D400-13-00 1 I56-555-09R DH400ACDCP Air Duct Smoke Detector INST ALLA TION AND MAINTENANCE INSTRUCTIONS 3825 Ohio A venue , St. Charles, Illinois 60 174 1-800-SENSOR2, F AX: 63 0-377-6495 www .
[3] Contents Of The Duct Detector Kit 1. Complete housing base and cov er assembly 2. T wo #1 0 sheet metal mounting scre ws 3. T wo sampling tube filter s 4. One test magnet 5. Drilling template 6. T wo 5/16 O-rings 7. T wo rubber tube bushing seals 8.
feet per minute . Be sur e to check engineering specifications to ensure that the air velocity in the duct falls within these parameter s . If necessary , use a velocity meter to check the air velocity in the duct. [5.2] Drill The Mounting Holes R emo ve the paper backing from the mounting template supplied.
[5.4.1] Installation For Ducts Less Than 8 Feet Wide 1. If the tube is longer than the width of the air duct, drill a 3/4-inch hole in the duct directly opposite the hole already cut for the inlet tube. If the tube is shorter than the width of the air duct, install the end plug into the inlet tube as shown in Figure 4.
Install the inlet tube as follow s: 1. Drill a 3/4-inch hole in the duct directly opposite the hole already drilled for the inlet tube . 2. Slide the inlet tube with the flange into the centermost housing bushing. Position the tube so that the arr ow s point into the air flow .
24V 120 VAC 220/240 VAC 1 2 1 2 13 14 AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 15 16 17 18 19 20 N.C. C. N.O. N.O. C. N.C. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS.
24V 120 VAC 220/240 VAC 1 2 12 13 14 AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 15 16 17 18 19 20 N.C. C. N.O. N.O. C. N.C. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS.
[5.6] Install The Filters T o install the sampling tube filters , simply push the filter adapter into the exhaust tube, and push the filter onto the adapter tube on the left, as shown in Figure 9. Install the other filter ov er the end of the inlet sampling tube .
[6.1] Smoke Entr y T ests [6.1.1] Air Flow T o verify sufficient sampling of ducted air , use a manometer to measure the differ ential pressure created from air flow across the sampling tubes . The pr essure should measure no less than 0.0 1 inches of water and no greater than 1.
the R T S45 1/R T S45 1KEY manual. The DH400A CDCP duct detector can be reset by the R T S45 1/R T S45 1KEY . If a sys- tem control panel is used, the panel itself may also requir e resetting. T o install the R T S45 1/R T S45 1KEY , connect the device as shown in Figur e 8; wir e runs must be limited to 25 ohms or less per interconnecting wire .
3. V acuum the photo chamber . Use clean compr essed air to blow it clean. 4. R eplace the screen by aligning the arro w on top with the field test port on the detector . Press the screen into place . It should fit tightly on the chamber . 5. R eplace the detector co v er and rotate it clockwise to lock it in place .
[8] Model DH400ACDCP Air Duct Smoke Detector Specifications Description HV A C air duct mounted ionization or photoelectronic smoke detector for separately power ed sy stems or stand alone sys- tems. A uxiliary alarm relay contacts pr ovide fan contactor shutdo wn to pr e vent HV A C circulation of smoke .
Electrical Specifications P o wer supply v oltage: 20-29 VDC 24 V A C 5 0-60-Hz 120 V A C 50-60 Hz 220/240 V A C 50-60 Hz Input capacitance: 27 0 µ F max. 27 0 µ F max. N/A N/A R eset v oltage: 3.0 VDC min. 2.0 V A C min. 1 0 V A C min. 20 V A C min.
NOTES D400-13-00 14 I56-555-09R.
NOTES D400-13-00 15 I56-555-09R.
D400-13-00 16 I56-555-09R © Sy stem Sensor 1997 DETECTOR TEST LOG Detector Identification Infor mation Manufacturer and Serial Date Detector Model: ______________________ Number: ___________________.
Ein wichtiger Punkt beim Kauf des Geräts System Sensor DH400ACDCP (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie System Sensor DH400ACDCP noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für System Sensor DH400ACDCP - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von System Sensor DH400ACDCP reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über System Sensor DH400ACDCP erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon System Sensor DH400ACDCP besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von System Sensor DH400ACDCP verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit System Sensor DH400ACDCP. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei System Sensor DH400ACDCP gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.