• Refer to Service Manual RS6100004 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. Models listed on page 3. GSH 14 SEER Remote Heat Pump RT6213004 April 2006 This manual is to be used by qualified HV AC technicians only .
PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. MULTIPLE POWER SOURCES MAY BE PRESENT.
PRODUCT IDENTIFICA TION 3 WARNING WARNING DO NOT CONNECT OR USE ANY DEVICE THAT IS NOT DESIGN CERTI- FIED BY GOODMAN FOR USE WITH THIS UNIT. SERIOUS PROPERTY DAMAGE, PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON-APPROVED DEVICES.
PRODUCT DESIGN 4 GSH14 SEER split system heat pump models are available in 1 1/2 through 5 ton sizes. They are designed for 208/230 volt single phase applications. Air is drawn through the outdoor coil by a propeller fan, and is discharged vertically out the top of the unit.
5 HEA T PUMP SPECIFICA TIONS GSH14[018-060]1A* (1) Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes . (2) May use fuses or HACR type Circuit Breakers of the same size as noted.
6 COOLING PERFORMANCE DA T A GSH140181A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OP ERA TI ON M ODEL: G SH140181A * / C A*F3131B6A *+TXV / M BR800**-1 Design Subcooling, 9 ±3 °F @ the liquid servic e.
7 COOLING PERFORMANCE DA T A GSH140181A* EXPA NDED PERFORMA NCE DA TA C OOL IN G OPER AT ION M ODEL: GSH 140181A * / CA* F 3131B6A *+T XV / M BR800**-1 Design Subcooling, 9 ±3 °F @ the liquid servic.
8 COOLING PERFORMANCE DA T A GSH140241A* EXPA NDED PERFO RMA NCE DA TA COOLI NG OPER A TION MO DEL: GSH140 241A * / CA *F3636B6A *+TXV / MBR800** 1 Design Subc ooling 9 ±3 °F @ the li qui d servic e.
9 COOLING PERFORMANCE DA T A GSH140241A* EXPA NDED PERFO RMA NCE DATA COOLING OPER A TION MO DEL: GSH140 241A * / CA *F3636B 6A *+TXV / MBR800 **1 Desi gn Subc ooling 9 ±3 °F @ the liqui d se rvice .
10 COOLING PERFORMANCE DA T A GSH140301A* EXPA NDED PERFORMA NCE DA TA CO OLING O PER AT ION MODEL: GSH140301A * / CA *F3636B6A * +TXV / M BR1200**-1 Design Subcooling 9 ±3 °F @ the liquid service v.
11 COOLING PERFORMANCE DA T A GSH140301A* EXPA NDED PERFORMA NCE DA TA CO OLING O PER AT ION MODEL: GSH140301A * / CA *F3636B6A * +TXV / M BR1200**-1 Design Subcooling 9 ±3 °F @ the liquid service v.
12 COOLING PERFORMANCE DA T A GSH140361A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OPER A TION MO DEL: GSH140361A * / CA* F4860C6A * +TXV / MB R1600**-1 Design Subcooling 9 ± 3°F @ the liquid service .
13 COOLING PERFORMANCE DA T A GSH140361A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OPER A TION MO DEL: GSH140361A * / CA* F4860C6A * +TXV / MB R1600**-1 Design Subcooling 9 ± 3°F @ the liquid service .
14 COOLING PERFORMANCE DA T A GSH140421A* EXPA NDED PERFORMA NCE DATA COOLING OPERA TION M ODEL: GSH140421A* / CA *F4860D6A*+TXV / M BR2000**-1 Design Subcooling, 9 ± 3 °F @ the liquid service valv .
15 COOLING PERFORMANCE DA T A GSH140421A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140421A * / CA*F4860D6A *+TXV / M BR2000**-1 D esign Subcoolin g, 9 ±3 °F @ th e liquid serv ice v.
16 COOLING PERFORMANCE DA T A GSH140481A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140481A * / CA*F4860D6A *+TXV / MBR2000**-1 Design Subcooling 9 ±3 °F @ th e liquid servi ce valve.
17 COOLING PERFORMANCE DA T A GSH140481A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140481A * / CA*F4860D6A *+TXV / M BR2000**-1 Design Su bcooling 9 ±3 °F @ th e liquid serv ice val.
18 COOLING PERFORMANCE DA T A GSH140601A* EXPA NDED PERFORMA NCE DATA COOLING OPER A T ION M ODEL: GSH140601A* / CA *F4860D6A* + T XV / M BR2000**-1 Design Subco oling 9 ±3 °F @ th e liquid service .
19 COOLING PERFORMANCE DA T A GSH140601A* EXPA NDED PERFORMA NCE DATA COOLING OPER A T ION M ODEL: GSH140601A* / CA *F4860D6A* + T XV / M BR2000**-1 Design Subco oling 9 ±3 °F @ th e liquid service .
20 PERFORMANCE DA T A Outdo or Temp. ° F. Total Btuh Sensib le Btuh Latent Btuh Total Watts 75° 18,900 13,282 5,618 1,367 80° 18,675 13,290 5,385 1,410 85° 18,450 13,295 5,155 1,452 90° 18,225 13.
21 EXPA NDED PERFO RMANC E DA TA MO DEL: G SH140181A* / CA*F3131B6A*+TXV / M BR800** -1 HEA TING OPERA TION Outdoor A mbient Temperature 65 60 55 50 47 45 40 35 30 25 20 17 1 5 10 5 0 -5 -10 MBh 22.6 21.4 20.2 18.8 18.0 17.4 16.2 14.9 13.6 12.5 11.5 10.
22 SPLIT SYSTEM HEA TING PERFORMANCE EXPA NDED PE RFO RMA NCE DA TA MODEL: GS H140421A * / CA *F4860D6A *+TXV / MB R2000**-1 HE AT I N G OP E R AT I O N Outdoor A mbient T emperat ure 65 60 55 50 47 45 40 35 30 2 5 20 1 7 15 10 5 - 5 -10 MBh 49.8 47.1 44.
23 HEA TING SPECIFICA TIONS capacity btuh c.o.p. 4.8 9.6 14.4 19.2 65 22.63 4.23 39.008 55.391 71.7732 88. 156 60 21.42 4.09 37.802 54.185 70.5672 86. 950 55 20.16 3.93 36.542 52.925 69.3072 85. 690 50 18.85 3.75 35.228 51.611 67.9932 84. 376 45 17.44 3.
24 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
WIRING DIAGRAMS 25 TO AVOID POSSI BLE ELECTRI CAL SHOCK, PERSONAL I NJURY, OR DEATH, DI SCONNECT THE POWER BEFORE SERVI C ING. WARNING ! GSH140[18-60]1A* US E N .E .C. CL AS S 2 WI R E NOTES : 1) TO INDOOR U NIT LOW VOL T AGE TER MINAL BLO CK & INDO OR TH ER M O ST A T .
Ein wichtiger Punkt beim Kauf des Geräts Goodman Mfg GSC140481A (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Goodman Mfg GSC140481A noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Goodman Mfg GSC140481A - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Goodman Mfg GSC140481A reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Goodman Mfg GSC140481A erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Goodman Mfg GSC140481A besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Goodman Mfg GSC140481A verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Goodman Mfg GSC140481A. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Goodman Mfg GSC140481A gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.