg GSX130361E. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Goodman Mfg GSX130361E gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.