Install ation and Ope rati on Instructions Installation and Ope ration Instru ctions Mark II Mark II XG XG Dies e l Engine Fire P ump C ontroll e rs Diese l Engine Fire Pump C ontrolle rs NS1100-50 E .
T abl e of Contents INTR ODUC TION .................................................................................................................. ......... 1 MOUNTING C ONTR OLLER ...................................................................
Pressure (con tinued) Ove rpressure Alarm ................................................................................................. 10 R ecor ding - Delta ........................................................................................
MAIN MENU - F AC T OR Y (continued) Con fi guration - Model Pressure Se nsor .................................................................................................... .... 15 Auto st ar t NC ................................................
These instructions are intended t o as sist in the understanding of the installation and ope ration of the F T A1100. Re ad through these instruc tions thoroughly prior to c onnec ting the controlle r .
5. U sing eithe r the dimension print or b y measuring the distanc e bet wee n the cen ter lines o f the 2 lowe r bracket slo ts, transcribe this dimension on t o the wall. Note : The bottom edge o f the en- closure should be a minimum o f 12” (305 mm.
2. V erify that the c ontrolle r inform ation is wh at is required on the project: • Firetrol catalog numbe r • Engine voltage and polarity of grounding • Incoming line v olt age and freque nc y • Maximum syste m pressure 3.
6. Connect AC pow er t o “L1” and “L2” (CB1) —120 V olt, 60 Hz or as called for on c ontroller d ata plat e. 7. Connec t remo te normally open ST ART push-button wires t o terminals “13” and “14” (if u sed). 8. If deluge valv e is used, remo ve jumper from t ermin als “16” and “17”.
AC POWER A V AILABLE ALARM MAIN SWITCH IN AUTO MAIN SWITCH IN MANUAL SYSTEM PRESSURE LOW ENGINE RUNNING ENGINE F AIL TO ST ART ENGINE TEMPERA TURE HIGH ENGINE OIL PRESSURE LOW ENGINE OVERSPEED ENGINE .
Mark II XG Us er Me nu Stru c ture Main Menu Setting s System Se tup Da te & Time Timers Pressure Engine & Cranking Alarm Limits Fe at. Settings Displa y Language/Units Passwords Time Date Daylight Sa ving On Dela y T ime Min.
Programming No tes The Firetrol Mark II XG is multi-leve l passwor d protected. User programm able func tions are protected b y a Lev el 1 pas s wor d. LE VEL 1 P A SSW ORD 2 - 1 - 1 - 2 Note: Many me nu settings f eature an “e nable/disable” option.
Mark II XG Us er Me nu Settings SET TINGS SYSTEM SETUP DIS PLA Y BRIGHTNESS 1 Use and arro ws to set de sired displa y brightness. Press to c on fi rm. Syst em Setup - Dis play SET TINGS SYSTEM SETUP DISPLA Y CONTRAST 1 Use and arro ws to set de sired displa y contrast.
SET TINGS D A TE & TIME D A YLIGHT SA VING 1 Use arrows t o enable or disable autom atic D aylight Saving time adju stments. Press t o con fi rm. (DST +) “Begin ” - Hour Use arrows t o set number of minute s to adju st for at the beginning or en d of Da ylight Saving time.
Use arrows t o enable or disable this setting. Pre ss to c o n fi rm. SET TINGS PRESS URE OVERP RESSURE ALARM 1 Use arro ws to en able or disable the overpre ssure alarm f eature . Press to con fi rm. Limit Use arro ws to set the pre ssure limit for the o verpressure al arm.
Use arrows t o set maximum voltage point f or Battery T rouble alarm. Press t o con fi rm. SET TINGS ALARM LIMITS 1 MAX Use arro ws to set minimum v olt age point f or AC V oltage Low alarm. Pres s to con fi rm. SET TINGS ALARM LIMITS 1 V MIN Use arro ws to set m aximum voltage point for A C Voltage High al arm.
SET TINGS FEA TURE SET TINGS MANUAL TEST 1 DURA TION Use arro ws to set the minimum run time (duration) whe n manual test pu sh -button is u sed (10 - 99 min.). Press t o con fi rm. SET TINGS FEA TURE SET TINGS PUMP RUN ALARM 1 AUD IBL E Use arro ws to en able or disable the audible alarm for Pump R un.
13 SET TINGS FEA TURE SET TINGS RELIEF V AL VE OPEN 1 AUD IBL E Use arro ws to en able or disable the audible alarm for R elief V alve Open. Pre ss to con fi rm. 1 COMMON ALARM Use arro ws to en able or disable the common alarm output (ALR re lay) f or Relie f Valv e Open.
SET TINGS OPTION SET TING S NOTE: The list of avail able options and the settings a ssociat ed with them will vary with each con troller . Listed below are the most c ommon use r de fi ned settings th at may appe a r . 1 AUD IBL E Use arro ws to en able or disable the audible alarm for selected op tion.
FA C TO RY CONFIG URA TION MODEL 3 SERIAL NUMBER Use arro ws to en ter the con troller serial numbe r . Press to c on fi rm. NO TE: This is a fac tory set paramete r and under norm al circumstance s would never be c hanged. 3 MODEL Use arrows t o selec t required mode l number .
LAMP TEST 1 Use arro ws to en able the lamp test. Press t o begin test. All System S tatus LED’s should illuminat e . Use arro ws to disable the lamp t est. Press t o end test. Syste m Status LED’s should turn off and return to norm al indications.
When installing the batt ery charge r as a re place men t par t, it is nece ssar y to verify the proper ch arge r setting s and adjust a s necessar y . 1. Incoming A C voltage 115 or 230 volts. 2. Batte r y voltage - 12 or 24 volts DC. 3. Batte r y t y pe - Le ad Acid / Ni-Cad 9 or 18 Cell / Ni-Cad 10 or 20 Cell.
Ein wichtiger Punkt beim Kauf des Geräts Emerson FTA1100 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Emerson FTA1100 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Emerson FTA1100 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Emerson FTA1100 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Emerson FTA1100 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Emerson FTA1100 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Emerson FTA1100 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Emerson FTA1100. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Emerson FTA1100 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.