ZONEKIT2ZCAR WeatherMaker® Two-Zone Installation and Start-Up Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. TABLE OF CONTENTS PAGE Safety Considerations .
Step 2—Wiring To prevent personal injury or possible equipment damage, disconnect the power supply before routing wire. All wiring must comply with local, state, and national codes.
2. Properly seal joint using duct tape, mastic, or other approved method. Do not allow mastic to come in contact with actuator. 3. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check your local codes.) (See Fig. 7.) NOTE: All zone dampers and ductwork must be properly sup- ported according to local codes or SMACNA standards.
Step 5—Install Barometric Bypass Damper NOTE: The barometric bypass damper is a critical part of the WeatherMaker Two-Zone System for control of minimum airflow and noise reduction. It is recommended that the bypass be installed. The bypass should be installed according to local codes and SMACNA standards.
In automatic changeover, the zoning system works on a first come first serve basis. If 1 zone is calling for heating and the other for cooling, the zone which sent its demand to the I/O center first will operate the equipment in that mode until that zone is satisfied.
Fig. 12—WeatherMaker Two-Zone Circuit Board with Standard Thermostat Wiring A97293 3 Thermostat Zone 2 Y 2 Y 1 R W 1 W 2 C G Thermostat Zone 1 Y 2 Y 1 R W 1 W 2 C Sensors HP Duct Equipment R c.
NOTE: An HP temperature sensor must be used with a heat pump application using electric strip heat. This is necessary in case the DTO is set to the Off position. Timeguard The WeatherMaker Two-Zone provides equipment protection with an internal 5-minute timeguard delay.
timer will start counting down 15, 14, 13...0 minutes. Once the timer expires the control will allow a new mode to restart the equipment. The internal time, as well as the cooling 5-minute timeguard can be cleared by using the comprotec override feature.
TROUBLESHOOTING This section contains information to assist you in troubleshooting problems and errors associated with the WeatherMaker Two-Zone system. See Table 2. Step 1—System Diagram, Jumpers, and Switches NOTE: For correct control board operation, it must have either a sensor attached or a 10k resistor in place at the duct and HP inputs.
I Red LED—Displays ON when fan is energized. J Red LED—Displays ON when first-stage cooling is energized. K Red LED—Displays ON when second-stage cooling is energized. L Red LED—Displays ON when reversing valve is ener- gized. M Red LED—Displays ON when first-stage heat is energized.
Table 3 shows a temperature/ohm/voltage relationship to help aid in troubleshooting the WeatherMaker Two-Zone System. This table will evaluate both the Duct/HP temperature sensor operation.
→ Fig. 17—Typical Fan Coil With Single-Speed Air Conditioner A97298 SINGLE-SPEED AIR CONDITIONER TYPICAL FAN COIL C Y G W2 W3 C R Y/Y2 O L E RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM See notes 1 and 3 * * * * * Y1 * * → Fig.
→ Fig. 21—Typical Fan Coil With 2-Speed Air Conditioner A97302 2-SPEED AIR CONDITIONER TYPICAL FAN COIL R G R C W2 Y/Y2 E W3 L O Y1 C Y2 Y1 RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM See notes 1, 2, and 3 * * * * * → Fig.
→ Fig. 23—Single-Stage Furnace With Single-Speed Heat Pump A97304 SINGLE-STAGE FURNACE TWO-ZONE SYSTEM INTERFACE CONTROL R GF RF WF R GT E HP O HP OT Y HP C W2 Y O RH G W2 .
→ Fig. 27—Single-Stage Furnace With 2-Speed Heat Pump A97308 2-SPEED HEAT PUMP SINGLE-STAGE FURNACE R G R C W Y C Y2 W3 RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM W2 Y1 O See notes 2, 5, 6, 7, 9, 10, and 11 → Fig.
→ Fig. 29—Typical Fan Coil With 2-Speed Heat Pump A97310 RH G W2 W1 Y1 Y2 O B RC 2-SPEED HEAT PUMP TYPICAL FAN COIL C G W2 Y/Y2 R C W3 L E Y1 R W2 O W3 Y1 Y2 O TWO-ZONE SYSTEM See notes 1, 2, 3, 9, and 11 * * * * * → Fig.
Ein wichtiger Punkt beim Kauf des Geräts Carrier ZONEKIT2ZCAR (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Carrier ZONEKIT2ZCAR noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Carrier ZONEKIT2ZCAR - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Carrier ZONEKIT2ZCAR reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Carrier ZONEKIT2ZCAR erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Carrier ZONEKIT2ZCAR besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Carrier ZONEKIT2ZCAR verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Carrier ZONEKIT2ZCAR. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Carrier ZONEKIT2ZCAR gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.