Benutzeranleitung / Produktwartung 5600 des Produzenten Eclipse Combustion
Zur Seite of 42
Modulation Model Purge Model No Purge Model Instruction Manual 818 2/02 V er iFlame Single Bur ner Monitor ing System Model 5600 V ersion 1.21.
2 Eclipse V e ri-Flame Instruction Manual 818 -2/02 Cop y r igh t 1 997 b y Ec li ps e C ombustion, In c . All rights r es er v ed w orl dwide. Thi s p u b l i c a t i o n i s p r o t e c t e d b y f .
3 Eclipse V er i-Flame Instruction Manual 818 - 2/02 A UDIENCE S COPE D OCUMENT C ONVENTIONS This man ual has been written for the people who select and install the product and the technicians who w ork on it. They ar e expected to ha v e previous expe- rience with this kind of equipment.
4 Eclipse V eri-Flame Instruction Manual 818 -2/02 H OW TO GET HELP If you need help , you can contact y our local Eclipse Combustion sales office. Y ou can also contact Eclipse Combustion, Inc . at: 1665 Elmwood Road Rockford, Illinois 61103 USA Phone: 815-877-3031 Fax: 815-877-3336 E-mail: eclipse @ eclipsenet.
5 Eclipse V er i-Flame Instruction Manual 818 - 2/02 About this manual ..................................................................................... 3 T ab le of contents ........................................................................
6 Eclipse V eri-Flame Instruction Manual 818 -2/02 Optional Featur es ................................................................................................. 16 Pilot T est Mode Sequence ......................................................
7 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Maintenance & T r oub leshooting .................................................... 28 Introdu ction ...........................................................................................
8 Eclipse V eri-Flame Instruction Manual 818 -2/02 The Eclipse Combustion V eri-Flame Single Burner Monitoring System contr ols the start-up sequence and monitors the flame of single gas, oil, or combination gas/oil burners. There ar e thr ee different models to the V eri-Flame line: the no purge, the purge and the modulation models.
9 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Specifications I NTRODUCTION Specifications This section giv es a detailed ov er view of V eri-Flame specifications and dimensions. 2 (continued onto next page ) P ARAMETER D ESCRIPTION Supply • Series 5602 & 5605: 1 20 V A C ( + 10%, - 15%), 50/60 Hz standard.
10 Eclipse V eri-Flame Instruction Manual 818 -2/02 Specifications (continued) P ARAMETER D ESCRIPTION Approvals • No Purge & Purge Models: Series 5602: UL listed, CSA cer tified, FM approv ed and IRI acceptable. Series 5603: No appr ovals. Series 5605: UL listed, FM appro v ed and IRI acceptable .
11 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Dimensions (continued) * * 171mm (6-3/4") Veri-Flame/Modulating Model with Base Model Number 5602-40 Remote Display Model Number 5602-DB Cont.
12 Eclipse V eri-Flame Instruction Manual 818 -2/02 I NTRODUCTION DIP Switch Location DIP Switch Selection This section details the location, selection and description of the V eri-Flame DIP switches, which allow for sequence and timing functions as well as sys- tem configuration.
13 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Close-up of DIP switches on back side of all V eri-Flame models. Figure 3. 1 DIP Switch Location Figure 3.
14 Eclipse V eri-Flame Instruction Manual 818 -2/02 I NTRODUCTION Function Summar y S T AND ARD FEA TURES 4 This section describes the featur es of the V eri-Flame. It is br ok en into thr ee categories: Standard f eatur es, Optional features and the LED Indicator Lights on the front co ver .
15 Eclipse V er i-Flame Instruction Manual 818 - 2/02 F or modulation models: This f eature is enabled when the jumper on the base is cut. The system checks that the high fire position switch and the main valve closed switch ar e both made at the end of the high fire purge.
16 Eclipse V eri-Flame Instruction Manual 818 -2/02 F or modulation models: the modulation f eature incorporates a high fir e purge time and a low fir e purge time into the purge sequence.
17 Eclipse V er i-Flame Instruction Manual 818 - 2/02 S T A TUS L IGHTS & P USH - BUTT ON All of the status lights and the TEST/RESET push-button ar e located on the fro nt cover of the V eri-Flame. This section describes their r espectiv e functions.
18 Eclipse V eri-Flame Instruction Manual 818 -2/02 System Installation In this section, the necessar y pr ocedures are detailed to integrate a V eri-Flame into a burner system; Figur es 5.1 and 5.2 illustrate the various terminal strips mentioned. Note: Shut off the power supply befor e the V eri-Flame is removed or replaced from the base.
19 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Ignition Wiring Lo w Fire Input Main V alve Closed Switch High Purge Input Remote Reset Route ignition wiring a sufficient distance fr om all sensors and other low v olt- age wiring to a void electrical interference, which ma y cause erratic operation of the V eri-Flame system.
20 Eclipse V eri-Flame Instruction Manual 818 -2/02 Figure 5. 1 No Purg e and Purg e Wiring Diagrams No Purg e Models Purg e Models Figure 5. 2 Modulation Wiring Diagram On/Off 15 A Fuse 7 S1 S2 V 1 2.
21 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Notes f or Figur es 5.1, 5.2 & 5.3: 1. Ground, shielding and conduit must not be connected to terminal S2. 2. Control circuit wir es must meet 90°C (194°F) specif ication minimum and must be No.
22 Eclipse V eri-Flame Instruction Manual 818 -2/02 Figure 5. 4 Purge and No Purge Bases Model Number 5602-10 Model Number 5602-10-1 5 6 S2 S1 7 8 3 4 V 2 1 A 5 6S 2 S 1 7 8 A 1 2 V 4 3 P3 P2 P1 Gnd G.
23 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Figure 5. 5 Sequence Dia grams T erminal 1 3 4 5 8 6 7 V Function Control P ow er Pilot V alve Ignition Main V alve Fan Air Switch Interlocks PO V.
24 Eclipse V eri-Flame Instruction Manual 818 -2/02 Flame Rods This section describes the pr oper wiring, installation and sighting considerations for all sensors that can be used with a V eri-Flame .
25 Eclipse V er i-Flame Instruction Manual 818 - 2/02 1) K eep the flame r od as short as possible and at least 13 mm (1/2") awa y from any refractory . 2) Position the r od into the side of both the pilot and main flames, pref erably at a descending angle to minimize dr ooping of the flame rod against burner parts, as sho wn in Figure 6.
26 Eclipse V eri-Flame Instruction Manual 818 -2/02 I NTRODUCTION Flame Signal Strength T est Pr ocedures 7 This section describes the test pr ocedures that must be perf ormed after instal- lation to insur e that the V eri-Flame is operating properly; these pr ocedures are mandatory .
27 Eclipse V er i-Flame Instruction Manual 818 - 2/02 1) Man ually shut off the fuel supply to the pilot and the main burner . 2) Place system in pilot test mode (please r e fer to page 15). 3) Start the system normally . The controller should lock out*; if it doesn’ t, then the controller is detecting a false flame signal (see Section 6).
28 Eclipse V eri-Flame Instruction Manual 818 -2/02 I NTRODUCTION 8 This section is divided into tw o parts: • The first part describes the maintenance pr ocedures. • The second part describes troubleshooting pr ocedures, from identifying pr ob- lems to interpr eting the operating conditions by the lit LEDs on the fr ont cove r .
29 Eclipse V er i-Flame Instruction Manual 818 - 2/02 T R OUBLESHOO TING Check main valve closed switch. No voltage on V (or D). Check air pressure switch adjustment. Check air filter . Check blower rotation. Check outlet pr essur e from blow er . No voltage on 6 after 8 is on.
30 Eclipse V eri-Flame Instruction Manual 818 -2/02 LED S T A TUS This section describes the status of operating conditions based on the LED or combination of LEDs which are lit on the fr ont cov er of each V eri-Flame model.
31 Eclipse V er i-Flame Instruction Manual 818 - 2/02 T able 8.2 LED Status & Conditions for V eri-Flame Purg e Models LED( S ) L IT P OSSIBLE C AUSES INTERLOCKS CLOSED SYSTEM ERR OR 1) The interlocks are closed (normal operation), pow er on terminal 7.
32 Eclipse V eri-Flame Instruction Manual 818 -2/02 T able 8.3 LED Status & Conditions for V eri-Flame Modulation Models Modulation Model LED( S ) L IT P OSSIBLE C AUSES SYSTEM ERR OR 1) The flame detected is out of sequence , flame signal light is on.
33 Eclipse V er i-Flame Instruction Manual 818 - 2/02 I NTRODUCTION 9 This section co vers how the optional remote displa y is used with the V eri-Flame . The remote displa y provides LCD messages which monitor the status of the V eri- Flame’ s functions as w ell as an y lock out conditions.
34 Eclipse V eri-Flame Instruction Manual 818 -2/02 T able 9.1 V eri-Flame Operating Sequence PO WER ON W as internal safe start check successful? EXTERNAL INTERLOCK CHECKS Is flame signal present? BURNER ST AR T -UP (see next page) YES NO YES NO YES NO YES NO V arious lockout messages Fan output is energized; modu- lator is sent to low fir e.
35 Eclipse V er i-Flame Instruction Manual 818 - 2/02 T able 9.1 V eri-Flame Operating Sequence (continued) BURNER ST AR T -UP Is volta g e pr esent at air flo w switch within ten seconds? Is flame signal present? (see next page) Spark turns off at end of TFI; sequence dela y ed 5 seconds.
36 Eclipse V eri-Flame Instruction Manual 818 -2/02 T able 9.1 V eri-Flame Operating Sequence (continued) BURNER ST AR T -UP (continued) Is flame signal present? NO Modulator sent to automatic 20 seconds after main valve is energized. Pilot will shut off 10 seconds after main flame is energized.
37 Eclipse V er i-Flame Instruction Manual 818 - 2/02 T able 9.1 V eri-Flame Operating Sequence (continued) BURNER SHUTDO WN Shutdo wn is started b y opening the operating interlock cir cuit. Is volta g e pr esent at interlocks? YES NO Fuel valves de-energized; fan energized for 15 seconds.
38 Eclipse V eri-Flame Instruction Manual 818 -2/02 Lockout For purge & modulation models: Combustion air flow limit switch opened for more than two seconds once initially proven.
39 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Lockout Main valve has been energized and main flame proven during trial for ignition. St at us Pilot valve is de-energized and main flame is on. Lockout For purge and no purge models: Main valve closed switch is open before start-up or after burner shutdown.
40 Eclipse V eri-Flame Instruction Manual 818 -2/02 Hold Flame signal—actual, induced, or runaway scanner—is detected be- fore start-up or after shutdown. The fan is energized. If the cause is corrected within 30 seconds, as in afterburn, the control will turn off the fan and continue the sequence.
41 Eclipse V er i-Flame Instruction Manual 818 - 2/02 C ONVERSION F A CT ORS Appendix Metric to English. F ROM T O M UL TIPL Y BY cubic meter (m 3 ) cubic f oot (ft 3 ) 35.31 cubic meter/hour (m 3 /h) cubic foot/hour (cfh) 35.31 degr ees Celsius (°C) degrees Fahrenheit (°F) (°C x 1.
I LLUSTRA TED P AR TS L IST Litho in USA Instruction Manual 818 2/02 Straight U .V . scanner 5600-91 49600-91 NEMA 4 U .V . scanner 5600-91N4 20898 90˚ U .V . scanner 5600-90A 49600-90 I.R. scanner 5600-92B 49600-92 Self-check scanner 5602-91 49602-91 10-f oot cable f or self-chec k scanner 5602-91-7 49602-91-7 Scanner suppor t (max.
Ein wichtiger Punkt beim Kauf des Geräts Eclipse Combustion 5600 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Eclipse Combustion 5600 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Eclipse Combustion 5600 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Eclipse Combustion 5600 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Eclipse Combustion 5600 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Eclipse Combustion 5600 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Eclipse Combustion 5600 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Eclipse Combustion 5600. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Eclipse Combustion 5600 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.